vizo 24/28
5.1 Installer Testing & Commissioning Tips
•The installer shall instruct the user in the operation
of the boiler, safety devices contained within the
boiler and instruction on how to re-pressurise the
system if the water pressure falls. The installer
should then hand over the instructions with the
Benchmark Logbook that has been completed.
•The user should be instructed to keep the
instructions in a safe place for servicing and future
reference.
•It is important to keep the boiler clear of dust
during the installation. In particular, do not allow
debris to enter the top of the boiler where the flue
connection is made. This may cause the fan outlet
to get blocked or combustion chamber to fill with
debris and will, of course, cause the boiler to fail to
ignite on first ignition. It is recommended that you
check the fan outlet before you light the boiler.
•Before you fit the boiler ensure that the pipe work
that you are installing is connected to the
appropriate connections on the boiler i.e. cold
water pipe to cold water inlet, hot water outlet to
the hot water tap etc.
•Because the boiler is actually operated, at the end
of each production stage, a small amount of water
is retained within the boiler when packed. Please
ensure that you spin the pump rotor manually
before firing the boiler.
•It is important that the boiler must be used in
conjunction with a Heat Line approved flue and all
flue connections are correctly sealed.
•Remember to flush out the system, both cold and
hot, in order to remove the debris from the system.
This should be done particularly where boilers are
being fitted to existing radiator circuits.
•Refer to BS 7593:1992 for the details to clean
DHW and Central heating system.
•This boiler has been factory set and does not
require any adjustments to the gas valve or fan
speed.
•Remember to release the small cap on top of the
auto air purge device on the pump, 1 turn, before
filling. This will ensure that air is removed as the
system fills.
•Do not use the pressure relief valve as a means
of flushing the system, please use the valve below
the pump. Discharging water from the system from
the pressure relief valve may allow water to seep
after you have left the job, causing the boiler to
lose pressure and debris to collect on the seating.
•The boiler is fitted with inlet filters both on the
cold water inlet and the central heating return. If
you are unable to obtain hot water at the faucet it is
likely that the cold water inlet valve filter has
become blocked, whilst blockage of the filter on
central heating return valve will cause the heater to
lock out at the overheat thermostat as the water
flow is reduced.
•If you are able to obtain hot water but not heating
it is also advisable to check the clock connections
and that the room thermostat and time clock are
calling for heat.
•Remember that after hot water draw off there is a
45 sec delay before the heating will fire up if No.3
dipswitch is in the OFF position, see fig 19 on
page 21
•When commissioning the boiler check the inlet
pressure is at 20mbar and burner pressure against
the Technical data on page 5.
•Note an anti-cycle delay time can be set up to a
maximum of 255 seconds by adjusting
potentiometer 2 as described in section 15.5 on
page 21.
If you experience any problems please refer to the
installation and commissioning guidelines within the
boiler instruction manual. If necessary, please contact
Heat Line
TM
Service Enquiries, in the UK, for further
advice and assistance on 0870 777 8318, in Ireland
call 01 466 4664.
NOTE – FOR INSTALLERS:
REMEMBER IT IS A LEGAL REQUIREMENT
TO COMPLETE THE BENCHMARK CODE OF
PRACTICE LOGBOOK BEFORE LEAVING
THE INSTALLATION.
5. General Installation
09