16 Betriebsanleitung_firestar_18-40_Lambda_Englisch_V1.6
8 BOILER STATUS
8.1 Unit off
In this condition the unit is switched off.
8.2 Burning phase
In the BURNING PHASE(2) condition wait to see
if the logs catch fire in the combustion chamber.
During 30 minutes an adequate flue temperature
(HEATING UP FROM MIN(P06)) is adjusted so
that it can be switched on into the HIGH
RUNNING PHASE(3) condition. If this flue
temperature is not set, it switches into the UNIT
OFF(1) condition and a fault is declared
accordingly.
In this condition it is possible to switch manually
into the UNIT OFF(1) condition.
8.3 High running phase
In the HIGH RUNNING PHASE(3) condition, after
lightings the logs, it tries to stabilise the
combustion and achieve the minimum boiler
temperature. The optional combustion control
(lambda control) is already activated at this time.
When reaching 65°C the boiler temperature (set
out in the program) is switched on into the control
phase. Should the flue temperature decrease in
this phase (under HEAT UP MIN(P06)),it
switches into the NEW START-UP(6).
8.4 Control phase
The CONTROL PHASE(4) condition carries out
actual boiler control, which splits into an output
and combustion control (OPTIONAL). If the boiler
temperature in this phase increases above the
maximum boiler temperature (BOILER
MAX(P02)), it switches into the READY(5)
condition. Should the flue temperature decrease
in this phase (HEAT UP MIN(P06)), it switches
into the NEW START-UP(6).
8.5 Ready
The maximal boiler temperature (BOILER
MAX(P02)) has been reached due to too low heat
capturing. Therefore the boiler has been switched
off. The boiler starts up again if the boiler
temperature falls 3°C below BOILER MAX(P02).
8.6 New start-up
The NEW START-UP(6) condition tries to re-
stabilise the combustion within a time limit
(adjustable via MAXIMUM RE-START(P07)). It
will always be activated if the flue temperature is
too low. If stable combustion adjusts again, it
switches immediately into the CONTROL
PHASE(4). Should a sufficient flue temperature
not be achieved after a specified time (under
HEAT-UP MIN(P06)), the boiler is switched off as
it is switched to the UNIT OFF(1) condition.
8.7 Re-heating
The RE-HEATING(7) condition is used for safe
operation for re-heating. If the customer re-heats
a larger amount of logs in operation, then this
operation is activated. The boiler then remains in
this condition for the time set. Should the boiler
temperature in the meantime increase above the
maximum boiler temperature, the boiler will be
switched off. After the set time, it switches to the
CONTROL PHASE(4) condition once an
adequate flue temperature is reached, and if the
flue temperature is too low (under HEAT UP
MIN(P06)), it is switched off and reported as a
fault. This function may only be activated by long
pressing the On/Off-switch in the STATUS MENU,
if the unit is in HIGH RUNNING(3) or CONTROL
PHASE(4).
8.8 Chimney sweeper
The CHIMNEY SWEEPING(8) condition is
available as a test mode for the chimney sweeper.
The boiler is precisely operated using rated output
and the chimney sweeper can carry out its test
measurements. The boiler usually runs high and
the chimney sweeper function is only activated
instead of the CONTROL PHASE(4). This
condition is left when deactivation occurs or when
the boiler maximum temperature is exceeded or
when the maximum chimney sweeping time is
exceeded (45min).