Hantech 4619277 User manual

OPERATING INSTRUCTIONS
BEDIENUNGSANLEITUNGEN
Artikelnummer:4619278(DE)
4619277(CH)


EN
1
Content
I.Attention Matters.................................................................................2
II.Featuresand Components.................................................................5
III.Control Setting.................................................................................6
IV.Protection function............................................................................8
V.Installation and adjustment..................................................................9
VI.Drainage Instructions..........................................................................11
VII.Maintenance.....................................................................................12
VIII.Out-of-seasonsave.........................................................................13
IX.Troubleshooting.................................................................................21
X.Addendum.........................................................................................23
The refrigerant used in mobile air conditioners is the environmentally friendly
hydrocarbon R290.This refrigerant is odorless, and compared to the alternative
refrigerant, the R290 is an ozone-free refrigerant, and its effect is very low.
Please read the instructions before use and repair.
The drawings provided in this manual may not be the same as the physical objects.
Please refer to the physical objects.

EN
2
I.Attention Matters
Warning matters:
1. Do not use means to accelerate the defrosting process or to clean,
other than those recommended by the manufacturer.
2. The appliance shall be stored in a room without continuously
operating ignition sources (for example: open flames, an operating gas
appliance or an operating electric heater.)
3. Do not pierce or burn.
4. Be aware that refrigerants may not contain an odour.
5. Appliance shall be installed, operated and stored in a room with a
floor area larger than 12 m2
6. Keep any required ventilation openings clear of obstruction;
7. Servicing shall be performed only as recommended by the
manufacturer.
8. The appliance shall be stored in a well-ventilated area where the
room size corresponds to the room area as specified for operation.
9. Anyperson who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an
industry-accredited assessmentauthority, which authorises their
competence to handle refrigerants safely in accordance with an industry
recognised assessment specification.
10.Servicing shall only be performed as recommended by the
equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person
competent in the use of flammable refrigerants.
11. All working procedure that affects safety means shall only be carried
by competentpersons.

EN
3
Notes:
*The air conditioning is only suitable for indoor use, and is not suitable
for other applications.
*Follow local grid interconnection rules while installing the air
conditioning and ensure that it is properly grounded. If you have any
question on electrical installation, follow the instructions of the
manufacturer, and if necessary, ask a professional electrician to install
it.
*Place the machine in a flat and dry place and keep a distance of above
50cm between the machine and the surrounding objects or walls.
*After the air conditioning is installed, ensure that the power plug is
intact and firmly plugged into the power outlet, and place the power cord
orderly to prevent someone from being tripped or pulling out the plug.
*Do not put any object into the air inlet and outlet of the air conditioning.
Keep the air inlet and outlet free from obstructions.
*When drainage pipes are installed, ensure that the drainage pipes are
properly connected, and are not distorted or bended.
* While adjusting the upper and lower wind-guide strips of the air outlet,
pluck it with hands gently to avoid damaging wind-guide strips.
*When moving the machine, make sure that it is in an upright position.
*The machine should stay away from gasoline, flammable gas, stoves
and other heat sources.
* Don't disassemble, overhaul and modify the machine arbitrarily,
otherwise it will cause a machine malfunction or even bring harm to
persons and properties. To avoid danger, if a machine failure occurs,
ask the manufacturer or professionals to repair it.
* Do not install and use the air conditioning in the bathroom or other
humid environments.
* Do not pull the plug to turn off the machine.
* Do not place cups or other objects on the body to prevent water or
other liquids from spilling into the air conditioning.
*Do not use insecticide sprays or other flammable substances near the
air conditioning.
* Do not wipe or wash the air conditioning with chemical solvents such

EN
4
as gasoline and alcohol. When you need to clean the air conditioning,
you must disconnect the power supply, and clean it with a half-wet soft
cloth. If the machine is really dirty, scrub with a mild detergent.
* The appliance can be used by children aged from 8 years and above
and persons with reduced physical, sensory or mental capabilities if
they have been given supervision or instruction concerning use of the
appliance in a safe way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and maintenance shall not
be made by children without supervision.
If the supply cord is damaged, it must be replaced by the manufacturer,
its service agent or similarly qualified persons in order to avoid a
hazard.
The appliance shall be installed in accordance with national wiring
regulations.
Do not operate your air conditioner in a wet room such as a bathroom or
laundry room.
Transportation, marking and storage for units
1. Transport of equipment containing flammable refrigerants
Compliance with the transport regulations
2. Marking of equipment using signsCompliance with local regulations
3. Disposal of equipment using flammable refrigerants Compliance with
national regulations
4. Storage of equipment/appliances The storage of equipment should
be in accordance with the manufacturer’s instructions.
5. Storage of packed (unsold) equipment Storage package protection
should be constructed such that mechanical damage to the
equipment inside the package will not cause a leak of the refrigerant
charge.
The maximum number of pieces of equipment permitted to be stored
together will be determined by local regulations.

