Inbeca MF 30 WS User manual


Technical Specifications:
- Function Limitations …….. ............................................................. 1
- Production capacity……… ............................................................. 1
- Dimensions .................................................................................... 2
- General Features ........................................................................... 2
General information and installation:
- Introduction .................................................................................... 3
- Unpackaging and inspection........................................................... 3
- Location and levelling….................................................................. 4
- Electrical connection ...................................................................... 4
- Drain and water connexions.. ........................................................ 4
Operation instructions
- Start-up…………….......................................................................... 5
- Verifying operation with the equipment working………………........ 5
Operation principle
- Water circuit….. ............................................................................. 7
- Cooling circuit…… ........................................................................ 8
- Components description……. ...................................................... 11
INDE
X
Process of adjusting, elimination and substitution of
components…............................................................................. 14
Electrical diagram ..................................................................... 19
Troubleshooting … .................................................................... 20
Diagnosis service....................................................................... 21
Cleaning and maintenance instructions
- General ........................................................................................ 22
- Cleaning the ice making equipment……...................................... 22
- Instructions for cleaning the water circuit………… ...................... 23
Control Panel ……..................................................................... 25
Components of Ice making equipment…............................. 26
Type of installation
- Installation in an adjacent room… ............................................... 28
- Installation in a false ceiling….. ................................................... 29
- Ice fountain semiannual maintenance….. .................................. 30

TECHNICAL SPECIFICATIONS
MODULAR ELECTRONIC ICE EQUIPMENT
mod. GEL-MF 30
¾ OPERATION LIMITS
MIN MAX
Environmental temperature 10º C 40º C
Water temperature 5º C 35º C
Water pressure 1 bar 5 bares
Variation with regard to plate tension -10% 10%
¾ PRODUCTION CAPACITY
NOTE: The daily production capacity change when the environmental
temperature and the water supply change, a capacidad de producción
diaria varía al variar la temperatura ambiente y del agua de alimentación
, thus the space around the equipment..
So as to mantain the equipment in maximum efficient conditions, it is
necessary to do the periodic maintenance as explained in the
correspondence part of the manual
1

¾ DIMENSIONS OF THE EQUIPMENT
High (Whitout
base) 525 mm
High (with base) 542 mm
Wide 560 mm
Deep 533 mm
Weight 49 Kg.
¾ MF – 30 GENERAL FEATURES
Model Cooling Material Compr. CV
Water consumption (l/24
HR)
MF 30 AS Air Stainless 3/4 200
MF 30 WS Water Steel 3/4 850 *
Ampere Electrical cons. Cable Fuse
Tension Amperes Start-up Power Kw h by 24 HR Section Amperes
230 / 50 / 1 4 20 760 W 17 3 x 1 mm 2 10
* To 15º C of water tem
p
erature
2

¾ INTRODUCTION
¾
This operation manual has been writing to give the technical
specifications as well as all the instalation instructions, start-up,
operation, maintenance and cleaning the modular equipment of ice
crusher and super ice crusher of MF electronic range.
The electronic equipment of ice crusher and super ice crusher has been
designed and manufactured with high quality level.
The equipment is tested during several hours and reassure a maximum
performance in whatever use and situation.
2. Check the external cartoon packaging and the wood platform used for the
delivery. Whatever obvious damage in the external packaging has to be notify
to the transport; in this case check the equipment with a representative of the
transport agency.
3. a) Cut and take out the plastic ribbons that mantain seale the cartoon
packaging.
b) Take out the cramps that fix the cartoon in the platform.
c) Open the upper side of the packaging and take out the V
protective angular plate
d) Lift the cartoon taking it out of the equipment.
4. In models MF 22, MF 30, MF 41 Y MF 51 take out frontal panel / saque el
frontal / top panel , while in model MF 61 take out top and lateral panels and
check the unit so as to verify it has not been damage during transport.
5. Take out the inner supports used for the transport as well as adhesive
ribbons.
6. Check the pipe of the cooling circuit do not graze between them and it do
not touch other pipes or surfaces; make sure the fan spin freely.
7. Check the compressor it is free of swing above their own shock absorbers..
8. Observe the details of the plate located in the back part of the frame near
the water and electrical connexions and check that the voltage of the electric
net it is suitable for the equipment.
ATTENTION: A wrong voltage of electric supply will cancel
automatically the warranty.
9. Fill in the warranty coupon located inside the User manual, refer to the
model and the serial number of the unit located in the plate fixed to the frame.
Send the coupon to your local distributor.
INSTALLATION AND GENERAL INFORMATION
NOTA: It is recommended when making the installation and the maintenance
operation, follow this manual so as not to damage or reduce the quality and
security characteristics of the equipment.
- Store of ice
The equipment model MF do not have pile ice dispenser basin, thus it is
necessary to design and build one with the material most suitable according
the the decoration of the room. Having into account the following points:
The high of the basin has to be between 90 and 100 cm to make easy the
pick up of the ice.
The dimensions of the ice dispenser has to be approximately of 60 cm wide
x60 cm deep x20 cm high.
It has to have a drain to throw away the ice.
¾ UNPACKAGING AND INSPECTION
- Ice equipment
1. Ask the assistance of the official distributor for a correct installation.
3

