
ENGLISH | 15
All electrical work shall be carried out under the super-
vision of an authorized, licensed electrician. The present
state adopted edition of the National Electrical Code as
well as all local codes and regulations shall be complied
with.
5.6.1 Verification of power supply
Prior to making any electrical connections or applying pow-
er to the pump, compare the power supply available at the
pump station to the data on the unit‘s nameplate. Confirm
that both voltage and phase match between pump and
control panel.
5.6.2 Power lead wiring
HOMA pumps may be provided with 1 or more cables,
depending on motor horsepower and operating voltage.
Power leads U1, U2, & Z2 for single phase and U, V, W for
three phase pumps may be provided as single conductor,
or as multiple conductors. Multiple conductor configura-
tions may use leads from separate cables, or may use
two conductors within one cable. Please refer to wiring
diagram in the appendix for specific connection details.
The pump must be connected electrically through a motor
starter with proper circuit breaker protection in order to
validate warranty. Do not splice cables.
5.6.3 Thermal switch wiring
Pumps are equipped with thermal switches embedded
in the stator windings which are normally closed, auto-
matically resetting switches. Switches will open when the
internal temperature rises above the design temperature,
and will close when the temperature returns to normal.
Thermal switches must be wired to a current regulated
control circuit in accordance with the NEC. Identify ther-
mal switch leads markedT1 and T3 in the power or control
cable. The resistance across the leads will be 0.5 Ohms.
Thermal leads must be connected to the thermal overload
relay located in the control panel. Thermal switch leads
must be connected to validate warranty.
Note: All sizes of Class 1, Div. 1 pumps for hazardous
service must have thermal switch leads connected to a
current regulated control circuit in accordance with NEC.
5.6.4 Seal probe wiring
The mechanical seal leak detector probe utilized in the
pump is a conductive probe which is normally open. The
intrusion of water into the seal chamber completes the
electrical circuit. Control panel provisions will sense this
circuit closure, and will provide indication or alarm func-
tions depending on the panel design. Either single or dual
wire systems may be provided. Single wire systems uti-
lize one energizing conductor, and the pump casing and
neutral lead as the ground or return portion of the circuit.
The dual wire systems utilize two separate conductors for
each leg of the circuit. With either system, the seal probe
leads must be wired into a control circuit provided in the
control panel. This control circuit must energize the probe
with a regulated power source, and sense the closed cir-
cuit in event of water intrusion Indication and alarm func-
tions must also be provided in the control circuit. Please
see control panel wiring diagram for seal probe connec-
tion points.
For Hazardous Area Classification Pumps, leak de-
tector circuit must be in conformance with applica-
ble NEC codes and regulations.
Pour les pompes classées en zone dangereuse, le
circuit du détecteur de fuites doit être conforme aux
codes et réglementations NEC applicables
5.6.5 Start / Run Capacitors and Relays
All single phase motors require start and run capacitors
along with a start relay to operate. Capacitors and relays
must be sized for the specific motor.
Capacitors are sized based on ideal conditions.
The run capacitor may need to be resized to match the
available field voltage. Each cap kit shipped is supplied
with a wiring diagram and start up procedure.
5.6.6 Single Phase Pump Start-Up Procedure
Run Capacitor sizing can vary depending on the incoming
supply voltage provided. HOMA Single Phase pumps are
provided with Start and Run Capacitor(s) sized for 220-
230V under load. Frequently, the available line voltage is
considerable different than indicated, and the Run capac-
itor(s) may need to be resized to match the available field
voltage. The following procedure will allow you to verify
proper operation of your single phase pump, and/or make
necessary changes to you capacitors to correct for your
power supply. After verifying wiring is in accordance with
your pump requirements, start pump and record the fol-
lowing readings from each of the (3) pump cable leads.
Current under load:
U1________Amps,>U2________Amps,>Z2________Amps
U1: (Should be) highest reading
U2: middle reading
Z2: lowest reading
Lead U1 (common) should have the highest current read-
ing. Lead Z2 (start) should have the lowest reading.
If Z2 current draw is greater than the current draw of ei-
ther U1 or U2, a smaller size Run capacitor (lower micro-
farad rating) is required to correct the condition. Example:
If a 60 µf Run capacitor was supplied, change to a 50 µf
Run capacitor and check current readings. Typically, only
one step down in capacitor size is required, but in certain
instances 2 steps may be required.
( ) The standard capacitor kit provided includes:
____________ µf start capacitor
____________ µf run capacitor.
( ) Additional run capacitors have been included for use in
tuning the pump to match available line voltages for opti-
mum performance.
____________ µf run capacitor
____________ µf run capacitor
____________ µf run capacitor