EN
5
II.Features and Components
1、Features
*Brand new appearance, compact structure, smooth line, simple and generous shape.
*Functions of refrigeration, dehumidification, air supply and continuous drainage
*Outdoor interface is set high to facility assembly and keep the smooth flow of the heat
pipe.
*LED displays the control panel, beautiful and fashionable, with high-quality remote
control.It adopts a user-friendly remote control design.
*Air filtration capability.
*Timing switch function.
*Protection function of automatically restarting the compressor after three minutes, a
variety of other protection functions.
The Max operation temperature for the air conditioner Cooling: 35/24℃; heating:20/12
℃; Temperature
operation range: 7-35℃.
2、 Component

EN
6
III. Control Setting
1.Control panel operation instructions
1)operation interface:
1: When the machine is powered on for the first time, the buzzer will play power-on
music, and then the machine will get into standby status.
2: Power Key: press the key to turn on and turn off the machine. In the case of power
on, press the key to turn off the machine; in the case of power off, press the key to
turn on the machine.
3: Mode Selection Key: In the case of power on, press the key to switch between
cooling → fan → dehumidifying mode.
4: Up Key and Down Key: press the two keys to change the setting temperature or
setting time, operate as follows:
While setting temperature, press up key or down key to select the required
temperature (not available in fan or dehumidifying mode).
While setting time, press up key or down key to select the required time.
5: Wind Speed Selection Key:
排热管组
Exhaust Pipe Assembly
Window Sealing Plate Assembly

EN
7
1)In cooling and fan mode, press the key to select high,low wind speed operation.
But limited by
anti-cold conditions, under certain conditions, it may not run according to the set
wind speed.
2)In dehumidifying mode, pressing the key is invalid, and the fan will forcibly choose
low wind speed operation.
6: Timing Key:
In the case of power on, press the key to close timing; in the case of power off, press
the key to open timing.
Press the key, when the timing symbol flashes, press up and down key to select the
required timing value.
Timing values can be set in 1-24 hours and the timing value is adjusted up or down by
one hour.
7: Sleep Mode:
In the cooling Mode,Press the UP and Fan Key to turn on the sleep mode,then the unit
will work on Energy-Saving and quiet type.
2.operation instructions of remote control
1) The remote control Panel is as follows:
1
2
3
4
5
6
7
8
9

EN
8
Instructions of key operation of the high-quality remote control are as follows:
1.Power: Press the key to turn on or turn off the machine.
2.Timer: press the key to set timing.
3. Down: press -the key to reduce temperature and timing set value.
4. Mode: press the key to switch between cooling, fan, dehumidifying mode.
5. Up: press +the key to increase temperature and timing set value.
6. Fan: press the key to select high, low wind speed.
7. Sleep Mode: Press the key to turn on the sleep mode.
8. Swing: Press the louver will swing up and down(optional).
9.℃&℉Change:Press to change ℃and ℉display .
IV. Protection function
3.1、Frost Protection Function:
In cooling, dehumidifying or economic power saving mode, if the temperature of
the exhaust pipe is too low, the machine will automatically enter protection status;
if the temperature of the exhaust pipe rises to a certain temperature, it can
automatically revert to normal operation.
3.2、Overflow Protection Function:
When water in the water pan exceeds the warning level, the machine will
automatically sound an alarm, and the "FULL" indicator light will flash. At this
point, you need to move the drainage pipe connecting the machine or the water
outlet to sewer or other drainage area to empty the water (details see
Drainage
Instruction
s at the end of this chapter). After the water is emptied, the machine
will automatically return to the original state.
3.3 Automatic Defrosting (cooling models have this function): The machine has
automatic defrosting function.Defrosting can be achieved through four - way
valve reversing.
3.4、Protection Function of the Compressor
To increase the service life of the compressor, it has a 3-minute delay booting
protection function after the compressor is turned off.

