ICE AIR VSHPW Operating instructions

Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Operating and
Maintenance Manual VSHPW
Vertical
Stack Unit
Water Source Heat Pump
(WSHP) Unit
E L A-13 0 8 6

2
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Welcome
Congratulations on your selection of the Ice Air Water Source Heat
Pump (WSHP). The WSHP is a combination cooling and heating
unit that provides an efficient room by room source for comfort
conditioning of your living environment.
Ice Air WSHP Vertical Stack units are built to a high standard of
quality and reliability, employing commercial grade components and
heavy duty, galvanized sheet metal casings. With proper maintenance
and usage, Ice Air WSHPs should provide many years of efficient,
quiet and trouble-free comfort.
To enhance the use of your Ice Air equipment, you will want to
read and carefully follow all of the instructions contained in this
Operating and Maintenance Manual. We recommend that you pay
special attention to the Safety and Warning Information section at
the beginning of this Manual, and to the various safety advisories
throughout this Manual.
Please retain this Manual for your future reference. We suggest that
you keep it with other important documents and product manuals.
If your unit has optional features, they will be explained in a separate
instruction sheet specific to that option.
On behalf of Ice Air, and our network of distributors and dealers, we
are happy to welcome you to our base of satisfied customers!
Location Model No. Serial No.
Living Room
Master Bedroom
Bedroom
Dining Room
Other
We recommend that you record the following information
about your Ice Air product(s).
Contents
Welcome........................................................ 2
Consumer Reference Information................ 3
Safety Guidelines.......................................... 3
Components and Parts Exploded View........ 4
Controls....................................................4-12
Troubleshooting .......................................... 13
Maintenance ..........................................14-15
Product Nomenclature...........................16-17
Warranty/Contact Information ................... 20

3
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Consumer Reference Information
For safe and optimal enjoyment of your Ice Air unit, please read
the following consumer safety and operating notes carefully before
operating your equipment!
p
! RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
p
!WARNING: Ice Air will not be responsible for any injury or
property damage arising from improper service, or service
procedures. If you install or perform service on this unit, you
assume responsibility for any personal injury or property
damage which may result. Many jurisdictions require a license
to install or service heating and air conditioning equipment.
p
!WARNING HIGH VOLTAGE: Disconnect all power before
servicing or installing unit. Multiple power sources may be
present. Failure to do so may cause property damage,
personal injury or death.
Safety Guidelines
Read this entire manual before operating the unit.
p
!WARNING: This unit MUST be serviced only by professionally
trained and qualified technicians. Do NOT attempt to maintain or
service this unit on your own – severe injury and death can occur
from electric shock, moving parts, and other hazards.
• Your Ice Air unit must be properly installed and commissioned
to operate correctly. Improper unit installation, adjustment or
commissioning, and/or improper heating system installation and
connection can lead to equipment malfunction and hazardous
operating conditions, and may void your warranty. If you have
any doubt about the proper installation of your Ice Air unit,
please contact your property manager at once to have a qualified
technician inspect the equipment.
• Your Ice Air units must each be wired on an individual, dedicated
electrical circuit with the correct voltage and proper amperage
(capacity) to match the unit nameplate requirements.
• Each unit’s electrical circuit must have a proper overcurrent
protection device, employing an approved circuit breaker or fuse
of the proper rating under NEMA and local building codes.
p
!WARNING: Every unit contains refrigerant within a sealed and
pressurized refrigerant system. This system must not be opened
or tampered with and any refrigeration system repairs MUST be
carried out by trained technicians. Refrigerant must be properly
handled and recycled per EPA regulations and guidelines.
p
!WARNING: Do NOT operate the unit with frayed, burnt or
damaged electrical wires!
p
!WARNING: Do NOT operate the equipment when in doubt –
have it inspected first!
IMPORTANT: It is not the intent of this maintenance manual to
correct any installation deficiencies. If you have any doubt about the
proper initial installation (or re-installation after servicing) of your Ice
Air unit(s) – noisy or inefficient unit operation, frayed or damaged
electrical connections, improper unit appearance, etc. – please
contact a trained servicer or building maintenance staff immediately.
The following physical conditions must be maintained for
proper unit operation:
Air flow must be unobstructed into and out of the unit return air
opening.
• Have the unit filter properly cleaned and serviced to prevent air
blockage from dirt and dust within the filter media.
Intended for indoor use only.
Proper installation and operating environment must be maintained.
Therefore:
• Do not operate the unit in corrosive environments such as
chemical plants, refineries or salt spray areas.
• Operate only with proper electrical service and protective circuit
breakers or fuses in place.
• Operate only with all unit and enclosure sheet metal parts in
place and properly installed.
• In areas of high concentrations of dirt, dust, pet dander or
pollutants, clean the filter often (at least monthly).
• Do not clean the unit with any solvents or cleaning solutions that
may damage the equipment.
• Understand and follow the unit operating instructions before
using your Ice Air equipment.