Before connecting the ice equipment with the electric line, check the ampère
again of the unit, detail in the plate, with the correspondent ampère of the
electric supply.
¾ WATER AND DRAIN CONNEXION
- General
When choosing the water line for the modular crush and supercrush ice
equipment of model MF take care of the following: la serie MF,
a) Length of the line
b) Clear and pure water
c) Suitable pressure of the line.
¾ LOCATION AND LEVELLING Water is the most simple and important ingredient for making ice, for this
resason the previous points are very important. A low pressure of water,
below 1 bar can origin problem with the operation of the unit.
Water that contains and excess of minerals can produce a residuum sheet
in the inner parts of the water system, meanwhile a soft water containing
lower mineral salts produce a granular ice too “dry”.
ATTENTION: this ice equipment has been designed to be installed in
areas where the room temperature do no exceed the maximum of 40 º C
nor the minimum of 10 º C
Prolonged period of operation with temperature different ot the
mentioned represents a wrong use of the equipment and suppose the
nullity of the guarantee.
¾ ELECTRICAL CONNEXIONS
To choose the kind and section of the cable observe the ampère indicated in
the plate of the equipment.
All the equipments has an electric supply cable, so it is needed a conection
to the electric line equipped with earth cable and with magnetothermic
switch with fuse appropriate as it is indicated in the plate of each equipment.
The maximum ampere variation permitted does not have to exceed a 10%
of the plate or be less than a 10% of the same.
A lower ampère can produce an anomalous operation and make damage
seriously the protection device and the electric winding.
NOTE: All the external connexions has to be perfect, according with the local
laws. In some cases it is needed the intervention of a qualified electrician..
A
TTENTION: Using soft water (lower mineral salt) with less electric
conductivity of 30 mS don’t let the low tension electricity to go
through between the sensors of water level, causing the stop or wrong
function of the unit.
Chlorine water or ironish water can be partially improve with active coal
filters.
- Inlet of water
Connect the male connector to the water inlet of 3/4" Gas to the water line
using a reinforced plastic pipe with non-polsonous material for food or a
copper pie with external diameter of 3/8".
The inlet water line has to have a stopcock located in an accessible place
near the unit. If water has a high level of impirites it is recommended to install
a fitler or a purifier to prepare it appropriately.
- Water inlet – Water cooling models
The models cooled with water need two separate inlet lines; one for the tank
and the other one has to go through one adjustment mechanic valve to the
cooling condenser.
Also for the water connection of the condenser use a reinforced plastic
flexible pipe or a copper pipe of 3/ 8 with female connector of+" Gas and a
separet bypass valve.
4

¾CHECKING THE PERFORMANCE WITH THE UNIT WORKING
D. Take out the front panel and if it is needed put the high and low pressure
gauge in their corresponding tyre valve to check the condensation and air
intake pressure.
- Drain
It is recommended a rigid plastic pipe with internal diameter of 18 mm and
constant flow of 3 cm per meter. The draining of remainder water it is made
by gravity; it is necessary a drianing with vertical air inlet near the connector
and that it go to the open siphon for a constant flow.
- Drain – Model cooled with water
The equipment cooled with water need a new line of drain separet with a
male connector 3/4" Gas that comes with the indication “Drain- Only for
cooled with water".
C. After the compressor work 2 or 3 minutes, check that the ice go out
through the unloading hole and through the pipe go to the store.
NOTE: All the water connections has to be perfect and realise according to
the local laws. In some cases it is necessary the intervention of a qualified
plumber.
¾ STARTING
A
fter a correct electrical, water and drain installation, follow the next
instructions for the starting up:
A. Open the tap and connect the plug or electric general switch located in the
electrical connexion line. The first GREEN LIGHT will light, showing the unit
is under tension.
OPERATION INSTRUCTIONS
NOTE: When the unit has been some time disconnected, the RED LIGHT
it is flashing during 3 minutes; afther these minutes it will start the motor ot
the gear reduction and after 5 seconds the compresor.
B. After the 3 minutes, the unit will start up activating the
following components:
- MOTOR / S REDUCTION GEAR COMPRESSOR
- MOTOR / S OF FAN(if the unit is cooling with air), controled by the
temperature sensor of the condenser located in the wings of the same.
NOTE. The first ice granule present a scarce consistence because the
temperature of evaporation still have to reach the normal functioning
value. Wait 10 minutes so as the evaporation temperature go down to
the normal functioning values so as the ice has the correct consistence.
NOTE. If after 10 minutes of being working the equipment the
temperature of the evaporator has not reach below 1°C due to an
inadequate quantity of cooler, the temperature sensor of the evaporator
detects this abnormal situation and consequently stop the unit. In this
circumstance, the YELLOW LIGHT switch on.
After diagnosing and eliminating the problem of this poor
evaporation temperature due to inadequate quantity of
cooler or excessive condensation temperature, press the
boton RESET located in the lid of the control
After 3 minutes, with the RED LIGHT flashing, the unit will start working.
5