EN
9
V.Installation and adjustment
1.Installation:
Warning: before using the mobile air conditioning, keep it upright for at least two hours.
The air conditioning can be easily moved in the room. In the moving process, ensure that the
air conditioning is in the upright position and the air conditioning should be placed on a flat
surface. Do not install and use the air conditioning in the bathroom or other humid
environments.
1.1 Install the heat pipe assembly (as shown in Fig.1)
Figure 1
1 ) take out the outer connector assembly and the exhaust pipe assembly, and
remove the plastic bags;
2)insert the heat pipe assembly (the end of the exhaust joint) into the back panel
vent slot (push to the
left) and complete the assembly (as shown in figure 1).
1.2 Installation of window sealing plate components
1)Half open the window,and mount the window sealing plate assembly to the window (as
shown in Fig.2 and
Fig.3).Components can be placed in horizontal and vertical direction.
2)Pull various components of the window sealing plate assembly open, adjust their
opening distance to bring
both ends of the assembly into contact with the window frame, and fix various
components of the
assembly.1.2 Install the window sealing plate assembly

EN
10
Notes:1)the flat end of the exhaust pipe joints must be snapped into place.
2)The pipe cannot be distorted nor has substantial turning (greater than 45 °). Keep
the ventilation of the exhaust pipe not blocked.
Figure 2Figure 3
1.3 Install the body
1)Move the machine with installed heat pipe and fittings before the window, and the
distance between the body
and walls or other objects shall be least 50 cm (as shown in Fig.4).
Figure4
3)Elongate the exhaust pipe and snap the flat end of the exhaust pipe joints into the hole
of the window sealing
plate assembly (as shown in Fig.5 and Fig.6) .
Notes:1、the flat end of the exhaust pipe joints must be snapped into place.
3、 The pipe cannot be distorted nor has substantial turning (greater than 45 °). Keep the
ventilation of the exhaust pipe not blocked.

EN
11
Figure 5Figure 6
Important Notice:
The length of the exhaust hose shall be 280~1,500mm, and this length is based on the
specifications of the air conditioning. Do not use extension tubes or replace it with other different
hoses, or this may cause a malfunction. Exhaust host must be not blocked; otherwise it may
cause overheating.
VI.Drainage Instructions
This machine has two drainage methods: manual drainage and continuous drainage.
1.Manual drainage:
1) When the machine stops after the water is full, turn off the machine power and unplug
the power plug.
Notes:Please move the machine carefully, so as not to spill the water in the water
pan at the bottom of the
body.
2) Place the water container below the side water outlet behind the body.
3) Unscrew the drainage cover and unplug the water plug, the water will automatically
flow into the water container.

EN
12
Notes:1)Keep the drainage cover and the water plug properly.
2)During drainage, the body can be tilted slightly backwards.
3)If the water container cannot hold all the water, before the water container is
full, stuff the water outlet
with the water plug as soon as possible to prevent water from flowing to the
floor or the carpet.
4)When the water is discharged, stuff the water plug, and tighten the drainage
cover
2.Continuous drainage (Optional) (only applicable to dehumidifying mode), as shown in
figure:
1) Unscrew the drainage cover, and unplug the water plug.
2) Set the drainage pipe into the water outlet.
3) Connect the drainage pipe to the bucket.
VII. Maintenance
Cleaning: before cleaning and maintenance, turn off the machine and unplug the plug.
1.Clean the surface
Clean with surface of machine with a wet soft cloth. Don't use chemicals, such as
benzene, alcohol, gasoline, etc; otherwise, the surface of the air conditioning will be

EN
13
damaged or even the whole machine will bedamaged.
2.Clean the filter screen
If the filter screen is clogged with dust, and the effectiveness of the air conditioning is
reduced, be sure to clean the filter screen once every two weeks.
3.Clean the upper filter screen frame
1)Unscrew one screw fixed by EVA filter net and back shell with screwdriver, and take out EVA
filter net.
2)Put the EVA filter screen into warm water with neutral detergent (about 40℃ / 104℉) and
dry it in the shade after rinsing clean.
VIII.Unit Storage:
1:Unscrew the drainage cover, unplug the water plug, and discharge the water in the water pan
into other water containers or directly tilt the body to discharge the water into other containers.
2:Turn on the machine, adjust it to low-wind ventilation mode, and maintain this state until the
drainage pipe becomes dry, so as to keep the inside of the body in a dry state and prevent it
from mildewing.
3:Turn off the machine, unplug the power plug, and wrap the power cord around the wrapping
post; install the water plug and the drainage cover.
4:Remove the exhaust pipe and keep it properly.
5:Cover the air conditioning with a plastic bag. Put the air conditioning in a dry place, keep it out