4
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Components and Parts Exploded View
V-WSHP GENERAL ASS'Y (BASIC)
ALUMINUM DOUBLE
DEFLECTION GRILLE
(OPTIONAL)
CONTROL COVER
BLOWER COVER
CHASSIS WITH
FILTER
SLIDE
RAILS
CASING
CONTROLS
BLOWER
ACCESS PANEL
WITH HINGED
DOOR

5
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
1. Overview
The Ice Air model ELA-13086 is a digital thermostat with a TFT
touch screen user interface (thin film transistor liquid crystal display;
TFT-LCD). It provides the user with control of heating or cooling
mode, temperature adjustment, 7-day programmable schedule, and
various working mode options. A time clock and calendar are integral
functions to this device.
2. Main Features
• Adjustable fan speed: High, medium, low, and auto. (2-speed or
3-speed can be set by the dip switch; 2-speed is the default)
• Optional mode: cooling, heating, auto and fan only. (heating
function can be set by the dip switch; the default assumes a
heating function present)
• Clock can be set to 12-hour (AM/PM) or 24-hour mode
• Calendar ranges: from 2020 to 2099
• 7-day programmable schedule (optional, set by the dip switch,
the default is “function available.” If the user wants to disable
the “7-day programmable schedule” they can do so via the
dip switch, which would cause the thermostat to operate like a
simple thermostat)
• Time delay function: 3 minute delay for compressor at first
power-on; (this can be using the dip switch; the default is delay
post start-up)
• System failure warning
• Heating mode: Set the heating mode type (hydronic coil heater,
electric resistance, heat pump, etc.) using the dip switch
• Space temperature sensor is integral to the thermostat; the
temperature sensing range is: 32°F to 99°F
• Optional unit mounted temperature sensor: User can select the
integrated temperature sensor within the thermostat (default)
or the unit mounted temperature sensor. (range of temperature
detecting: 32°F to 99°F)
• Anti-freeze protection for hydronic heating applications
(protection triggered when return air temperature is less than
or equal to 40°F; thermostat returns to the previously set mode
when the ambient temperature is higher than 60°F)
• Cold air prevention function, available only for hydronic heating
applications in heating mode
3. Electrical Specifications
Power supply: AC24V/1A/50-60HZ
Warning input: AC24V±20%, keeping 10s (warning is triggered if
abnormal condition occurs for more than 10 seconds)
Rest output: AC24V
Control signal output: AC24V/0.5A
4. Outside Temperature Sensor
5K/3950K±1% (cable type)
5. Specification of TFT Screen
Size: 3.5”
Resolution: 320×480 dot RGB
Display area: 48.96(H) × 73.44(V) mm
Screen type: Capacitive TFT touch screen
Controls

6
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
8. 7-day Programmable Default Schedule TABLE 3
The default day, time, and temperature are noted in Table 3 below.
These values can be changed by the user at any time.
Event Time Heat Cool
Monday to Friday
Wake 6:00 AM 70 °F 78 °F
Away 8:00 AM 62 °F 85 °F
Home 6:00 PM 70 °F 78 °F
Sleep 10:00 PM 62 °F 82 °F
Saturday and Sunday
Wake 6:00 AM 70 °F 78 °F
Away 10:00 AM 62 °F 85 °F
Home 6:00 PM 70 °F 78 °F
Sleep 11:00 PM 62 °F 82 °F
9. Mode Functional Description
• Cool Mode
• Select the Cool function from the menu by touching the
MODE icon on the main screen (see Figure 1)
• Select FAN SPEED from the menu by touching the FAN
SPEED icon on the main screen then selecting High,
Medium, Low, or Auto (see Figure 2)
• The unit will run according to the default settings in Table 3 if
the user has not altered any settings
• Temporary Override: The user can change the temperature
setting temporarily by touching the “+” or “-” icon on the
main screen to get the expected temperature settings. The
“+” and “-” icons appear after the user touches the screen.
The temporary override setting will be effective once the user
has not touched the screen for more than 3-seconds;
(Figure 3)
• The temporary override setting will only apply to the time
period between the input and the next temperature pre-
loaded in the programmed weekly schedule.
• The Temporary Override will be shown on the screen, to
indicate the new setting is different with the setting that
set in the weekly schedule; and will not disappear until the
applicable time period has passed
• The color of the temperature value and temporary override
text will be white when the setting is equal to the ambient
temperature, it will be blue when the setting is lower than
the ambient temperature, and it will be orange when the new
setting is higher than the ambient temperature
• Temperature Range: 51°F to 91°F
6. Dip switch options TABLE 1
Dial
code Description ON OFF Default
J1 Heating function Valid Invalid Valid
J2 7-day programing
function
Valid Invalid Valid
J3 Heating mode Hydronic heating
coil
Others Hydronic heating
coil
J4 Fan speed 2-speed 3-speed 2-speed
J5 Product type PTAC/FCU/Hybrid WSHP/PTHP PTAC/FCU/Hybrid
J6 Compressor delay
at first power-on
Valid Invalid Valid
J7 Space temperature
sensor
Inside (thermostat
built-in)
Outside Inside
* To set various dip switch status to get suitable functions as below Table 2.
Notes:
J1: If the unit has any heating function, then J1=ON; J1=OFF in cooling only
applications.
J2: If the user does not want “7-day programing function,” then J2=OFF. With J2=OFF,
the thermostat functions like a simple thermostat.
J3: The thermostat needs to know what type of heating is present. If the unit is using
hydronic heating coil for the heating function (such as PTAC with hydronic heating
coil or Hydronic WSHP), then J3=ON.
J4: For 2-speed fan operation J4=ON; for 3-speed fan applications J4=OFF.
J5: Refer to Table 5 for details.
J6: J6=ON is the default. J6=OFF is a test/service function option.
J7: There are two ambient temperature sensors in total, one is inside the
thermostat A, the other is inside the unit. This switch is to set which sensor the
customer is going to use.
7. Input or output for the terminal block TABLE 2
Terminal # Description Terminal Input/Output Voltage
1Transformer L R Input 24VAC
2Transformer N C Input 0VAC
3Cooling COOL Output 0/off; 24VAC/on
4High fan speed F1 Output 0/off; 24VAC/on
5Medium fan speed F2 Output 0/off; 24VAC/on
6Low fan speed F3 Output 0/off; 24VAC/on
7Heating H1 Output 0/off; 24VAC/on
8Hydronic heating coil
detecting
P Input ON/OFF signal
9Common terminal G Input --
10 Outside ambient
temperature sensor
RT Input --
11 Resume RST Output 0/off; 24VAC/on
12 Alarm ALARM Input 0/off; 24VAC/on