F. Check the correct function of ice level control electronic eyes, put the
hand between the two sensor located in the outlet pipe. (one in every
pipe in model MF61). In this way it is interrumped the beam and switch
off the RED LIGHT located in the front side of the electroic
Card. After 6 second the unit stops automatically and switch
On the YELLOW LIGHT showing the situation FULL CABIN.
The beam of light is retablished after 6 seconds, the unit will start up
Automatically (after de 3 minutes of delay) and the yellow
Light that has been switched on before.
NOTE: in the air cooled models, the condensation pressure remain
between two values preestablished throught the fan, sending
intermittently through the sensor located in the wings’ condenser.
If the condensation temperature reach to 70 º C due to
and obstruction in the condenser and/or the motor of the
fan do not work, the sensor temperature of the condenser
stop the unit and consequently a RED LIGHT of danger is
switch on.
After diagnosing and solving the problem, repit the operation indicated in
the previous “Note” to start up again the unit.
E. Check the correct functioning of the water level sensor, close the
stopcock. After some minutes when the level of water
Go down the sensor, the unit will stop and inmediately
switch on the YELLOW LIGHT showing the lack of water.
NOTE: The water level sensor detects the presence of inadequate quantity
of water in the tank and it confirms it to the microprocessor manintining an
electric low ampère flow through the sensors using the water as a
conductive material.
ATTENTION. To use demineralize water (water whitout or with little
salt) with a electric conductivity of less than 30 mS not allow the
lower tension electricity to pass making the unit to stop or not
functioning, a YELLOW LIGHT swith one showing a lack of water.
After open again the stopcock, the YELLOW LIGHT switch off automatically
and a RED LIGHT is flashing. After 3 minutes the unit start up again, first
the reduction gear and after 5 seconds the compresor.
NOTE. The control level of the ice (infrared system) is independent of the
temperature, otherwise it can be affected for the external light and the dirty or
lime deposits located directly in the eyes(infrared sensors).
For a correct operation of the unit it necessary to install it far away of direct
point of light and to scrupulously observe the points mentioned in the
maintenance of the eyesde los ojos.
G. If they are instaled take out the auxiliar manometers and install again the
frontal panel that have been taken before.
H. Explain to the owner the function of the ice equipment as well as the
cleaning and maintenance of the same.
6

¾ WATER CIRCUIT
Water enter into the machine by the inlet line, where there is a small arille filer
located in the back side and here reach the wáter tank going through a float
valve.
PRINCIPLE OF OPERATION
NOTE: The presence of water in the tank is detected by a system of two
sensors that work together with the electronic board. Both sensors use the
water as a conductive to maintain a electric flow of low voltage that it is send
to the electronic board showing the presence of water in the tank. The lack of
water or the presence of soft water with an electrical conductivity with less of
30mS (demineralize waters)means the interruption of electrical flow to the
electronic boards and consequently the stop of the unit and the switch on of
the YELLOW LIGHT of ” lack of water”.
Tank of wáter is located allied of the evaporator case to a high that allows
through the communicative pipes, maintain constantly a correct level of
wáter inside the evaporator case.
Water enters from the tank through the conexion pipe inside the
evaporator case, where it is unfreeze and it is transformed in ice; this is
constantly mantained in movement by a stainless steel shaft that turn
inside the evaporator case.
The shaft, sumerge in water inside the evaporator turn in antitimetable
direction by the action of a reductive motor, pushing up the sheet of ice
that is formed in the internal cooled walls of the evaportor.
The ice, when it is push up by the shaft becomes more thick and when it
reach the crush it is compacted and cut into pieces, going through the outlet
pipe and falling into the ice keeper.
When the unit start up, it start up the continuous process of ice making,
process that continue until the ice keeper is full until the level sensors located
in the pipe of outlet ice.
When the ice interrumps the infrared beam of light between both electronic
eyes ( one or both in the model MF 61), the unit stops, the YELLOW LIGHT
switch on that shows the situation of full cabin.
7

