manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ideal Boilers
  6. •
  7. Boiler
  8. •
  9. Ideal Boilers CLASSIC SE FF User manual

Ideal Boilers CLASSIC SE FF User manual

SE15P FF, SE18P FF
& SE24P FF
users guide
ENGINEERED FOR PEACE OF MIND
When replacing a part on this appliance use only spare parts that you can be assured
conform to the safety and performance specification that we require. Do not use
reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
Classic
Your Ideal users guide
See reverse for Classic installation & servicing instructions
2
Classic SE Propane FF - Users
Minimum clearances
A clearance of 533mm (21") MUST be available at the front of the
boiler for servicing.
The minimum clearances given below MUST be complied with in
order to maintain the safe running of the boiler and to facilitate
servicing. Above the boiler 100 mm (4")
At each side of the boiler 5 mm (1/4")
Underneath the boiler 100 mm (4")
In front of the boiler 450 mm (17 3 /4 ")
To light the boiler. Refer to Frame 1
1. CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER
ISOFF.
2. Open the controls access door by hinging downwards.
3. Ensure that the gas service cock (D) is OPEN.
4. Press the overheat reset button (E), located as shown in
Frame 1.
5. Ensure that the mains on/off switch (C) is in the OFF
position.
6. Switch ON the electricity supply to the boiler. Check that all
external controls, e.g. room thermostat etc., are ON.
7. Turn the boiler thermostat knob (B) to position 6 and the
mains on/off switch (C) to ON. After about 15 seconds the
boiler will light automatically - this can be viewed through the
sight glass (A).
Set the boiler thermostat to the desired position.
8. Close the controls access door.
In winter conditions, i.e. central heating and domestic hot water,
the thermostat should be set at position 5 or 6.
For summer conditions, i.e. domestic hot water only, the
thermostat should be set at position 3.
These settings, however, are offered for general guidance only
and other settings may be found preferable, dependent upon the
type of system installed or as recommended by the installer.
Approximate flow temperatures for the boiler thermostat settings are:
CLASSIC SE FF(
Propane Gas Models Only)
Introduction
It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this
boiler must be installed by a CORGI registered installer or in
IE a competent person, in accordance with the above
regulations.
Electricity Supply
This appliance must be efficiently earthed.
Supply: 230 V ~ 50 Hz. The fusing should be 3A.
Connection must be made in a way that allows complete
isolation of the electrical supply such as a double pole switch
having a 3mm (1/8") contact separation in both poles, or a plug
and socket, serving only the boiler and system controls. The
means of isolation must be accessible to the user after
installation.
Important notes
a.
This appliance must not be operated without the casing
correctly fitted and forming an adequate seal.
b.
If the boiler is installed in a compartment then the
compartment MUST NOT be used for storage purposes.
c.
The ventilation provided for the boiler during installation
MUST NOT be blocked, and a check should be made
periodically that the ventilation areas are free from any
obstruction.
d.
If it is known or suspected that a fault exists on the boiler
then it MUST NOT be used until the fault has been
corrected by a CORGI registered installer or in IE a
competent person.
e.
Inflammable materials must not be placed in close
proximity to the appliance. Materials giving off flammable
vapours must not be stored in the same room as the
appliance.
f.
Under NO circumstances should any of the sealed
components on this appliance be used incorrectly or
tampered with.
g. Where the boiler is fitted with a Vertex Flue System with a
draught diverter in the loft, the loft space MUST NOT be
used as a dwelling area.
To shut down the boiler
1. For short periods: Turn the boiler on/off switch (C) to OFF.
When heating is again required, restore the switch to ON.
2. For longer periods: Turn the boiler on/off switch (C) to OFF.
Switch the electricity supply to OFF.
Frost protection
If no frost protection is provided and frost is likely during a short
absence from home, leave the heating controls at a reduced
temperature setting.
For longer periods, the entire system should be drained - including
the domestic water supply. If the system includes a frost thermostat
then, during cold weather, the boiler should be turned OFF at the
time switch(es) ONLY. The mains supply should be left switched
ON, with the boiler thermostat left in the normal running position.
Models G.C. Appliance No.
White
Classic SE15P FF ....... 41 395 37
Classic SE18P FF ....... 41 395 38