7
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
FIGURE 1
FIGURE 2
FIGURE 3
• Heat Mode
• Same operation as Cool mode; See specific operation for
Cool mode page 11
• This function only applies to the unit with heating function
• Auto Mode
• The same operation as Cool mode; See specific operation
for Cool mode page 11
• This function only applies to the unit with both cooling and
heating functions. The AUTO option will be invalid if the unit
is configured for cooling only
• The unit will run automatically to maintain the space
temperature, selecting either heating or cooling mode as
required by the space conditions
• When AUTO mode is selected, the unit will operate the
fan at low speed for 20-seconds, then enter into cooling,
heating, or fan mode depending on the deviation between
the space temperature and the set point temperature. The
default temperature is 77°F in this mode, and the unit will
run as noted in Table 4. The unit only runs in one functional
mode once it enters into cooling or heating mode
TABLE 4
Space temperature (Tr) Tr <70°F (criterial) 70F≤Tr≤79°F (criterial) 79°F≤Tr (criterial)
Function Mode Heating Fan Cooling
• User can set new expected temperature from 51°F to 91°F
by touch “+” or “-” icon on the main screen, the unit will run
similarly as Table 4 but with different criterial temperature.
• Fan Only Mode
• To select Fan Only function and fan speed; see referenced
MODE and FAN SPEED instructions
• In Fan Only mode, the unit will only operate the indoor
evaporator fan
• Temperature cannot be set at this mode, “+” and “-” icon on
the main screen will be invalid
10. Fan Speed Display Related to Signal Output to Fan Motor
for Various Product Types
• When dip switch J4 = ON, i.e. 2 fan speed [Alternate: “fan
speed 2” or “dual fan speed operation”]; High, Low, and Auto
fan speed can be selected
• When dip switch J4 = OFF, i.e. 3 fan speeds [Alternate: “fan
speed 3” or “tri fan speed operation”]; High, Medium, Low
and Auto fan speed can be selected (option for future use)
• See Table 5 and Table 6 for fan speed set points and the
corresponding Signal Output to the fan motor for various
products
PTAC / FCU / Hybrid (J5 = ON) TABLE 5
Function Mode Cooling Heating Fan only
Set Point Display LOW HIGH LOW HIGH LOW HIGH
Signal output (J3 = On) Medium High Low Medium Medium High
Signal output(J3 = Off) Medium High Medium High Medium High
WSHP / PTHP (J5 = OFF) TABLE 6
Function Mode Cooling Heating Fan only
Set Point Display LOW HIGH LOW HIGH LOW HIGH
Signal output (J3 = On) Medium High Medium High Medium High
Signal output(J3 = Off) Medium High Medium High Medium High

