The FT Series Floor Standing, Combination Boiler Page 69
Index Default Parameter Description
1: EH Error History History fault code (E0~E9)
2: cE OFF Clear Error History Clearing of error History buer
3: In OFF System initialize System initialize to default
4: Fu GA Flow unit gallon / liter
5: St On Heat storage function Heat storage function On/O
6: OH 68°F (20°C) Maximum Outdoor Temperature Range: (Minimum Outdoor Temperature + 9°F) to 110°F
7: OL 30°F (-1°C) Minimum Outdoor Temperature Range: -4°F to (Maximum Outdoor Temperature -9°F)
8: FH 0Max fan Adjusts Maximum Fan Speed
Range: -30 - +30 Default 00 Note: Factory set - do not adjust
9: FL 0Min fan Adjusts Minimum Fan Speed Range: -30 -+30 Note: Factory set - do not adjust
10: dr NO Delete running time Delete running time
11: dI NO Delete igniting times Delete igniting times
12: bt 0Outdoor reset Boost Delay Time
When using the outdoor reset sensor, if a call for heat is longer than Boost delay time,
the boiler will Boost to the maximum supply water temperature - see parameter 16CH.
(0~120 min)
13: Ft 1 min Delay time for heating burner
operation
Burner does not operate during the delay time when the burner is turned o due to
the temperature during heating operation. (0~20 min)
14: bo 15°F (10°C) Burner ON dierential Heating temperature setting during heating operation –
Operate in burner ON temperature setting Range: 9 - 27°F (5 - 15°C)
15: OF 110°F (38°C) Warm Weather Shutdown This warm weather temperature setting will shut down CH Mode.
Range: 50 - 110°F (10 - 43°C).
16:cH 180°F (82°C) Setting for Heating Maximum
Temperature
Range: 9°F less than Minimum Temperature to 180°F
5°C less than Minimum Temperature to 82°C
17:cL 130°F (54°C) Setting for Heating Minimum
Temperature Range: 86°F to 9 degrees °F less than Maximum Temperature
18:dH 140°F (60°C) Setting for Hot Water Maximum
Temperature Range: 120°F - 140°F (49°C to 60°C)
19:cb 100% Heating Combustion Rate Range: 50%~100%
20:db 100% Hot Water Combustion Rate Range: 50%~100%
21:PP 40 min Boiler pump post burner limit
run time
(Boiler Pump) 1 min - 60 min. As long as TT is closed, boiler and system pump
both run, even when boiler hits high limit. (TT is closed).
22:Po 5 min Pump on Time (Boiler Pump Repeat ON Time) Range: 1 min ~60 min (While TT is closed)
23:PF 0 min Pump o Time (Boiler Pump Repeat O Time) Range: 0min ~60 min (While TT is closed)
24:SF 150°F (66°C) Storage o temperature Range: 140°F - 180°F (60°C to 82°C)
24:SF 105°F (41°C)
DHW Recirculation o temp
(when DHW/Surface sensor is
connected)
Range: 95°F - 140°F (35°C to 60°C) The range is automatically changed when
DHW/Surface sensor is connected.
25:So 18°F (10°C) Storage on Δtemp Range: 9°F - 36°F (5°C to 20°C)
25:So 9°F (5°C)
DHW Recirculation on temp
(when DHW sensor or aquastat
is connected)
Range: 9°F - 27°F (5°C - 15°C) The range is automatically changed.
26:dt 0 min Smart DHW Priority Delay time
Range: 0 – 2 minutes. If Smart DHW Priority is ON (see parameter P36), a call for
domestic hot water will be prioritized by the boiler for delay time value. The boiler
will turn heating back on as long as boiler can satisfy both domestic and heating
demands otherwise, heating will remain o until domestic demand has ended.
27:PE 1 min
Internal Boiler Pump and system
pump Post-Purge Time,
T/T Satised
Allows the user to set the boiler pump and system pump post purge time once
the appliance CH set point and thermostat are satised. Range: 1-5 minutes
28:
HA 0-2 High Elevation Mode
High Elevation Mode: 0 - 2, 2 - 5, 5 - 8, 8 - 10 Default: 0 - 2
0 - 2: 0 - 2,000 ft
2 - 5: 2,000 - 5,000 ft
5 - 8: 5,000 - 8,000 ft
8 - 10: 8,000 - 10,000 ft
Index Default Parameter Description
29: AP
AP:cP 5
CH System Pump and
DHW Indirect Pump Test
Mode
This function sets the time to run Boiler pump to purge air from the
system. Range: 1 – 30 minutes
OFF Boiler Pumps Test Mode Turn this function on to activate Boiler pump.
Only works in installation mode. Turns o when in normal mode.
cP:O
or
cP:On
30: dP 4 hrs DHW Timeout Feature Range: 0 - 12 hours, ‘0’ OFF
31: SA
AqUA
dHr Select AqUA or dHr
Select Storage Type, Aquastats or DHW-recirc Sensor (Aects P24:
SF, P25: So)
- Aqua: DHW Recirculation Operation with aquastat (not supplied)
- dHr: DHW Recirculation Operation with DHW-R / surface sensor
(optional equipment)
- dHr Sensor not connection: Storage Operation
dHr
32: rC 15 min
DHW in stand-by, DHW
recirc pump not running for
recirc for 15 min. (Applies
when not using DHW-R
sensor or aquastat; pairs
with P33)
Range: 1 – 60 (min) To run continuously between
rC and rt
If ow is detected, rC timer
resets to zero.
33: rt 10 min DHW recirc pump run time
to reach DHW recirc temp. Range: 0 – 15 (min)
34: HF 80%
Hybrid O Firing Rate
(DHW mode change: CH-
O, DHW ON)
Activated during “Smart” DHW function,
Boiler ring rate has reached set maximum heating rate, deactivate
the external CH pump for DHW priority, Range 50 - 90%
35: Hn 50%
Hybrid On Firing Rate
(CH mode change: CH +
DHW)
During activate “Smart” DHW function,
Boiler ring rate has reached set minimum ring rate, activate
external CH pump, Range 30 - 50%
36 : Ho ON “Smart” DHW mode:
ON/OFF
Activate “Smart” DHW operating function: ON/OFF
When set to ON, it operates in hybrid mode.
When set to OFF, it operates in normal mode. (DHW priority)
Installer Parameters (cont)
Parameters 31 to 36 are for the oor model combi units only.
FT WALL MOUNTED AND FLOORSTANDING COMBI MODELS