The liquid circuit lead the
refrigerant from the condenser
to the capillary tube through a
dehydrated filter.
When the refrigerant in liquid state
goes through the capillary tube
lose gradually a part of pressure
and a part of temperature.
Then it reachs and enter in the coil
evaporator. Water in contact with
the cooled walls of the evaporator
give heat to the refrigerant that
flow inside the coil, making its
evaporation and the consequent
change of liquid state into steam.
The regrigerant in steam state after
going through the accumulator it is
suck in again in the compressor
trhough the aspiration line.
NOTE: The interruption of the beam between the sensors is inmed
i
ately
showed by the switch off of the RED LIGHT located in the electronic board.
Afther the interrumption of the beam of light during 6 seconds, the unit stops
and the YELLOW LIGHT switch on. The 6 seconds of delay protect the unit
of unnecessary stops due to the eventual interruption of the beam of light,
that can be produced for the fall of the ice through the pipe.
When the ice is taken out of the store cabin and the outlet pipe get free, the
beam of light between the two sensors is inmediately reestablished and the
RED LIGHT is switch on in the centre of the board. After 6 seconds the unit
start up again, the YELLOW LIGHT of full cabin switch off and after 2-3
seconds the ice fall again through the pipe.
¾ COOLING CIRCUIT
The refrigerant in gaseous state and high temperature it is pumped from the
compressor, going through the condenser and it is transformed in regrigerant
in liquid state.
The pressure of push of the refrigerant system (high pressure) it is mantained
between the previously establish values (8/9 bar for MF 22 and 17/18 bar for
MF30, MF 41, MF 51 Y MF 61) through the temperature sensor of the
condenser that has the probe located inside the sheet of the condenser, in th
e
air cooled models.
This sensor notice the increase of temperature in the condenser above the
established limit, change its electric resistance and send low tension electricit
y
to the MICROPROCESSOR of the electronic board that supply through a triac
the fan motor in intermittend way ON – OFF.
8

In water cooled models, the high pressure of the system is constant
to 8.5 bar in model MF 22, and to 17 bar in models MF 30, MF 41, MF
51 Y MF 61, due to a quantity of water that goes through the
condenser, which flow is controled by the action of the presostate
valve that it is open to increase the water flow that cool the
condenser.
9

NOTE, In case the temperature sensor of the condenser detects 70ac ' in the
cooled air model or 62º Cin the water cooled version for one of these
reasons:
- DIRTLY CONDENSER (cooled by air)
- INADEQUATE CONDENSATION WATER (cooled by water)
- BURNT FAN OR STOPPED (cooled by air)
- HIGH ROOM TEMPERATURE (UP TO 43° C)
the unit stop inmediately so as to prevent to be working in extremely
abnormal and dangerous situation. When this happens it switch on the RED
LIGHT,that warn of high temperature.
After eliminating the cause of excessive temperature in the condenser,
push button RE-SET.
The RED LIGHT will flash and after 3 minutes the unit will start working. The
temperature sensor of the condenser has also another option for security, it
consist in preventing the start up of the unit if the room temperature (detected
by the sensor of the condenser) in where it is installed the unit is less than 10
C.
When the room temperature is up to 10º C, the electronic board start up
again the unit automatically after 3 minutes.
The pressure of air intake or low pressure in normal conditions is of 0.5 bar in
model MF 22 and 2.4+2.6 bar in model MF 31, MF 41, MF 51 Y MF 61 after
some minutes of operation. These valuer can change between 0.1 bar or 1.2
bar, in relation with the water temperature that supply the evaporator.
NOT
E
If after 10 minutes of operation not produce ice and the tempertaure
registered by the sensors of the evaporator do not reach -1 C, the unit stops
and switch on flashing the 5th YELLOW LIGHT
COOLING EXPANSION DEVISE: Capillary pipe
PRESSURE OF OPERATION (With a room temperature of 21º)
Pressure of impuls: MF - 22 MF 30 - 41 - 51 - 61
Cooling by air 8 / 9 bar 17 / 18 bar
Cooling by water 8,5 bar 17 bar
Pressure of air intake: 0,5 bar 2.5 bar
COOLING CHARGE (R 134 A)
Cooling by air Cooling by water
MF 22 440 g 380 g
COOLING CHARGE (R 404 A)
Cooling by air Cooling by water
MF 30 540 g 410 g
MF 41 750 g 600 g
MF 51 880 g 820 g
MF 61 2200 g 1300 g
NOTE: Before charging the refrigerator system, check the technical data of
the identification plate of the unit for the kind of indentification of the
equipment as well as the kind of refrigerant and the quantity
10