8
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
11. AUTO Fan Speed in Different Modes
• Cooling – Auto
• High speed: when space temperature ≥ Cool set point +2°C
(4°F)
• Low speed: when Cool Set point -1°C (2°F) ≥ space
temperature ≥ Cool Set point +1°C (2°F)
• Fan stop: when compressor stop
• Electrical heater heating and others – Auto
• High speed: when space temperature ≤ Cool Set
point +2°C (4°F)
• Low speed: when Cool Set point -1°C (2°F) ≤ space
temperature ≤ Cool Set point +1°C (2°F)
• Fan stop: 10 seconds delay after the heater relay closed
• Hydronic coil heating including Hybrid/FCU – Auto
• High speed: when the P1 was detected to be closed, and,
space temperature ≤ Cool Set point +2°C (4°F)
• Low speed: when space temperature ≤ Cool Set
point -1°C (2°F)
• Fan stop: 10 seconds delay after the heater relay closed
• MODE – Auto
• Once the MODE is selected to AUTO, the fan will run in the
same manner as noted in Cooling mode page 11
Remark: Other fan speeds like High, Medium and Low will cause no change once it
is selected.
12. Compressor Control for Cooling Mode
• Criterial for compressor ON or OFF
• Compressor ON: space temperature ≥ Cool Set point +1°C (2°F)
• Compressor OFF: space temperature ≤ Cool set point - 1°C (2°F)
Remark: The fan status noted in the figure below only refers to the fan speed in
“Auto” fan mode.
FIGURE 4
• Compressor protection
• If the power is cycled ON, the compressor will start after 3
minutes delay, and will indicate “Starting Up…” on the main
screen and flash the Cool icon (see Figure 5); This function
can be set to valid or invalid by the dip switch J6
• The compressor always starts with a 3 minutes delay each
time it is enabled; the “Starting Up…” message is not shown
in between compressor cycles, only when being powered up
from an power OFF position
FIGURE 5
13. Heating Relay Control for Heat MODE
• Criterial for heating relay ON or OFF
• Relay ON: space temperature ≤ Cool set point - 1°C (2°F)
• Relay OFF: space temperature ≥ Cool set point +1°C (2°F)
Remark: The fan status in Figure 6 only refers to the fan speed at AUTO fan mode
FIGURE 6
14. Anti-freeze Protection for Hydronic Heating Coil
Applications
• This function is valid only when the unit is using a hydronic coil
for heating and dip switch J3 = ON
• Trigger criterial: when the unit is ON or standing by, and, when
the ambient temperature is ≤ 40°F (5°C), the protection is
triggered. The unit will enter heat mode (heating reply is ON) and
run medium fan speed, and Figure 7 will be shown on the main
screen
• Resume criterial: when the space temperature = 60°F, the unit
go back to pervious working status

9
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
FIGURE 7
15. Alarm System
• When the unit has a fault occurred (for example, high pressure
protection triggered), if terminal “ALA” receives a signal for 10
seconds, then the unit will stop all output to the components, and
Figure 8 will be shown on the screen
• The user can try to restart the unit by touching the “PRESS TO
RESTART” icon on the screen
• If the system does not restart and operate normally, technical
support is available at www.ice-air.com
FIGURE 8
16. 7-Day Programmable Schedule
• Home, Away, and Sleep Temperature Settings
• Touch the Menu icon on the main screen, then enter the
sub-menu, and touch Cool Setting to enter another sub-
screen for the cooling temperature setting (for example)
(see Figures 9, 10, 11)
• To set the expect temperature for various time periods, touch
the “+” or “-“ icons next to the temperature settings (see
Figures 12, 13)
• Users can switch from °F or °C by touching said icons
located at the bottom of the Settings page (see Figures 11,
12, 13)
• To exit and go back to the main screen, touch the X icon in
the upper right hand of the screen, or touch to go back to
the previous screen (see Figures 11, 12, 13)
• The new setting are effective immediately for the week and will
display in the weekly schedule screen; User can see the new
settings when entering the weekly schedule screen
• Heat Settings function that same as the Cool Settings
• The default settings for the weekly temperature schedules is
noted in Table 3. New settings will overwrite previous settings
FIGURE 9
FIGURE 10
FIGURE 11
FIGURE 12

10
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
FIGURE 13
• Weekly Schedule Settings
• Touch the MENU icon on the main screen, enter the sub-
menu, and select Weekly Schedule to enter the selection
screen (see Figures 14, 15, 16, 17)
• To set the Wake Time for one day or several days (example:
Monday, Wednesday and Friday), touch “M”, “W” and “F” one
by one, then touch time icon under the Wake icon to enter
the time setting for Wake Time; see Figure 18
• Touch or icons to set expected hour and minutes; (the
time advances in 5-minute intervals)
• Touch the Save icon to record the settings, and touch
Remove to reset the setting
• Touch the Xicon to finish the settings and return to the main
screen, or touch to page backwards
• The new setting will be shown on the Weekly Schedule
screen; User can see the new settings when entering into
the Weekly Schedule screen
• Use the same procedure to set the expected time for Away,
Home and Sleep
• If the user does not select specific days and set specific
times directly, then the new settings will apply to all of the
days of the week
• The default settings for the weekly temperature schedules is
noted in Table 3. New settings overview the previous settings
• Prior to the Day and Time being set by the user, the display
will show “No Set” in the time display section of the screen.
Once the Day and Time are set, it will display under the
temperature indicator (see Figure 14)
• If the settings for each day are different, then “Multiple” will
be indicated; if the settings for several days is the same, the
set time will be shown (see Figure 17)
FIGURE 14
FIGURE 15
FIGURE 16
FIGURE 17