EN
14
of the reach of children, and take dust control measures.
6:Remove batteries of the remote control and keep them properly.
Note: ensure that the body is placed in a dry place and keep all machine components properly.
IX.Troubleshooting
1. Information on servicing
1) Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating
system, the following precautions shall be complied with prior to conducting work on the
system.
2) Work procedure Work shall be undertaken under a controlled procedure so as to minimise
the risk of a flammable gas or vapour being present while the work is being performed.
3) General work area All maintenance staff and others working in the local area shall be
instructed on the nature of work being carried out. Work in confined spaces shall be avoided.
The area
around the workspace shall be sectioned off. Ensure that the conditions within the area
have been made safe by control of flammable material.
4) Checking for presence of refrigerant The area shall be checked with an appropriate
refrigerant detector prior to and during work, to ensure the technician is aware of potentially
flammable atmospheres. Ensure that the leak detection equipment being used is suitable for
use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
5) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or
CO2 fire extinguisher adjacent to the charging area.
6) No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing
any pipe work that contains or has contained flammable refrigerant shall use any sources
of ignition in such a manner that it may lead to the risk of fire or explosion. All possible
ignition sources, including cigarette smoking, should be kept sufficiently far away from the

EN
15
site of installation, repairing, removing and disposal, during which flammable refrigerant
can possibly be released to the surrounding space. Prior to work taking place, the area
around the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. “No Smoking” signs shall be displayed.
7) Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into
the system or conducting any hot work. A degree of ventilation shall continue during the
period that the work is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
8) Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to
the correct specification. At all times the manufacturer’s maintenance and service
guidelines shall be followed. If in doubt consult the manufacturer’s technical department
for assistance.
The following checks shall be applied to installations using flammable refrigerants:
– The charge size is in accordance with the room size within which the refrigerant
containing parts are installed;
– The ventilation machinery and outlets are operating adequately and are not obstructed;
– If an indirect refrigerating circuit is being used, the secondary circuit shall be checked
for the presence of refrigerant;
– Marking to the equipment continues to be visible and legible. Markings and signs that
are illegible shall be corrected;
– Refrigeration pipe or components are installed in a position where they are unlikely to
be exposed to any substance which may corrode refrigerant containing components,
unless the components are constructed of materials which are inherently resistant to
being corroded or are suitably protected against being so corroded.
9) Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is necessary to continue operation, an
adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.

EN
16
Initial safety checks shall include:
• That capacitors are discharged: this shall be done in a safe manner to avoid possibility
of sparking;
• That there no live electrical components and wiring are exposed while charging,
recovering or purging the system;
• That there is continuity of earth bonding.
2. Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall be disconnected from
the equipment being worked upon prior to any removal of sealed covers, etc. If it isabsolutely
necessary to have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is affected.
This shall include damage to cables, excessive number of connections, terminals not made to
original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the
purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to working
on them.
3. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring
that this will not exceed the permissible voltage and current permitted for the equipment
in use.
Intrinsically safe components are the only types that can be worked on while live in the
presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may
result in the ignition of refrigerant in the atmosphere from a leak.

EN
17
4. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.
5. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
6. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall
be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source
of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set
at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant
employed and the appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use
of detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through
the system both before and during the brazing process.
7. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered

EN
18
to:
• Remove refrigerant;
• Purge the circuit with inert gas;
• Evacuate;
• Purge again with inert gas;
• Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system
shall be “flushed” with OFN to render the unit safe. This process may need to be
repeated several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting to atmosphere, and
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is
within the system. When the final OFN charge is used, the system shall be vented down
to atmospheric pressure to enable work to take place. This operation is absolutely vital if
brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there
is ventilation available.
8. Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
– Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimise the amount of
refrigerant contained in them.
– Cylinders shall be kept upright.
– Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
– Label the system when charging is complete (if not already).
– Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system it shall be pressure tested with OFN. The system shall be
leak tested on completion of charging but prior to commissioning. A follow up leak test
shall be carried out prior to leaving the site.
This manual suits for next models
1
Table of contents
Languages:
Other Hantech Air Conditioner manuals
Popular Air Conditioner manuals by other brands

York
York HVHC 07-12DS Installation & owner's manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

GE
GE AEC14 Owner's manual and installation instructions

Argo
Argo SWAN EVO operating instructions

Friedrich
Friedrich WallMaster WS10 Installation and operation manual

Panasonic
Panasonic CU-2S18NBU-1 Service manual