¾ DESCRIPTION OF COMPONENTS
A. TEMPERATURE SENSOR OF THE EVAPORATOR
The sensor of temperature of the evaporator, located inside a bulb pipe, it is
welded in the outlet of the freezer tube, register the temperature of the
refrigerant aspirated transmitting a signal (low tension electricity) to the
microprocessor.
Depending on the signal received, the microprocessor give green light to the
ice equipment to continue working (evaporation temperature below -1°C after
10 minutes working or in case there is a lack partially or totally of refrigerant in
the system, stops the equipment flashing the 5a YELLOW LIGHT
(evaporation temperature above -1°C after 10 minutes of operation).
B. SENSOR OF WATER LEVEL FLOAT TANK
The sensor of water level of the flowt tank it is composed of two stainless
steel sensors vertically anchored to the lid and connected electrically to the
low tension circuitry of the electronic board.
Its lower extreme is sumerged in the water tank and throught a current of flow
that it is transmitted through the mineral salt of the water, mark its presence to
the electronic board.
NOTE. The lack of water or the presence of water whitout mineral salt
(electrical conductivity below 30 mS)means the interruption or reduction of
the electric current transmitted to the electronic board, with the consequent
stop of the unit, show with the switch on of the YELLOW LIGHT.
In the models cooled by air, the probe of the condenser control also the
operation of the fan motor through a MICROPROCESSOR of the electronic
board. Using the TRIAC, tjos start up the motor of the fan removing the heat
of the condenser and consequently lowing the temperature.
If the temperature of the condenser is above 62°C to 70°C depending on the
position of the microswitch number 8, the signal that arrives to the
MICROPROCESSOR make to stop the unit.
C. SENSOR OF TEMPERATURE OF THE CONDENSER
The sensor of temperature of the condenser (located between the wings of
the air condenser or in contact with its coil in the case of water condenser)
registers the temperature of condensation and transmitt the variations
sending a signal to the electronic board.
In case the temperature of sensor of the condenser have a value below +3°C
(room temperature too low), the electronic board don’t start up the unit the
temperature of the probe gets to +10°C.
NOTE. So as the unit start up again, push the button REARM (after solving
the cause that has produce the stop) or unplug and plug again the unit.
D. SPEED SENSOR AND DIRECTION OF MOTOR IN THE REDUCTION
GEAR (Two in models MF 61)
The sensor of speed and the direction of rotation of the motor in the reduction
gear (one for each motor in model MF 61). Register through a magnetic
signal (effect hall) the speed and direction of rotation of the motor. When it is
below 1300 revolutions by minute, the signal transmitted to the
MICROPROCESSOR of the electronic board stop inmediately the unit and it
switch on a YELLOW LIGHT.
The same happens when the motor run in the incorrect direction avoinding
that the ice inside the evaportor make a unic body with the axis.
NOTE. To start up the unit in both cases ( slow don and attempt opposing
rotation) push button rearm (after solving the cause that has produced the
stop) or the switch and the electrical connexion.
11

E. OPTICAL SYSTEM OF ICE LEVEL CONTROL (Two in the models MF
61)
The optical system to control the level of ice (one for each discharge pipe in
model MF 61), installed inside the ice discharge pipe, stop the unit when the
level of ice interrumpt the beam of light(by infrared) transmitted between the
two electronic eyes.
When the beam of light stop, the RED LIGHT in the centre of the electronic
board switch off; the continuos stop of the beam of light during more than 10
seconds stop completly the unit switching on the second YELLOW LIGHT.
The 10 seconds of delay for the stop of the unit prevent that the unit stops by
a chance and undesired interrumption of the beam of light (pieces of ice that
fall for the discharge pipe)
En cuanto se quita el hielo para que el haz de luz pueda volver a pasar entre
los ojos electrónicos, la LUZ ROJA vuelve a encenderse inmediatamente
arrancando, después de 10
F. ELECTRONIC BOARD
The electronic board, located in a plastic box fix in the front part of the unit,
consists of two separate printed circuit, one of high voltage and the other one
of low voltage, protected by three fuses, integrated it by a button RE-SET
(REARM). There are also 5 lights indicating the operation of the unit, one
extra RED LIGHT , 8 DIP SWITCH of switching inlet and some connection
terminals with the inlet peripherals (sensors) and outlet peripherals (electric
components). The electronic board is the brain of the system and process
through the microprocessor, the signals received by the sensors to control
the functioning ot all the electric components of the unit (compresor,
reduction gear, etc).
The five LIGHTS in the front of the electronic board show the following
situations:
GREEN LIGHT:
Low tension unit / operation
YELLOW LIGHT:
Unit stop storage full
RED LIGHT FLASHING:
3 minutes of delay
RED LIGHT FIX:
Unit stop for high temperature of condensation
Unit stop for room temperature below 3ºC
YELLOW LIGHT:
Unit stop low level of water in the tank
YELLOW LIGHT FIX:
Unit stop rotation in the opposite direction of
The motor in the reduction gear
Unit stop for speed of rotation of the motor,
Reduction gear too low
YELLOW LIGHT FLASHING
Unit stop for high temperature of evaporation above – 1º C
after 10 minutes of working
12