11
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
FIGURE 18
17. System Time and Date Setting
• Touch the MENU icon on the main screen to enter the sub-
menu, then touch Date & Time to enter the Day & Time sub-
screen (see Figure 19, 20, 21, 22)
• Touch Edit Date or Edit Time to enter the screen to edit these
settings (see Figures 23, 24)
• User can select 12-hour or 24-hour format by touching the 12h
or 24h icon respectively
• To set Date: Touch or icon to set expected year, month and
date; touch Save & Exit to save the settings and go back to the
upper menu
• To set Time: Touch or icon to set expected hour and minutes
(5 minutes as a step when pressing on the time adjustment
icon); touch Save & Exit to save the settings and go back to the
upper menu
• If the user does not touch the Save & Exit icon after the new
setting, and touches Xor instead, the system will reminder
the user to save or not save (see Figure 25)
FIGURE 19
FIGURE 20
FIGURE 21
FIGURE 22
FIGURE 23

12
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
FIGURE 24
18. Power ON and Power OFF the Thermostat
• The thermostat requires 24-VAC power
• The thermostat will start up by showing the Ice Air logo and main
“standing by” screen; Push main button on the plastic casing for
the thermostat to enter working status; see Figures 26, 27
• To power the thermostat OFF, press the main button on the
plastic casing for 3-seconds
• The screen will go into sleep mode 30-seconds after the last
touch to the screen has been made. The user needs to touch the
screen to wake up the display
FIGURE 25
FIGURE 26
FIGURE 27
FIGURE 28
PLEASE NOTE: Other thermostats are available including:
System compatible with other 3rd party thermostats not shown here.
For more information go to: www.ice-air.com/thermostats
Digital LCD Thermostat
Habitat Wireless
Thermostat

13
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Troubleshooting
IMPORTANT: It is not the intent of this maintenance manual to
resolve any problems with the operation of your Ice Air unit.
Please contact a trained servicer or building maintenance
staff immediately if your unit fails to perform properly.
1. Contact a trained service technician to conduct full unit
diagnostics and repair to equipment.
2. Record any unit that does not operate noting the unit serial
number on your report.
If unit is not operating, conduct the following checks:
1. Check the electrical connections.
2. Check the voltage and current against the electrical
specifications on the unit nameplate.
3. Look for wiring errors. Check for loose screw connections in both
line and low voltage terminals.
4. Check the water supply piping for proper water connection.
5. Check for dirty filters.
6. Check indoor fan for proper operation.
7. Check that unit did not cycle off due to improper thermostat
settings.
8. Check for fault codes on the control board – consult the Board
Troubleshooting Table.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
WARNING: Ice Air will not be responsible for any injury or
property damage arising from improper service or service
procedures. If you install or perform service on this unit, you
assume responsibility for any personal injury or property
damage which may result. Many jurisdictions require a license
to install or service heating and air conditioning equipment.
WARNING HIGH VOLTAGE: Disconnect all power before
servicing or installing unit. Multiple power sources may be
present. Failure to do so may cause property damage,
personal injury or death.
Board Troubleshooting Table
Display (Fault Code)
LED
Yellow Green Red
Normal Mode OFF ON OFF
HPS (Refrigerant Pressure) (E1) OFF OFF FLASH
LPS (Refrigerant Pressure) (E2) FLASH OFF OFF
Evaporator coil low temperature protection (E3) FLASH OFF FLASH
Coaxial Coil Anti-freeze protection (E4) FLASH ON OFF
Temperature probe fault (E5) OFF FLASH OFF
High/Low Voltage Protection (E6) OFF OFF ON
Low Pressure Protection (E7) OFF ON ON
Condensate Overflow Electronic Protection (E8) ON OFF OFF
Coaxial Coil water flow low temperature
Protection (E9)
ON OFF FLASH
Low Ambience Temperature Protection (E10) ON FLASH OFF

14
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Maintenance
Your Ice Air unit is designed to provide
many years of efficient, trouble-free comfort
conditioning service. To ensure equipment
longevity and efficiency, please make sure
that the following simple maintenance
procedures are followed. This manual
assumes that your unit has been installed
by a qualified installation professional, and
is operating properly prior to maintenance
service.
Have your unit periodically inspected by
a properly trained service professional or
building maintenance staff person. The unit
should be checked for the safe and proper
functioning of all of its systems at least
once a year. The following recommended
maintenance procedures should be carried
out only by trained personnel with strict
adherence to the Safety Guidelines outlined
at the beginning of this manual. These
procedures MUST be followed to ensure
your safety and the safety of the person
maintaining the equipment!
Indoor Air Filter
It is recommended that you clean the indoor
air filter after every 350 to 400 hours of
unit operation – more frequently if the unit
is running in an environment of high dust,
pet dander or other pollutants in the indoor
atmosphere.
Condensate Drain Pan and Drain Hoses
Check the unit condensate drain pan and
drain hoses annually to ensure proper
condensate drainage. If any foreign matter
build-up in the drain pan is found, clean the
drain pan and drain hoses – frequency of
cleaning depends on the level of dirt and
pollutants that may be present in the indoor
environment.
Evaporator Coil
Check and clean (if necessary) the unit
evaporator coil annually.
Evaporator Motor and Blower Assembly
Check and clean for dust and dirt build up as
necessary.
Compressor
Annual check should be performed to detect
potential problems.
Condenser (Water Heat Exchanger)
Water coil maintenance is not required. If the
unit installation is located in a system with
water problem history, it is best to establish
a periodic maintenance program. It is the
building’s responsibility to maintain a water
system that should provide your unit with
treated and filtered water to keep water
flowing freely through your equipment.
With these simple maintenance procedures
carried out on a proper maintenance
schedule, your unit should provide many
years of trouble-free service. The procedures
are covered in greater detail on the following
pages and should be implemented by trained
personnel. But there are certain items that
you, the apartment owner or tenant, can do
to ensure proper unit function:
• Keep the area around your unit clear of
objects that may block air flow into the
unit – furniture, carpets and rugs, etc.
may restrict air movement.
• Keep the top of your cabinet free of
objects that may block air flow out of the
unit – plants, paperwork and books, etc.
should not be placed on or above the
discharge grille area.
• Keep drapes, blinds and other window
treatments clear of the air discharge
area – any blockage of discharge air will
have a negative impact on the unit and
on its ability to properly condition the
room.
General Unit Inspection
Visually inspect unit at least once a month.
Pay special attention to hose assemblies and
connections. Repair any leaks and replace
deteriorated hose immediately to avoid
potential costly damage to your property due
to component failure.