Classic SE24P FF ....... 41 395 39
Silver
Classic SE15P FF ....... 41-397-72
Classic SE18P FF ....... 41-397-73
Classic SE24P FF ....... 41-397-74
KnobSetting Flow Temperature
°C °F
156 133
261 142
366 152
472 161
577 170
682 180
CAUTION. Toavoid the possibility ofinjury duringthe installation,servicing orcleaning
ofthis appliancecare shouldbe takenwhen handlingedges ofsheet steelcomponents
3
Classic SE Propane FF - Users
1
BOILER CONTROLS
LEGEND
ASightglass
BThermostat knob
CMains on/off switch
DGas service cock (shown in the
OPEN position)
EOverheat thermostat reset button
View inside boiler controls area
Boiler Overheat Thermostat
The boiler is fitted with a safety 'cutout' thermostat. This will shut
down the boiler in the event of overheating. Should this occur allow
the boiler to cool, press the reset button (E) then relight as detailed
in steps 1-8 in 'To light the boiler'.
If the cutout condition still persists turn off the boiler and consult a
CORGI registered installer or in IE a competent person.
Control of water temperature
1. Adjust the boiler thermostat (B) to give the required temperature
for central heating.
2. The boiler thermostat automatically switches the main burner
OFF and ON to maintain the selected temperature.
To relight the boiler
Repeat the procedure 1 - 8, detailed in 'To light the boiler'.
Loss of system water pressure
Boilers fitted with Classic Sealed System Units only
If the red arrow on the unit pressure gauge is set above zero and
the system pressure is seen to fall below this value over a period
of time then a water leak is indicated. In this event a CORGI
registered installer or in IE a competent person should be
consulted.
DO NOT OPERATE THE BOILER IF THE PRESSURE HAS
REDUCEDTO ZERO FROM THE ORIGINAL SETTING.
Escape of gas
Should a gas leak be suspected contact your local gas supplier
without delay.
Do NOT search for gas leaks with a naked flame.
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains, wipe with a damp cloth
and finish off with a dry cloth.
Do NOT use abrasive cleaning materials.
Maintenance
The appliance should be serviced at least once a year by a CORGI
registered installer or in IE a competent person.
THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS,
STATUTORYINSTRUMENT1994,NO.1886,ANDAMENDMENTS
1996,IMPOSECERTAINLEGALOBLIGATIONS ONGAS USERS.
AllCORGIregistered installers carry aCORGIID card, and havearegistration number.Both should be recorded in
your Benchmark Log Book. You can check your installer by calling CORGI direct on 01563 72300
THELOG BOOK SHOULDBECOMPLETED AFTER EACHSERVICEAND KEPT WITHTHESEINSTRUCTIONS
Caradon Ideal Limited is a member of the Benchmark initiative and fully supports the aims of
the programme. Benchmark has been introduced to improve the standards of installation and
commissioning of central heating systems in the UK and to encourage the regular servicing of
all central heating systems to ensure safety and efficiency.
Changing gas cylinders
a. Ensure that the replacement gas cylinder is the correct one for
the installation.
b. Extinguish any fire, flame or source of ignition (including
cigarettes, pipes and pilot lights) before changing the gas
cylinders.
c. Change cylinders with caution.
d. Ensure that the gas cylinder valve(s) is/are closed before
disconnecting an empty cylinder or before removing any plastic
cap or plug on the outlet connection of the replacement cylinder.
Never use tools on cylinder valves, hand wheels or levers.
Note.
Cylinders with threaded connections have a left hand
thread. For cylinders with self-sealing clip-on valves, ensure
that the regulator tap is closed before disconnection.
e. Ensure that the replacement cylinder connections are gastight.
Any leaking vapour will have a distinctive odour. Test by using
leak detection solution around the connections - bubbles will
form if vapour is leaking.
NEVERUSEANAKEDFLAME
f. Itis essential that the correctpressure regulator,with the correct
pressure setting and capacity for the installation, is used in
accordance with the manufacturer's instructions.
g. In the case of a connection on a pressure regulator or gas
appliance which relies upon a sealing washer to maintain a
gastight joint, it is essential to check that the washer is
present and that it is sound and correctly positioned prior to
making the connection. Where the connection relies on a
metal-to-metal seating or bullnose connection to obtain a
gastight joint, it is essential that the mating surfaces be
clean and undamaged.
Under no circumstances should a damaged valve or
connection be used.
h. Where connections are designed to be tightened with a
spanner, it is essential that a spanner of the correct size is
used and that the union is firmly tightened - hand tightness is
