
Literature # 900040 2019
INSTALLATION
Carefully unpack the pump and select a location on the floor. The pump must be level and the inlet must be
below the lowest drain, either coil or furnace. Remove and discard the shipping pin that is located in the side
of the switch cover box. This releases the float for fully automatic operation. (Not used on A2SA)
PIPING—Run flexible tubing or pipe
from the evaporator and furnace to
the pump. Insert the pipe into the
drain inlet hole. Make sure the pipe
does not interfere with the float.
Cut an angle on the inlet pipe so
that it doesn’t close off against the
bottom of the pump. See Figure 1 –
exploded detail.
Connect 3/8” NPT piping to the
discharge port. Extend this piping
or tubing straight up as high as
necessary. (Do not extend this
tubing past the head/GPH of the
pump installed). Do not kink the
tubing, as this will block the flow.
From this high point, slope the
discharge tubing downward to a
point above the drain, then turn
down and extend to a point below
or level with the bottom of the
condensate pump. If it is not
possible to slope the discharge
tubing downwards, make an inverted “U” trap directly above the pump at the highest point. (Figure 1) A
check valve is required and should be of a soft seat swing check design. A spring loaded ball check is
permissible if the lift is one half of the pump shut off level and the spring pressure is equal to, or less than one
(1) psi.
ELECTRICAL CONNECTIONS—review precautions on previous page
LINE VOLTAGE—Connect power cord to the proper voltage as indicated on the motor nameplate. Connect
only to a source of constant power, not an intermittent source such as a fan or limit control circuit. Connect
the back and white wires to the appropriate voltage source and the green wire to ground.
Models with an “X” designation are equipped with a LOW VOLTAGE—AUXILIARY
SAFETY SWITCH–Connect the leads of auxiliary safety switch to the thermostat
control circuit of the air conditioner/furnace. This will disrupt the thermostat
demand in a high water condition. (Figure 2)
CAUTION –Thermostat demand disruption should not be utilized if cooling or
heating requirements are a necessity. An alarm system should be used with the
auxiliary switch instead.
OPERATION
After proper installation, the operation of the HARTELL condensate pump is automatic. Water is collected in
the reservoir and pumped out when the float raises to a pre-set point. As the water level goes down the float
turns off the motor at another pre-set point. Under most circumstances the pump requires little maintenance
for efficient operation. If a problem occurs, please refer to the maintenance instructions below.
Figure 1
Figure 2