manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Hochiki
  6. •
  7. Rack & Stand
  8. •
  9. Hochiki NS4-100 User manual

Hochiki NS4-100 User manual

This manual suits for next models

23

Popular Rack & Stand manuals by other brands

Dynex DX-MP3MT Quick setup guide

Dynex

Dynex DX-MP3MT Quick setup guide

Konig & Meyer 24185 manual

Konig & Meyer

Konig & Meyer 24185 manual

ECG LD 326501 instruction manual

ECG

ECG LD 326501 instruction manual

Philips SB7S19S/00 quick start guide

Philips

Philips SB7S19S/00 quick start guide

Woodline KIT-250 lb instructions

Woodline

Woodline KIT-250 lb instructions

ricoo S1222 installation instructions

ricoo

ricoo S1222 installation instructions

Kanto P301 user manual

Kanto

Kanto P301 user manual

VidaBox VB MNT FFS2 installation guide

VidaBox

VidaBox VB MNT FFS2 installation guide

PROEL PLWIN60C user manual

PROEL

PROEL PLWIN60C user manual

AllMounts PLB-43S instruction manual

AllMounts

AllMounts PLB-43S instruction manual

VMP VH-001 instruction sheet

VMP

VMP VH-001 instruction sheet

Nederman SYSTEM 920/400 instruction manual

Nederman

Nederman SYSTEM 920/400 instruction manual

Glasdon ORBIS POST MOUNTING KIT installation guide

Glasdon

Glasdon ORBIS POST MOUNTING KIT installation guide

Songmics LGR105 manual

Songmics

Songmics LGR105 manual

Grape GM401 user manual

Grape

Grape GM401 user manual

FourStarGroup 11225296 manual

FourStarGroup

FourStarGroup 11225296 manual

CHIEF FLR100 installation instructions

CHIEF

CHIEF FLR100 installation instructions

FEC XDCAM EX PMW-EX30 manual

FEC

FEC XDCAM EX PMW-EX30 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Hochiki America Corporation
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268
DWG # HA-06-060, Rev 11/21
PAGE 1 of 2
PART # 1700-09987
Conventional Detectors and Bases
BASE SPECIFICATIONS
MODEL
Base
ID
Compatible
Detector ID
Alarm Current
Mounting Box
NS4-100, NS4-100W
HB-55
HD-3 or HD-5
150mAlimit externally @15.0 - 33.0V max
3” Octagonal
NS6-100, NS6-100W
HB-55
HD-3 or HD-5
150mAlimit externally @15.0 - 33.0V max
4” Octagonal / 4” Square
NS4-220, NS4-220W
HB-3
HD-3 or HD-5
93mA (136mA @33.0V max)
3” Octagonal
NS6-220, NS6-220W
HB-3
HD-3 or HD-5
93mA (136mA @33.0V max)
4” Octagonal / 4” Square
NS4-221, NS4-221W
HB-4
HD-3 or HD-5
46mA (77mA @33.0V max)
3” Octagonal
NS6-221, NS6-221W
HB-4
HD-3 or HD-5
46mA (77mA @33.0V max)
4” Octagonal / 4” Square
NS4-224, NS4-224W
HB-5
HD-3 or HD-5
43mA (58mA @30.0V max)
3” Octagonal
NS6-224, NS6-224W
HB-5
HD-3 or HD-5
43mA (58mA @30.0V max)
4” Octagonal / 4” Square
HSC-220R, HSC-220RW
2 Wire Relay Base
HB-72
HD-3 or HD-5
88mA (98mA @ 26.5V max)
4” Octagonal / 4” Square
HSC-221R, HSC-221RW
2 Wire Relay Base
HB-71
HD-3 or HD-5
49mA (62mA @ 30.0V max)
4” Octagonal / 4” Square
HSC-224R, HSC-224RW
2 Wire Relay Base
HB-73
HD-3 or HD-5
43mA (58mA @ 30.0V max)
4” Octagonal / 4” Square
HSC-4R 4 Wire 24V Base
N/A
HD-3 or HD-5
43mA (58mA @ 30.0V max)
4” Octagonal / 4” Square
HSC-4R12 4 Wire 12V Base
N/A
HD-3 or HD-5
47mA (75mA @ 18.0V max)
4” Octagonal / 4” Square
NOTES:
Alarm current for 2-wire operation applies to the FACP Initiating Device Circuit and detector.
Alarm current for 4-wire operation applies to the Auxilliary Power Supply and detector.
NS4-100 and NS6-100 must be current limited by the FACP
Standard base is ivory color, W suffix indicates white color
Refer to the Technical Bulletin HA-06-434 issued 07/21 (accessible at www.Hochiki.com) for the following UL listed
compatible detectors. Connect these detectors only to a listed-compatible control panel. Refer to the control panel