15
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Evaporator Motor and Blower Assembly
If there is evidence of dirt or dust build-up in
the evaporator motor or blowers, they should
be cleaned either by vacuum cleaning (if
working in an apartment) or by removing the
unit to a workshop location and cleaning with
compressed air.
p
!WARNING: Always obey safety
guidelines for using compressed air
in this latter case.
Your Ice Air unit has permanently lubricated
motor bearings that do not require additional
lubrication. Blowers and motors are factory
assembled for quiet performance – if there
is any excessive noise and vibration from this
assembly, it should be serviced by a qualified
technician.
Condenser (Water
Heat Exchanger)
Generally, if water
flow exceeds 3 gpm
per ton, the water
velocities should
keep your coil free of
scaling of debris that
could lead to erosion
and fouling.
Evaporator Coil
Check the coil for cleanliness and uniformity
of fins. If the coil is dirty, vacuum clean with
a soft brush attachment. This is the only form
of cleaning that should be carried out within
an apartment. If the coil requires additional
cleaning, the unit must be removed and
cleaned using compressed air and/or
washed. These operations MUST be carried
out in a facility properly equipped to handle
this type of work in a safe and professional
manner.
Roomside Component Cleaning
IMPORTANT: Power MUST be disconnected
before carrying out any of the following
cleaning!
To access the components within the chassis
of the unit:
1. Unit must be in OFF Position.
2. Disconnect unit from power source.
3. Remove the unit front cover/access door
by unscrewing the retaining screws
that hold it in place. You will then have
access to the unit components.
NOTE: Pictures of components and parts
may vary depending on your model.
Air Filter
1. Remove Air Filter.
2. If reusable, wash Air Filter in warm water
and biodegradable cleaner.
3. Rinse with clean water and allow to dry
completely.
4. Replace Air Filter.
5. As an alternate cleaning method, the
filter may be cleaned on both sides using
a vacuum cleaner and a soft brush type
attachment.
6. If your filter is disposable, replace with
new filter.
IMPORTANT: Do not operate unit without
filters.

16
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Product Nomenclature
Casing Nomenclature
Model Selection 8 VSHPW 12 P N F 1 S I X U U G
1 2 3 4 5 6 7 8 9 10 11 12 13
Primary Part
Item
#
Matrix
Name
Code
String
Value
Description
1POWER
8208V/1PH/60HZ
7277V/1PH/60HZ
5115V/1PH/60HZ
2UNIT TYPE VSHPW Vertical Stack WSHP
3CAPACITY
(BTUH)
09 9,000 (3/4-Ton)
12 12,000 (1-Ton)
15 15,000 (1-1/4-Ton)
18 18,000 (1-1/2-Tons)
24 24,000 (2-Tons)
30 30,000 (2.5-Tons)
36 36,000 (3-Tons)
4MOTOR
PPSC Motor
EEC Motor
BBLDC
5ELECTRICAL
CONNECTION
FFused Disconnect
NNon-Fused Disconnect
PLine Cord With Plug
XDefault: Terminal Block
6CASING
CONFIG. NNot Applicable
7CASING
DETAILS
SStandard 88” Casing
CCustom Casing
PCasing 68” (Reduction From The Top)
RCasing 86” (Reduction From The Top)
AStandard 88” Casing with 1” Stand
BStandard 88” Casing with 2” Stand
CStandard 88” Casing with 3” Stand
DStandard 88” Casing with 4” Stand
EStandard 88” Casing with 5” Stand
FStandard 88” Casing with 6” Stand
GStandard 88” Casing with 7” Stand
HStandard 88” Casing with 8” Stand
8INSULATION SInsulation: 12.7 mm (1/2") Fiberglass
CClosed Cell Foam Insulation
9P-TRAP
IInternal P-Trap
EExternal P-Trap
XNo P-Trap
10 RISERS
XNo Risers
HUnit Mounted Half Risers
GUnit Mounted Half Risers (Geothermal Units Only)
FUnit Mounted Full Risers
Item
#
Matrix
Name
Code
String
Value
Description
11 PIPING
ORIENTATION
LLeft Hand Connection
RRight Hand Connection
MLeft Hand with Bypass and Ball Valves (Half Riser Only)
NRight Hand with Bypass and Ball Valves (Half Riser Only)
ARear
BRear with Bypass and Ball Valves (Half Riser Only)
XPiping Orientation Not Applicable
12 WIRE WHIPS
A6.5’ Wire Whip for Remote Mounted Thermostat
B10’ Wire Whip for Remote Mounted Thermostat
C12’ Wire Whip for Remote Mounted Thermostat
D30’ Wire Whip for Remote Mounted Thermostat
E50’ Wire Whip for Remote Mounted Thermostat
FStandard 18" wire whip
UUnit Mounted Thermostat
13 DRAIN PAN
GPowder Coated Galvanized Drain Pan
SStainless Steel Drain Pan
XNo Drain Pan

