•The user should be instructed to keep the instructions in a safe place for
servicing and future reference.
•It is important to keep the boiler clear of dust during the installation. In
particular do not allow debris to enter the top of the boiler where the flue
connection is made.
•Before you fit the boiler ensure that the pipe work that you are installing is
connected to the appropriate connections on the boiler i.e. cold water pipe to cold
water inlet hot water outlet to the hot water tap etc. See Figure 1 for detail.
•Please ensure that you spin the pump rotor manually before firing the boiler.
•Remember to thoroughly flush the water circuits after isolating the boiler
Remember to thoroughly flush the water circuits after isolating the boiler Remember to thoroughly flush the water circuits after isolating the boiler
Remember to thoroughly flush the water circuits after isolating the boiler in
in in
in
order to remove any fluxes and debris from them.
order to remove any fluxes and debris from them.order to remove any fluxes and debris from them.
order to remove any fluxes and debris from them. This should be done
This should be done This should be done
This should be done
particularly where boilers are being fitted to existing radiator circuits.
particularly where boilers are being fitted to existing radiator circuits. particularly where boilers are being fitted to existing radiator circuits.
particularly where boilers are being fitted to existing radiator circuits.
•R
RR
Refer to BS 7593:
efer to BS 7593:efer to BS 7593:
efer to BS 7593:2006
20062006
2006 for the details to clean DHW and Central heating system.
for the details to clean DHW and Central heating system. for the details to clean DHW and Central heating system.
for the details to clean DHW and Central heating system.
•This boiler has been factory set
This boiler has been factory set This boiler has been factory set
This boiler has been factory set but adjustment may be required to the Heating
but adjustment may be required to the Heating but adjustment may be required to the Heating
but adjustment may be required to the Heating
input in order to match the heating demand. This can be done using
input in order to match the heating demand. This can be done using input in order to match the heating demand. This can be done using
input in order to match the heating demand. This can be done using
potentiometer R29
potentiometer R29potentiometer R29
potentiometer R29.
..
. See section
See section See section
See section 15 for details.
15 for details. 15 for details.
15 for details.
•To ensure that air is vented from the pump and heat exchanger as the system
fills release the small vent caps (1 turn) of the air vents which are located on top
of the pump and at the top left hand side of the heat exchanger before filling.
•Do not use the pressure relief valve as a means of flushing the system
Do not use the pressure relief valve as a means of flushing the systemDo not use the pressure relief valve as a means of flushing the system
Do not use the pressure relief valve as a means of flushing the system please
use the valve below the pump. Discharging water from the system from the
pressure relief valve may allow debris to collect on the seating allowing water to
weep after you have left the job causing the boiler to lose pressure and shut
down.
•The boiler is fitted with inlet filters both on the cold water inlet and the central
heating return. If you are unable to obtain hot water at the tap it is likely that the
cold water inlet valve filter has become blocked whilst blockage of the filter on
central heating return valve will cause the heater to lock out at the overheat
thermostat as the water flow is reduced.
•If you are able to obtain hot water but not heating it is also advisable to check the
clock connections and that the room thermostat and time clock are calling for
heat.
•Remember that after hot water draw off there is a 45 sec delay before the
heating will fire up if No.S3 dipswitch is in the OFF position
see fig 22
.
•When commissioning the boiler check the gas inlet pressure is 20mbar (NG) or
37mbar for LPG.
•Note an anti-cycle delay time can be set up to a maximum of 255 seconds by
adjusting potentiometer R28 as described in section
15.1
.
If you experience any problems please refer to the installation and commissioning
guidelines within the boiler instruction manual. If necessary please contact Heat
LineTM Service Enquiries in the UK on 0870 777 8341 for further advice or technical
assistance on 0870 777 8318
0870 777 83180870 777 8318
0870 777 8318.
NOTE
NOTE NOTE
NOTE –
––
– FOR INSTALLERS:
FOR INSTALLERS: FOR INSTALLERS:
FOR INSTALLERS:
REMEMBER IT IS A REQUIREMENT TO COMPLETE THE BENCHMARK CODE OF
REMEMBER IT IS A REQUIREMENT TO COMPLETE THE BENCHMARK CODE OF REMEMBER IT IS A REQUIREMENT TO COMPLETE THE BENCHMARK CODE OF
REMEMBER IT IS A REQUIREMENT TO COMPLETE THE BENCHMARK CODE OF
PRACTICE LOGBOOK BEFORE LEAVING THE INSTALLATION. YOU ARE ALSO
PRACTICE LOGBOOK BEFORE LEAVING THE INSTALLATION. YOU ARE ALSO PRACTICE LOGBOOK BEFORE LEAVING THE INSTALLATION. YOU ARE ALSO
PRACTICE LOGBOOK BEFORE LEAVING THE INSTALLATION. YOU ARE ALSO
REQUIRED TO REGISTER THE INSTALLATION WITH C.O.R.G.I.
REQUIRED TO REGISTER THE INSTALLATION WITH C.O.R.G.I.REQUIRED TO REGISTER THE INSTALLATION WITH C.O.R.G.I.
REQUIRED TO REGISTER THE INSTALLATION WITH C.O.R.G.I. OR YOUR LOCAL
OR YOUR LOCAL OR YOUR LOCAL
OR YOUR LOCAL
AUTHORITY.
AUTHORITY.AUTHORITY.
AUTHORITY.