not sufficient.
When self sealing valves are incorporated in a gas cylinder,
connection should be made in accordance with the
manufacturer's instructions and tools should not be used.
i. If the continuation of supply is interrupted when a cylinder is
changed, it is essential that all appliance taps are turned off
before the change is made.
j. With bulk storage tanks always ensure that the site is kept
clean and clear of rubbish. Such vessels are designed to be
filled on site by the gas distributors.
GAS LEAK
(usually detected by a distinctive smell)
DO NOT
use electrical switches
DO NOT
look for a leak with a
naked flame
IMMEDIATE ACTION:
•CLOSE
all supply valves.
•EXTINGUISH all sources of ignition.
•Open all doors and windows.
•If leakage cannot be stopped REMOVE CYLINDERS to a
safe place in the open air and advise the supplier. If this
is not possible, evacuate the premises and call the fire
brigade.
•Do not use the installation until it has been checked by a
CORGI registered installer or in IE a competent person.
FIRE
IMMEDIATE ACTION:
IF SAFE TO DO SO
, SHUT OFF THE GAS SUPPLY
Do not attempt to extinguish gas flame by any other means.
Raise the alarm and call the fire brigade statingthata liquefied
petroleum gas cylinder is involved, and give its location.
DONOTGONEARACYLINDERifacylinderisbeingheatedbyfire.
ALERT EVERYONE in the immediate area of the fire and
evacuate the building.
ADVISETHE FIREBRIGADEontheirARRIVALoftheLOCATION
of the cylinder.
If a cylinder is not involved in the fire and it is SAFE TO DO SO,
close all cylinder valves and remove the cylinders to a safe
place.
EMERGENCYACTION
Ideal Boilers, P.O. Box 103, National Ave, Kingston Upon Hull, HU5 4JN. Tel.
01482 492251 Fax. 01482 448858. Registration No. London 322 137.
Caradon Ideal Limited pursues a policy of continuing improvement in the design and
performance of its products. The right is therefore reserved to vary specification without notice.
Ideal Consumer Helpline
Tel: 01482 498660
www.idealboilers.com
EMERGENCYACTION
POINTS FOR THE BOILER USER
Note.
Inline with ourcurrent warrantypolicy wewouldask that youcheck throughthe followingguideto identify any
problems external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than
withthe appliance we reservethe rightto levya charge forthe visit,or forany pre-arrangedvisit whereaccess isnot gained
bytheengineer.
TROUBLESHOOTING- TYPICALNON PRODUCT FAULTS
Problem Solution
Boiler is not working for
central heating or hot water. •Check on/off switch ( C ) is in the ‘on’position.
•Press overheat thermostat (E) - the boiler should then relight –If the fault recurs turn off the
boiler and contact the installer.
Boiler goes through the
ignition sequence but will not
fire for central heating or hot
water.
•Check gas supply (try at another gas appliance e.g. cooker / fire) –If no gas supply then not a
boiler fault –contact your gas supplier.
Boiler is operating
satisfactorily for domestic hot
water but will not operate for
central heating.
•If an external programmer is fitted check that the central heating channel is at an ‘on’period.
•Check that the room thermostat is set at the required temperature. Test the room thermostat
by turning this fully up –if this does not respond contact your installer.
Boiler is operating
satisfactorily for central
heating but will not operate
for domestic hot water.
•If an external programmer is fitted check that the domestic hot water channel is at an ‘on’
period.
•Check that the domestic hot water cylinder thermostat is set at the required temperature. Test
the cylinder thermostat by turning this fully up –if this does not respond contact your installer.
Boiler will not fire the pilot
light is lit but the igniter
continues to spark and the
main burner does not ignite.
•This is a symptom of crossed polarity i.e. the live and neutral supply to the boiler are crossed
over. This is not a boiler fault contact your installer to correct the wiring.
If the boiler is fitted with a
sealed system kit. •Check pressure gauge on the boiler this should read a minimum of 1 bar If below 1 bar re-
pressurise the system via the filling loop. Once pressure reaches 1 bar turn off the tap on the
filling loop and press the overheat thermostat reset button (E) to reset the boiler. If unable to
do so or if the pressure continues to drop after refilling contact your installer.
Boiler cycling on and off the
fan and burner come on for
short periods but the pump
can be heard.
•There is an air lock in the boiler or system popework and the interrupter thermostat is shutting
down the boiler. Vent air from the radiators and ensure all thermostatic radiator valves are in
the open position. If unable to free the air lock contact your installer.