G. TANK FOR THE FLOAT
The tank has a plastic box with a float with screw of adjustment in the top that
mantains a constant level of water in the tank and with communicating
vessels inside the evaporator.
In the lid there are two sensors to control the level of water that signs to the
electronic board the presence of water in the tank.
J. REDUCTION MOTOR (two in model MF 61)
It has an asynchrounous one-phase motor with a condenser installed in
reduction gear box of gears and pinions, the reduction motor activate through
a transmission connection the axis of elevation of ice located inside the
vertical evaporator.
The rotation of the motor, subjected by two ball bearing of permanent
lubrication, transmit the movement to a fibre gear (to reduce the fluid) of it,
with a pair of gears and pinions subjected by the roller gears located in the
upper and lower extreme of the outlet axis.
The reduction gear is seal, by the presence of thw retainers installed in the
hole of rotor axis and outlet axis and it is lubricated with specific grease
(MOBILPREX IP 44).
K. MOTOR OF THE FAN (Models cooled by air)
The motor of the fan is comanded through the TRIAC of the electronic board, by the
sensor of temperature of the condenser. It works making to flow the air thorugh the
sheets of the condenser. In conditions with a low room temperature, it can
intermittently work to maintain the condensation temperature between the
pressetablished values.
L. PRESOSTATIC VALVE (Model cooled by water)
The presostatic valve mantains a contant value of high pressure in the
cooling circuit changing the water flow in the condenser. When the pressure
increase the presostatic valve interiorily opens to increase the flow of water in
the condenser.
M. COMPRESOR
The hermetic compresor is the heart of the system and it makes the
refrigerant to circulate in the refrigerator. It intakes the refrigerant as a low
pressure and low temperature steam and it transforms it as high pressure
and high temperature steam, sending it to the circuit through the discharge or
high valve.
NOTE. It is very important to place correctly the lid in the tank of the float, so
as to the sensors be submerged and can transmit an electrical signal that
confirms to the electronic board the presence of water in the tank and avoid
inopportune stop of the ice equipment.
H. EVAPORATOR (Two in model MF 61)
The evaporator has a stainless steel vertical pipe in which external side it is
solded the evaporation chamber of the refrigerant and in which in the interior
there is the axis that turns and it is mantained in axis by the action of the top
and lower treads. In the lower part of the evaporator there is a retention ring
that hermetically seals it, while in the top part there is the ice crusher
machine.
I. CRUSHING RING OF ICE (Two in model MF 61)
The crushing ring of ice is on the top side of the evaporator and it has in
models MF 22-30, two cogs to crush the ice; with its inclined shape (the back
cogs to front) compress and force the ice to come out in horizontal direction.
In the other models, the ice crusher equipment has some rectangular holes
through the ones the ice is compressed. In this way, the ice loses the excess
of water and fall to the storage in compact and dried grains.
In the crush ice machine there is a top tread, and it has two stainless steel
rolling crowns located in a way that can support the axial and radial load of
the axis.
NOTE: It is recommended to check every 6 months the state of the lubricant
as well as the upper tread. 13

A. ADJUSTMENT THE WATER LEVEL IN THE EVAPORATOR
2. To drop the level of water make the same as before but putting down the
tank.
PROCESS OF ADJUSTMENT, REMOVAL AND
SUBSTITUTION OF THE COMPONENTS
NOTE: Reas carefully the following instructions before make a substitution or
adjustment process.
The correct level in the
evaporator is 25mm
below the outlet ice
hole (discharge hole).
A lower level of water
can cause a major
rubing of the ice and of
the axis due to a
quickly freese of water.
When the level of water is above or below than the normal level, the
regulation consists in raising and droping the level of water moving up or
down the tank
1 To raise the level of water act as following:
-a)Take out the screw that fix the support of water tank and raise it all
the necessary until it reach the level required.
-b ) Put the screw in the correspondent drill holes and tighten it.
ATTENTION. Before doing this regulation makes sure that the problem
is the level of water (check troubleshooting). Make sure the electric
supply is disconnected and the stopcock of water close so as to
prevent damages.
B. SUBSTITUTION OF THE SENSOR OF TEMPERATURE OF THE
EVAPORATOR
1.Take out the fornatl /upper panel.
2. Take out the isolation of pipes that connect the evaporator with the
storage heater to accede the bulb tub weld in the pipe of the cooling pipe
outlet and take out the inner sensor of temperature.
3. Look for the connection of the evaporator’s sensor in the back side of the
electric box and disengage it making prise with the anchored tab.
4. To install again the sensor of the evaporator follow this process on the
other way round.
C. SUBSTITUTION OF THE SENSOR OF TEMPERATURE OF THE
CONDENSER
1. Take out the frontal / upper panel and in model MF61 take out also the
right side panel.
2. Look for the sensible bulb of the condenser sensor placed between its
wings and in the models cooled by air and take it out. In models cooled by
water take the bulb out after open the plastic bracket (it can be used again)
that fix it to the pipe of the liquid.
3. Look for the connection of the sensor of the evaporator in the back side of
the electric box and disengage it making prise with the anchored tab.
4. To install again the sensor of the evaporator follow this process on the
other way round.
14

