INTRODUCTION
i3H provides:
Powerful Standard Features in one unit including
Controller
Network
Operator Interface
Highly Visual Display Screen
.
Standard Features on i3H
Base
Model
Network Screen Type Standard
Features
i3H08
On-Board
Ethernet
100BaseT
8.4” TFT SVGA
with 32,768
colors
CompactFlash
3 Serial Ports
Ethernet
i3H10 10.4” TFT
SVGA
with 32,768
colors
i3H12 12.1” TFT
SVGA
with 32,768
colors
2 Specifications/ Product Descriptions
Table 2 – i3H Base Specifications
Base Models i3H08
(8-inch) (SVGA)
i3H10
10-inch) (SVGA)
i3H12
(12-inch) (SVGA)
Display Type
(LCD with
backlight)
800 x 600
TFT
800 x 600
TFT
800 x 600
TFT
Display Size 8.4” 10.4” 12.1”
Display Screen
Dimensions
6.7”W x 5”H
(170 x 128 mm)
8.3“W x 6.2“H
(211 x 159 mm)
9.7“W x 7.3“H
(246 x 185 mm)
Display Memory 8 MBytes
User Keys 7 configurable keys + System Key
Screens
Supported
1,023 screens
(300 objects per screen)
Number of
Colors
32,768
3 INSTALLATION
Base
Models
i3H08
(8-inch)
i3H10
10-inch)
i3H12
(12-inch)
Primary
Power
Voltage:
24 VDC (+/-10%)
Steady State
Current:
0.625 A @ 24 VDC
Inrush Current:
(25 A @ 24 VDC)
for 0.7 ms
Voltage:
24 VDC (+/-10%)
Steady State
Current:
1.25 A @ 24 VDC
Inrush Current:
(30 A @ 24 VDC)
for 1 ms
Voltage:
24 VDC (+/-10%)
Steady State Current:
1.25 A @ 24 VDC
Inrush Current:
(30 A @ 24 VDC)
for 1 ms
i3H Dimensions
See Panel Cut-outs and Dimensionsfor complete details (Section 3.2)
Base
Models
i3H08
(8-inch)
i3H10
10-inch)
i3H12
(12-inch)
Height 7.0” (178 mm) 9.09” (230.9 mm) 10.25” (260.4 mm)
Width 9.17” (233 mm) 11.95” (303.5 mm) 12.87” (326.9 mm)
Mounting
Depth
2.35” (59.70 mm) 2.52” (64 mm) 2.52” (64 mm)
Keypad
Material
Faceplate made of LexanHP92 by GE Plastics.
The material is resistant to most corrosive substances found in
industrial environments. The material also holds up well in most
industrial conditions.
Serial Ports 3RS-232 / RS-485 Ports. Software Selectable.
Network
Options
On-board Ethernet 100BaseT
Control
Memory
256K Ladder Memory plus 32KB Register Space
Control
Scan Rate
0.2mS / K Ladder Logic (typical)
Portable
Memory
Compact FLASH (CF) slot
Temperature
& Humidity
32 - 122°F (0 - 50°C), 5 to 95% Non-condensing
UL Please contact IMO for certificate information
CE
i3H Series Models:
i3H08/00000-SEOL - 8
”
display model
i3H10/00000-SEOL - 10
”
display model
i3H12/00000-SEOL - 12
”
display model
Note: Prior to mounting, observe requirements for the panel layout design and adequate clearances in the I3 Hardware Manual. A handy checklist is provided in the Installation
chapter.
3.1 Installation Procedures
a. i3H Base Installation
1. Per specifications of the I3H model you are using, carefully prepare the panel cutout. Make sure the corners of the cutout are square andfree from burrs.
(Locate the panel
cut-outs and dimensionsthat pertain to your I3H model as shown in this document.)
2. Cut the host panel
3. Insert the i3H (base unit only) through the panel cutout from the front. The gasket material needs to lie between the host panel and the I3H.
4. Install and tighten the mounting clips (provided with the I3H) until the gasket material forms a tight seal.
5. Connect cables as needed such as communications, programming, power and fiber optic cables to the I3H ports using the provided connectors.
6. As a final step before using, carefully remove the protect
ive, plastic sheet from the front of the unit. The protective, transparent sheet is used to protect the display window.
7. Begin configuration procedures for the I3H.
Caution: Do not force the I3H into the panel cutout. An incorrectly sized panel cutout damages the I3H screen.
Caution: Do not over-tighten. Over-tightening damages the case.