installation manual for additional instructions. Smoke detectors are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose:
SOC-24V/SOC-24VN/SOC-24VW Smoke Detector (Compatibility ID HD3)
SOE-24V/SOE-24V (WHT) Multi-criteria Smoke Detector (Compatibility ID HD3)
SOE-24H/SOE-24H (WHT) Multi-criteria Smoke and Heat Detector (Compatibility ID HD3)
DCD-135/DCD-135W Fixed Temperature and Rate of Rise Detector (Compatibility ID HD3)
DCD-190/DCD-190W Fixed Temperature and Rate of Rise Detector (Compatibility ID HD3)
DSC-EA/DSC-EAW Rate of Rise Dry Contact Heat Detector
DFE-135/DFE-135W/DFE-135C Fixed Temperature Dry Contact Heat Detector
DFE-190/DFE-190W/DFE-190C Fixed Temperature Dry Contact Heat Detector
Detectors must be installed and maintained in accordance with applicable NFPA standards, local codes and any authority
having jurisdiction. Refer to NFPA 72 "National Fire Alarm and Signaling Code" for installation guidelines and testing
procedures. Smoke detectors should be tested in accordance with NFPA 72, section on "Inspection, Testing and
Maintenance".
Seal conduit openings in the electrical box with 3M Weatherban #606 nonflammable sealing compound (or equivalent)
to reduce the stack effect. Attach the detector to the base by turning the detector clockwise until it stops.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Hochiki America Corporation
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268
DWG # HA-06-060, Rev 11/21
PAGE 2 of 2
PART # 1700-09987
NS6-100
DEVICE
END OF LINE
LISTED
NS6-220/-221/-224
NS4-220/-221/-224
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
NEGATIVE
UL LISTED
2-WIRE OPERATION
2-WIRE RELAY OPERATION
USE ONLY WITH A UL LISTED ACCESSORY
RATED 20MA MAX, 24VDC MIN.
MODELS: RAI-LED
BLU
GRN
GRY
YEL
PUR
ORN
H1
ORN
YEL
H2
HSC-220/-221/-224
LISTED
RELAY
END OF LINE
PAM-4
HSC-4R/-4R12
PUR
CONTROL
PANEL
INITIATING
CIRCUIT
HSC-4R/-4R12
4-WIRE OPERATION
12
65
4
3
12
65
4
3
12
65
4
3
UL
LISTED
POWER
SUPPLY
12VDC
use
HSC-4R12
or
24VDC
use
HSC-4R
HSC-XXXR SERIES
CONTACTS, SHOWN
WITH POWER OFF,
NORMAL OPERATION.
L3 L4
H2
H1
L1
L2
S2
S1
L3 L4
H2
H1
L1
L2
S2
S1
L3 L4
H2
H1
L1
L2
S2
S1
L3 L4
H2
H1
L1
L2
S2
S1
(+)
(-)
(C)
(NC)
HSC-4R/-4R12
CONTACTS, SHOWN
WITH POWER OFF,
NORMAL OPERATION.
2A, 30VDC
1A, 120VAC
2A, 30VDC
1A, 120VAC
(+)
(-)
WIRING TERMINALS
NS4-100 AND NS6-100
ARE IDENTICAL
LISTED
DEVICE
END OF LINE
LISTED END
OF LINE
DEVICE
Go/No-Go testing can be used to confirm a detector is within its sensitivity limits and operating normally
GO/NO-GO TESTING SOC-24V/-24VW
1. Hold a magnet (2lb pull force min) on the detector as shown.
2. For go: The detector should alarm and latch red within 10 seconds.
When using Alarm Verification, may take up to 30 seconds.
For no-go: The detector will blink red every 3 seconds and
never alarm or latch red.
3. Upon reset, the smoke detector LED should blink Green every
3 seconds. If the detector blinks red, it should be replaced.
GO/NO-GO TESTING SOE-24V/-24V (WHT)/-24H/-24H (WHT)
1. Place the Hochiki America Test Magnet to align the LED marking as shown.
2. For go: The detector will blink red every second. Holding the magnet
in position for at least 13 seconds will cause the detector to alarm
with the red LED latched on.
For no-go: After at least 13 seconds, the detector will continue to
blink red every 3 seconds and never alarm or latch red.
3. Upon reset, the smoke detector LED should blink Green every
3 seconds. If the detector blinks red, it should be replaced.
SOC-24V Magnet Placement
Hold Magnet
Here
LED
SOE-24V Magnet Placement
L
E
D