D. SUBSTITUTION OF OPTICAL CONTROL OF LEVEL OF ICE
1. Take out the upper /frontal panel in models MF 22, MF 30, MF 41 Y MF 51
and take out the frontal/ back panel in model MF 61.
2. Look for in the back side of the electric box the optical control conexión of
level of ice with 4 plugs of white colour and disengage it from its place making
prise with rubber anchored tab.
3. Take out the two electric eyes of its light port take them out of the drills
located in the two opposite side of the outlet discharge hole, making pressure
in the external part of the rubber elements, take attention so as not to
damage the sensible side (infrared reader)
4.To install again the optical control of ice level follow this instructions on the
other way round.
E. SUBSTITUTION OF CORRECT SENSOR OF ROTATION IN THE
MOTOR (HALL EFFECT)
1.Take out upper/frontal and side/back panel in models MF22, MF30, MF41
and MF51, while in model MF61 take out the left side/upper panel..
2. Unscrew the screws that fix the plastic lid in the place of the magnetic
sensor and take it out.
3. Unscrew the two screws that fix the sensor in the plastic space and take it
out.
4. Look for in the back side of the electric box the connection of the rotation
sensor of 4 red plugs and disengage of its place making prise with the
anchored tab.
5. To install again the sensor of correct rotation of the motor follow this
instructions on the other way round.
F. SUBSTITUTION OF SENSOR OF WATER LEVEL IN THE TANK
1. Take out the frontal/upper panel.
2. Unscrew the anchore nuts from the connection of cables of both stainless
steel bars –sensor of level of water-located in the float tank.
3. Look for in the back side of the electric box the connection of the sensor of
level of water from two red plugs and disengage it from its place making prise
with the anchored tab.
4. To install the new sensor of level of water follow this instructions on the
other way round.
G. SUBSTITUTION OF THE ELECTRONIC BOARD
1. Take out the frontal/upper panel.
2.Look for in the back side of the electric box the connections of the sensors
and disengage them of its location making prise with the anchored tab.
3. Disengage from the back side of the electronic board the terminal of the
electrical connections, after that take out the electronic board unscrewing the
4 screws that fix it to the plastic electric box.
4. To install the new electronic board follow this instructions on the other way
round.
H. SUBSTITUTION OF THE ICE DISCHARGE HOLE
1. Unscrew the nuts and take out the upper/frontal panel.
2. Take out hte nut and the cutting edge of the ice discharge taking attention
of not to damage the electronic eyes.
3. Slacken the two brackets that fix the polystyrene insulater in the upper part
of the evaportor and take out the two parts of the insulator.
15

6. Install the new entrance following this instructions on the other way round.
I. SUBSTITUTION OF THE AXIS, RETENTION RING, BALL BEARING
AND JOINT.
1. Unscrew the screws and take out the upper/frontal panel.
2. Follow the instructions detailed in point H to take out the ice discharge
entrance..
3. In models MF22-30 unscrew and take out the two screws and washer that
fix the support of the discharge entrance. In models MF41, MF51 and MF61
unscrew and take out the 4 nuts that fix the crushing ice euipment to the
upper clamp in the evaporator.
4. In models MF22-30 hold the ring located in the upper part of the ice
crusher in the evaporator and pull up to take out the axis, the lid and the ice
crusher. In models MF41, MF51 and MF61 introduce the end of screwdriver
in the space between the ice crusher and the upper clamp and turning rise
the axis/ice crusher. Take the ice crusher and take out the axis/ice rusher
taking it out from the evaporator.
4. In the models MF22-30 take out the stainless steel entrance of its bronze
part while in the other models inscrew the two nuts that fix it to the crush ice
equipment.
5. In the models MF22-30 unscrew the two screws taht fix the bronze
entrance to the evaporator and release it.
5. In models MF22-30 using a nipper of seeger take out the seeger washer
that fix the lid in the ice crusher while in the others models make prise with a
screwdriver and take out the lid of the ice crusher.
6. Unscrew and take out the head nut that fix the ice crusher to the bearing in
the axis, then take out the ice crusher from the nut.
7. Take out the exceed of grease inside the ice crusher and analise the state
of the binding and if it is not in good condition replace it.
8. Analise with attention the bearing located inside the ice crusher. If there is
a damage or lack of lubricant replace it.
NOTE. In models MF22-30 inspect the rectangular binding of the rubber
entrance and if it is damage substitute it.
NOTE. IF you can’t take out the axis/ice crusher f rom upper part, follow
instructions in points 10 and 11 as to do it from the interior side. Using a
wood hammer or plastic hammer, knock the inferior extreme side of the axis
to back off and take it out from the upper side of the evaporator..
ATTENTION. The upper ball bearing works in extreme condition making
reference to lubrication due to it is inside the ice crusherwhere there is
always so much condensation liquid. It is necessary to use fat and
water repellent to guarantee a correct lubrication.
9. Take out the inferior side of the axis, the turning washer from the gland
seal system..
ATTENTION. Every time you dismantle the axis to make a control or
substitution, take attention so as not to enter dirty inside the evaportor
and that the dirty don’t reach the surface carbon in the ring retention. If
you have doubts replace the ring.
10. Unscrew and take out ¾ nuts that fix the aluminium support in the inferior
side of the evaporator.
11. Raise the evaporator taking it out of its support then in models MF22-30
with a wood or plastic tool push the evaporator to the outward from the
inferior extrem as the retention ring as the inferior ball bearing. If it is
necessary use a hammer.
16