I3H08-12IBD Specifications / Installation
__________________________________________________________________________________________________________________________________________________
5/12/2010 Page 2 of 5
3.2 Panel Cut-Out and Dimensions
3.2.1 i3H08 (8-inch)
3.2.2 i3H10 (10-inch)
3.2.2 i3H12 (12-inch)
Figure 2 – Panel Cut-out and Dimensions 8-inch
I3H Panel Cut-Out 9.17"
(233.0 mm)
2.35"
(59.70 mm)
i3H
I3H Side View
I3H Rear View
8.69 [220.7mm]
6.53 [165.9mm]
Figure 4 – Panel Cut-out and Dimensions 12-inch
I3H Panel Cut-Out
2.52”
(64 mm)
i3H
i3H
I3H Side View
I3H Rear View
12.87"
(326.9mm)
12.29 [312.0mm]
9.66 [245.4mm]
Figure 3– Panel Cut-out and Dimensions 10-inch
11.95
(303.5 mm)
2.52
(64 mm)
i3H
I3H
I3H Side View
I3H Rear View
I3H Panel Cut-Out
8.505
(216.0 mm)
11.360
(288.5 mm)

I3H08-12IBD
__________________________________________________________________________________________________________________________________________________
5/12/2010 Page 3 of 5
3.3 i3H Base Ports and Connectors
3.3.1 Primary Power Port / Grounding
a. Port 1 (MJ1) / Port 2 (MJ2) Modular Jacks
Figure 6 – Close-up of Port 1 (MJ1) / Port 2 (MJ2) (RS-232 and RS-485)
The I3H base has power, network, programming and fiber optic ports. Three RS-232 and RS-485 ports are available. (Default programming port is MJ1)
Parallel
Port
Port 2Port 3 Port 1LAN
Primary Power
Connector
001QX005
Parallel
Port
Port 2
CN1
Port 1
Parallel
Port
Port 2Port 3 Port 1LAN
Primary Power
Connector
001QX006
i
3H10
10”
i
3H08
8”
i
3H12
12”
Port 3
MJ1 MJ2
MJ1
MJ1 MJ2
MJ2
CN1 CN1
Primary Power
Connector
Figure 5 – I3H Base Ports and Connectors
Table 4 – Primary Power Port Pins
Signal Pin Description
V+ Input power supply voltage
V- Input power supply ground
Frame Ground
Note: Power Supply Voltage Range is from 24VDC ±
±±
±10%.
3.3.2 RS-232 Port / RS-485 Port
There are a variety of ways to connect to the RS-232 and RS-485 ports; You can use
two modular jacks (MJ1 and MJ2) or the 25-pin Dsub connector (CN1).
Table 5 – Ports and Functions (Port 1, 2, and 3)
Functions Port 1 (MJ1)
Port 2 (MJ2) Port 3 (CN1)
RS-232 2
22
22
22
22
22
2
RS-485 2
22
22
22
22
22
2
Hardware Handshaking 2
22
2
Programming 2
22
2
Ladder Function
Controlled 2
22
22
22
22
22
2
Modem 2
22
2* 2
22
2* 2
22
2
* Not supported by i3 Config Modem Function Blocks
1 2 3 4 5 6
Table 6 – Port 1 (MJ1) / Port 2
(MJ2) Pins
Pin Signal
1 +SD/RD
2 -SD/RD
3 +5V
4 +5V
5 0V
6 0V
7 RXD
8 TXD
Output power supply: Max.
150mA
Figure 7 – Port 3 (CN1) RS-232 / RS-485 Connector
b. Port 3 (CN1) Connector
Table 7– Port 3 (CN1) Pins
Pin # Signal Pin # Signal
1 FG 14 I3H451, 551, 651: +RTS
2 TXD 15 Not Used
3 RXD 16 Not Used
4 RTS 17 I3H451, 551, 651: -RTS
5 CTS 18 -CTS
6 Not Used 19 +CTS
7 SG 20 Not Used
8 Not Used 21 Not Used
9 +5V 22 Not Used
10 0V 23 Not Used
11 Not Used 24 +RD
12 +SD 25 -RD
13 -SD
1
13
14
25
3.3.3 DIP-Switch
The DIP switch is used for setting the terminating resistance of the RS-485 signal line at the CN1,
MJ1, or MJ2 connector.
Figure 7 – DIP Switch
(1)
Set DIPSW 8 to ON position when termination is required on MJ2.
(2)
Set DIPSW 7 at the terminating station of the i3H units to the ON position when
connecting PLCs through RS-422/485.