17
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Item
#
Matrix
Name
Code
String
Value
Description
1POWER
8208V/1PH/60HZ
7277V/1PH/60HZ
5115V/1PH/60HZ
2UNIT TYPE VSHPW Vertical Stack WSHP
3CAPACITY
(BTUH)
09 9,000 (3/4-Ton)
12 12,000 (1-Ton)
15 15,000 (1-1/4-Ton)
18 18,000 (1-1/2-Tons)
24 24,000 (2-Tons)
30 30,000 (2.5-Tons)
36 36,000 (3-Tons)
4COMPRESSOR
BLANKET
BSound Attenuation Blanket
XNo Compressor Blanket
5CONTROLS
CNon-Programmable LCD Touchpad Thermostat (ELA-12690)
DNon-Programmable LCD Thermostat (ELA-8842 via dip
switch)
E7-Day Programmable LCD Thermostat (ELA-8842)
F7-Day Programmable Touchscreen Thermostat (ELA-13086)
GNest Thermostat (ELA-10665)
HHabitat Wireless Wi-Fi Thermostat with Water Leak Detector
(ELA-13161)
INon-Programmable LED Touchpad Thermostat (ELA-10328)
XThermostat Field Mounted By Others
6MOTORIZED
VALVES
A2-Way, 2-Position Motorized Valve NO
B2-Way, 2-Position Motorized Valve NC
CCustom
D3-Way, 2-Position Motorized Valve NO
E3-Way, 2-Position Motorized Valve NC
XNo Motorized Valve
Item
#
Matrix
Name
Code
String
Value
Description
7FLOW VALVES
AAutoflow Valve (HAYS 2510/2517)
BAutoflow Valve/Shutoff combo (HAYS 2519)
HAutoflow Valve (HAYS 2515) [high GPM only]
CAutoflow Valve w/PT Ports (YR Flow Valve)
MManual Balancing Valve
YY-Strainer
FAutoflow Valve w/PT Ports (YR Flow Valve) and Y-Strainer
DAutoflow Valve (HAYS 2510/2517) and Y-Strainer
EAutoflow Valve/Shutoff combo (HAYS 2519) and Y-Strainer
GManual Balancing Valve and Y-Strainer
XNo Flow Valves
8CONDENSATE
PUMP
IInternal Condensate Pump
EExternal Condensate Pump
XNo Condensate Pump
9FILTER
AMERV 8 Filter
BMERV 12 Filter
CMERV 13 Filter
WWashable Filter
PFiberglass Filter
XNo Filter
10 AIR VENTS
MManual Air Vent
TBleed Tee
XNo Air Vents
11
VALVE
SHIPPING
OPTIONS
AAssembled
SShipped Loose
XNone
Product Nomenclature
Chassis Nomenclature
Model Selection 8 VSHPW 12 B C A A I A M A
1 2 3 4 5 6 7 8 9 10 11
Primary Part

18
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Notes or Technical Comments

19
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Notes or Technical Comments