12In models of super crushing with the end of two screw drivers make prise
in the inferior extreme of the bronze ring.
18. Put lubricant and put the steel washer.
19. After substituting the O-ring in the rusher ice machine, install it in the
inner side of the axis and fix it to the upper nut.
20. Install the axis/crusher ice equipment in the evaporator following the
above instruction on the other way round.
J. SUBSTITUTION MOTOR OF THE REDUCTION GEAR
1 Take out the frontal/upper panel and back/side panel in models MF22,
MF30, MF41 and MF51 and in model MF61 the frontal panel and the left
upper panel.
2. Unscrew the ¾ nuts that fix the evaporator in the upper body of the
reduction gear.
3. Take out the sensor of rotation direction following instructions in section E,
unscrew the screws that fix the motor of the reduction gear in the framwork.
4. Disconnect the motor of the electrtical conexión of the unit. The reduction
gear now can be substituted.
5 To install the new motor of the reduction gear follows the instructions on the
other way round.
NOTE. It is recommended to substitute the mechanic retention ring, the
ball bearing upper and inferior as well as the bindings or every time the
evaporator is dismantled. There is one kit with these spare parts
number 001028.07 for MF22-30 and number 001028.08 for MF41-51-61
with a fat tube and water re
p
ellent.
13. From the interior of aluminium support, take out the components that
integrate the transmision connection.
14. Check the two half-connections, if they are not in good conditions replace
them.
15. Install the inferior ball bearing in its bronze place taking attention with the
plastic ring.
16 Install the upper ball bearing in the crush ice equipment starting from the
radial side that has to be installed with the flat side.
17. Put lubricant in the upper side, and install the ball bearing box with the
small holes upwards to give a free movement between the plastic box and
the flat area of the inner side of ball bearing (check picture).
NOTE. Drain carefully the cooking circuit to remove excess of humidity and
the condensation gas after substituting the condenser..
K. SUBSTITUTION OF WATER CONDENSER
1. Take out hte frontal/upper panel and side/upper panel in models MF22,
MF30, MF41 and MF51 and the frontal/right side panel in model MF61
2. Take from the condenser the sensitive bulb of the sensor.
17

3. Unscrew and take out the nuts that fix it in the base.
4. Unscrew the brackets of the tub and disconnect the plastic pipes from the
two end of the condenser.
5. Get the refrigerant out of the system and let it in a tank to use it again after
treat it.
6. Unweld the pipes of the cooling installation from the two end of the
condenser.
NOTE. Purge carefully the cooling circuit to remove the excess of humidity
and the no condensation of gas after the substitution of the presostathic
valve.
NOTE. Sustitue the dehydrate filter every time the cooling refrigerant is open.
Do not put the dehydrate filter until the reparation or substitution process is
finished..
7. To install a new condenser follow the instructions on the other wa
y
round.
NOTE. Purge carefully the cooling circuit to remove the excess of humidity
and the no condensation gas after the substitution of the condenser..
L. SUSTITUTION OF THE PRESOSTATHIC VALVE (UNIT COOLED BY
WATER)
1. Take out frontal/upper panel and back side panel in models MF22, MF30,
MF41 and MF51 and left side panel in model MF61.
2. Close the stopcock of water and disconnect the pipe from the presostathic
valve from the back side of the unit.
3. Get the refrigerant out of the ysstem and let it in a tank to use it again after
treat it.
4. Unscrew and take out the capillary pipe from the presostathic valve from
the refrigerator circuit.
5. To Install the new presostathic valve follow this instruction on the other way
roundl.
NOTE. The flow of water that go through the presostathic valve has to be
adjusted using the screw located in the upper side of its rod until the
condensation pressure is of 8.5 bar in MF22 and 17 bar in MF30,41,51,61..
M. SUBSTITUTION OF THE CONDENSER
1. Take out the forntal/upper panel and back lateral panel in models
MF22,MF30, MF41 and MF51 and frontal panel in model MF61.
2. Take out the lid and disconnect the electrical cable from the connections in
the condenser.
3. Get the refrigerant out of the system and let it in a tank for using it again
after drain it.
4. Unweld and disconnect the impulsion pipe and the aspiration pipe pof the
compresor.
5. Unscrew the screws that fix it in the base and take the compresor out of the
base of the unit.
6. Take out hte auxiliar/load pipe and reserve it to weld it again in the
compresor.
7. To install the new compresor follow these instructions on the other way
round .
NOTE. Sustitute the dehydrated filter every trime the refrigerator circuit is
open. Not install the new filter unit all the substitution or reparation process
has finished..
NOTE. Purge carefully the cooling circuit to remove the excess of humidity
and the no condensation gas after the sustitution of the condenser..
18
This manual suits for next models
5
Table of contents