This manual suits for next models

3

Other Ideal Boilers Boiler manuals

Ideal Boilers Buccaneer GTE 4 User manual

Ideal Boilers

Ideal Boilers Buccaneer GTE 4 User manual

Ideal Boilers Henrad SE 30 FF User manual

Ideal Boilers

Ideal Boilers Henrad SE 30 FF User manual

Ideal Boilers Logic Combi C User manual

Ideal Boilers

Ideal Boilers Logic Combi C User manual

Ideal Boilers Optia HE 12 User manual

Ideal Boilers

Ideal Boilers Optia HE 12 User manual

Ideal Boilers Classic Combi FF 280 User manual

Ideal Boilers

Ideal Boilers Classic Combi FF 280 User manual

Ideal Boilers Logic System 15 User manual

Ideal Boilers

Ideal Boilers Logic System 15 User manual

Ideal Boilers Mexico Slimline RS 445 User guide

Ideal Boilers

Ideal Boilers Mexico Slimline RS 445 User guide

Ideal Boilers LOGIC COMBI C24 User guide

Ideal Boilers

Ideal Boilers LOGIC COMBI C24 User guide

Ideal Boilers Buccaneer GTE 5 Datasheet

Ideal Boilers

Ideal Boilers Buccaneer GTE 5 Datasheet

Ideal Boilers 330 RDI User manual

Ideal Boilers

Ideal Boilers 330 RDI User manual

Ideal Boilers H12IE User manual

Ideal Boilers

Ideal Boilers H12IE User manual

Ideal Boilers LOGIC Combi ES24 User manual

Ideal Boilers

Ideal Boilers LOGIC Combi ES24 User manual

Ideal Boilers LOGIC COMBI C24IE User guide

Ideal Boilers

Ideal Boilers LOGIC COMBI C24IE User guide

Ideal Boilers Mexico Slimline CF440 User manual

Ideal Boilers

Ideal Boilers Mexico Slimline CF440 User manual

Ideal Boilers Mexico Slimline RS 3/40 User guide

Ideal Boilers

Ideal Boilers Mexico Slimline RS 3/40 User guide

Ideal Boilers istor HE260 User guide

Ideal Boilers

Ideal Boilers istor HE260 User guide

Ideal Boilers Classic FF 360 User manual

Ideal Boilers

Ideal Boilers Classic FF 360 User manual

Ideal Boilers LOGIC COMBI C30 User manual

Ideal Boilers

Ideal Boilers LOGIC COMBI C30 User manual

Ideal Boilers BOXER C 24 User guide

Ideal Boilers

Ideal Boilers BOXER C 24 User guide

Ideal Boilers INSTINCT 24 User manual

Ideal Boilers

Ideal Boilers INSTINCT 24 User manual

Ideal Boilers Mexico Super RS 3/40 User guide

Ideal Boilers

Ideal Boilers Mexico Super RS 3/40 User guide

Ideal Boilers RD1 User guide

Ideal Boilers

Ideal Boilers RD1 User guide

Ideal Boilers Ideal Esprit HE24 User guide

Ideal Boilers

Ideal Boilers Ideal Esprit HE24 User guide

Ideal Boilers CLASSIC 24 User manual

Ideal Boilers

Ideal Boilers CLASSIC 24 User manual

Popular Boiler manuals by other brands

Buderus 800-24 user manual

Buderus

Buderus 800-24 user manual

Keston C90 User instructions

Keston

Keston C90 User instructions

PENSOTTI PCH 34B-H instruction manual

PENSOTTI

PENSOTTI PCH 34B-H instruction manual

Rendamax R2000 Series Technical documentation

Rendamax

Rendamax R2000 Series Technical documentation

PB Heat SC SERIES User's information manual

PB Heat

PB Heat SC SERIES User's information manual

Sime BRAVA ONE BF User, installation and servicing instructions

Sime

Sime BRAVA ONE BF User, installation and servicing instructions

Burnham SCG 1100-H4 Installation & service instructions

Burnham

Burnham SCG 1100-H4 Installation & service instructions

Well-mcLain SlimFit SF1000 Addendum manual

Well-mcLain

Well-mcLain SlimFit SF1000 Addendum manual

ICI Caldaie REX 7 Instructions for installation, use and maintenance manual

ICI Caldaie

ICI Caldaie REX 7 Instructions for installation, use and maintenance manual

Sime MURELLE HE ErP Series manual

Sime

Sime MURELLE HE ErP Series manual

Austria Email GTS 120 Installation and warranty guide

Austria Email

Austria Email GTS 120 Installation and warranty guide

Beretta EXCLUSIVE installer and user manual

Beretta

Beretta EXCLUSIVE installer and user manual

Bryant BS1 User instruction manual

Bryant

Bryant BS1 User instruction manual

Viessmann Vitoflex RF 150 Installation and service instructions

Viessmann

Viessmann Vitoflex RF 150 Installation and service instructions

Immergas VICTRIX PRO 35 1 I Instruction and warranty book

Immergas

Immergas VICTRIX PRO 35 1 I Instruction and warranty book

Riello TAU 150 N Installation, operation & maintenance instructions

Riello

Riello TAU 150 N Installation, operation & maintenance instructions

Roca LAURA 20/20 Installation, assembly, and operating instructions for the installer

Roca

Roca LAURA 20/20 Installation, assembly, and operating instructions for the installer

Wolf MKS 500 Technical guide and installation instructions

Wolf

Wolf MKS 500 Technical guide and installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.