20
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
Twelve (12) Month Warranty of Ice Air units – Ice Air,
LLC, herein referred to as “Ice Air,” warrants to the
original owner that the entire unit is free from defects
in material and workmanship for a period of twelve (12)
months from the date of delivery. Any part of portion
thereof which becomes defective under normal use
during the period of this warranty will be repaired or
replaced provided Ice Air’s examination shall prove to its
satisfaction that the part was or became defective under
normal use. Ice Air’s obligations under this warranty
are limited to: (a) Repairing the defective part or (b)
furnishing a replacement part provided the defective
part is returned to the factory, without shipping damage,
transporting charges prepaid. No reimbursement will be
made for expenses incurred in making field adjustments
or replacements unless specifically authorized in writing
by the Company.
The Company is not obligated under this warranty for
field labor such as service for inspection, removing,
packing and/or reinstalling water source unit, nor for the
return transportation charges.
OPTIONAL Extended Refrigeration
Circuit Warranty
The Optional Extended Refrigeration Circuit Warranty
MUST be purchased from Ice Air within thirty (30) days
from date of delivery to be valid. The hermetically sealed
refrigeration circuit (consisting of the motor, compressor
assembly, evaporator coil, coaxial/condenser coil and
interconnecting tubing) is warranted to the original
owner for four additional years from date of the
expiration of the Twelve Month Warranty. Components
under this warranty will be supplied at Ice Air’s expense
provided the failed component is returned to the factory.
This optional warranty does not include any other parts
of the equipment such as fans, fan motors, controls,
cabinet parts, electrical relays, capacitors, protective
devices, or wiring. Ice Air is not obligated under this
warranty for field labor such as service for inspection,
removing, packing, and/or reinstalling the refrigeration
circuit, nor for return transportation charges. Ice Air
reserves the right to make a handling and inspection
charge in the case of parts or equipment improperly
returned as defective and/or as being in warranty.
To obtain assistance under the parts warranty or to
purchase the optional extended warranty, simply contact
Ice Air Customer Service at 80 Hartford Avenue, Mount
Vernon, New York 10553. Telephone 914-668-4700.
The Twelve Month and the OPTIONAL Extended
Refrigeration Circuit Warranty (which must be purchased
separately) constitute the buyer’s sole remedy. They are
given in lieu of all other warranties. There is no implied
warranty of merchant-ability or fitness for a particular
purpose. In no event and under no circumstance shall
Ice Air be liable for incidental or consequential damages,
whether the theory is breach of this or any warranty,
negligence, or strict tort.
No person (including any agent, salesman, dealer or
distributor) has authority to expand Ice Air’s obligation
beyond the terms of these express warranties, or to
state that the performance of the product is other than
that published by Ice Air.
General Conditions
The above warranties are void if Ice Air’s equipment has
been damaged, misused, subjected to abnormal use or
service or its serial number has been altered, defaced,
or removed, or payment for the equipment is in default.
Ice Air is not responsible for service to correct conditions
due to misapplication, improper installation, inadequate
wiring, incorrect voltage conditions or unauthorized
opening of the refrigeration circuit, nor for consequential
damages. In case Ice Air’s equipment is installed in
conjunction with cabinets, grills, louvers, controls or
other parts manufactured by others, these warranties
shall apply only to Ice Air’s manufactured portion of the
equipment. The conditions of the standard warranty plan
are effective for 18 months from TCO. Ice Air reserves
the right to make a handling and inspection charge in
the case of parts or equipment improperly returned as
defective and/or as being warranty.
Important
The following are the responsibility of the user. They
are not manufacturing defects, and are therefore not
included in the warranty plan.
1) Failure of unit to operate satisfactorily due to
improper amount of air on evaporator coil or air
supply to air cooled condensers.
2) Damage to unit or unsatisfactorily operation due to
improper cleaning of evaporator coil or use of unit
in corrosive atmosphere locations such as chemical
plants, refineries, or salt spray areas.
3) Damage to unit from unsatisfactory operation due
to blown fuses, inadequate or interrupted electrical
service, use of improper electrical protective devices
or operation of unit on power supply other than
covered by nameplate rating of unit.
4) Damage due to failure to properly maintain unit.
5) Damage due to transportation or handling prior to and
during installation.
6) Damage due to accident or from alteration, improper
installation, tampering.
7) Filter cleaning or replacement.
8) Misapplication.
Check, Test and Start
Check, Test and Start of the air conditioners by an
experienced person is the responsibility of the installing
contractor. This consists of physically confronting each
unit operating in both heating and cooling modes and
correcting any minor deficiencies noted. After the
equipment leaves the factory, it may become damaged
or maladjusted during transportation or on the job.
Sometimes wires are disconnected accidentally, or fan
motors move on their bases due to rough handling,
causing fans to strike; a component(s) may be
inoperable. The correction of such conditions is part of
the Check, Test and Start. Note that unless otherwise
specifically agreed to in writing, Ice Air includes no field
labor, Check, Test, and Start (or the like) in the price of
its equipment.
Installation
Ice Air is not responsible for the design, execution
and performance of the installation method or any of
the accessory items used during installation such as
seals, caulking, weatherproofing, supporting structures,
attachment means, louvers and frames supplied by
others.
80 Hartford Avenue, Mount Vernon, NY 10553
Tel: 877-ICE-AIR-1 (877-423-2471)
Fax: 914-668-5643
email: service@ice-air.com
www.ice-air.com
© 2022 by Ice Air, LLC ICE6058.2 02/22
Limited Warranty
Other manuals for VSHPW
1
This manual suits for next models
1
Table of contents
Other ICE AIR Fan manuals
Popular Fan manuals by other brands

emerio
emerio FN-108774 instruction manual

GERMANICA
GERMANICA GF20ACB instruction manual

Skil
Skil 3163 Original instructions

Goldair
Goldair GCMF100 operating instructions

Domus Ventilation
Domus Ventilation Sapphire DME100C Centrifugal dMEV installation instructions

Faro Barcelona
Faro Barcelona Morea manual