(3)
Set DIPSW 6 to ON position when termination is required on MJ1.

I3H08-12IBD Specifications / Installation
__________________________________________________________________________________________________________________________________________________
5/12/2010 Page 4 of 5
Figure 8 - Port 3 (CN1) RS-232 Port
Figure 9 – Port 3 (CN1) RS-485 Port
Shielded Cable
Receive Data
SG
SG
Send Data
To RS-232 Port
SG 7
CS 5
Port 3
RS 4
RD 3
SD 2
FG 1
Signal Pin No.
Shielded Cable
Send Data (-)
To RS-485 Port
SG
Send Data (+)
Receive Data (-)
Receive Data (+)
SG 7
-SD 13
Port 3
+SD 12
-RD 25
+RD 24
FG 1
Signal Pin No.
3.5 Quick Start Instructions
1. Download i3 Configurator V9.0 (or better) from the IMO website and install, following on-screen instructions.
2. Connect a suitable 24Vdc supply to the screw terminals as shown in Figure 5, and power up.
Serial Programming:
Requirements: i3-PC45 programming cable (optional part: PC501 - USB to
Serial Converter for PC’s without serial port), PC with Windows XP or better.
1. Connect the RJ45 connector of the i3-PC45 cable to the i3H port
MJ1 and connect the 9-pin D-type connector to the PC and open
i3 Configurator.
2. Select Tools->Application Settings->Communications-
>Configure->Com Port (or USB if convertor used). Input the
required com port number then press OK.
3. If the connection is successful, then the status of the i3 should no
longer be grayed out and display as shown .
4. To get started with the programming download the i3 Basic
Tutorial from the IMO website.
Ethernet Programming:
Requirements: Ethernet cross-over patch cable, PC with Windows XP or better.
1. Set up the PC to have a fixed IP and Subnet of 192.168.254.1/
255.255.255.0 (for in-depth instruction on how to do this please
download the i3 Ethernet tutorial.pdf).
2. Connect the RJ45 connector of the patch cable to the i3H LAN port
and to the PC LAN port and open i3 Configurator.
3. Select Tools->Application Settings->Communications->Configure-
>Ethernet. Then enter IP address 192.168.254.128, select mode
iNX/i3Ce then press OK.
4. If the connection is successful, then the status of the i3 should no
longer be grayed out and display as shown .
5. To get started with the programming download the i3 Basic Tutorial
from the IMO website.

I3H08-12IBD Specifications / Installation
_______________________________________________________________________________________________________________________________________________
5/12/2010 Page 5 of 5
4 Safety
5 Technical support
Warning: Consult
user documentation.
Warning: Electric
Shock hazard
When found on the product, the following symbols specify:
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for Class I, Division 2
AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE
CLASSE 1, DIVISION 2.
WARNING - The USB parts are for operational maintenance only. Do not leave permanently connected unless area is known to be non-hazardous.
WARNING – EXPLOSION HAZARD - BATTERIES MUST ONLY BE CHANGED IN AN AREA KNOWN TO BE NON-HAZARDOUS
AVERTISSEMENT - RISQUE D'EXPLOSION - AFIN D'EVITER TOUT RISQUE D'EXPLOSION, S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX
AVANT DE CHANGER LA BATTERIE
WARNING - Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose Of In Fire
WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved s
hould install, adjust, operate, or service
this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe
bodily injury or loss of life.
For detailed installation and a handy checklist that covers panel box layout requirements and minimum clearances, refer to the hardware manual.
•All applicable codes and standards need to be followed in the installation of this product.
Adhere to the following safety precautions whenever any type of connection is made to the module.
•Connect the green safety (earth) ground first before making any other connections.
•When connecting to electric circuits or pulse-initiating equipment, open their related breakers. Do not make connections to live power lines.
•Make connections to the module first; then connect to the circuit to be monitored.
•Route power wires in a safe manner in accordance with good practice and local codes.
•Wear proper personal protective equipment including safety glasses and insulated gloves when making connections to power circuits.
•Ensure floor, hands and shoes are dry before making any connection to a power line.
•Make sure the unit is turned OFF before making connection to terminals. Make sure all circuits are de-energized before making connections.
•Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
Please contact automation@imopc.com
For further technical information and a full specification,
please consult the Hardware Manual
IMO Precision Controls Ltd
1000 North Circular Rd, Staples Corner, London. NW2 7JP
Tel: +44 (0) 208 452 6444,
Fax: +44 (0) 208 450 2274,
Web: www.imopc.com