manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Jackson
  6. •
  7. Relay
  8. •
  9. Jackson Wireless RELAY WR-400 User manual

Jackson Wireless RELAY WR-400 User manual

WR-400™
4-CHANNEL WIRELESS
RELAY KIT
Installation / Operation
Manual
Wireless
RELAYTM
Introduction:
Installation:
The WR-400™ Wireless Relay kit contains a 4-channel base transceiver and
a 4-channel satellite transceiver. Both transceivers are powered by 24 VAC.
The base module has 3 transmitting channels and 1 receiving channel. The
satellite module has 3 receiving channels and 1 transmitting channel.
Whenever possible, mount the base module and satellite module on a non-
metallic surface close to the equipment. Use a WR-400-E weather proof, plastic
enclosure for outdoor applications.
Before wiring the base and satellite modules to the equipment, conduct the
following communications test:
1. Provide 24 Volts AC to both modules. ( and )
2. Take a jumper wire and land it across terminals
and .
3. Use anAC volt meter and confirm 24 volts across and
at the . If no voltage is present, relocate one
or both modules until communications is established.
DO NOT INSTALL TRANSCEIVERS IN METAL ENCLOSURES.
Testing the communications link:
COM 24V
Base Module 24V
CH 1 SEND
COM CH 1
REC Satellite Module
WR-400-BM Wireless
Transceiver
Base Module
WR-400-SM Wireless
Transceiver
Satellite Module
WR-400-BM
Wireless Transceiver
3 Send - 1 Receive
CH1 SEND
CH2 SEND
CH3 SEND
CH4 REC
WR-400-SM
Wireless Transceiver
1Send-3Receive
CH4 SEND
CH1 REC
CH2 REC
CH3 REC
24 V (COM)
24 V (HOT)
CHANNEL 4 (RECEIVE) 24V Out
CHANNEL 3 (SEND) 24V In
CHANNEL 2 (SEND) 24V In
CHANNEL 1 (SEND) 24V In
24 V (COM)
24 V (HOT)
CHANNEL 3 (RECEIVE) 24V Out
CHANNEL 2 (RECEIVE) 24V Out
CHANNEL 1 (RECEIVE) 24V Out
CHANNEL 4 (SEND) 24V In
2
On power up, LED is solid green and then
blinks every 15 seconds
On power up, LED is solid green and then
blinks every 7 seconds
WR-400-BM
Wireless Transceiver
3 Send - 1 Receive
CH1 SEND
CH2 SEND
CH3 SEND
CH4 REC
Using multiple transceiver kits:
If more than one WR-400™ kit is used in the same building, each additional
WR-400™ kit must be programmed with a different address. All kits come
from the factory programmed as Address 1. There are 5 additional addresses
available for additional kits allowing up to a total of 24 control channels.
Press the program button on the base module (WR-400-BM) and the LED
will blink red 1 time, then 2 times up to 6 times. 1 blink equals Address 1, 2
blinks equal Address 2, etc. For example, if you release the program button
after 2 blinks, the transmitter is programmed as Address 2.
Take the corresponding satellite module (WR-400-SM) and use the same
steps to program it as Address 2.
Sequence of Operation:
WR-400-BM Base Module
WR-400-SM Satellite Module
Failsafe Protection:
When base module channel 1, 2 or 3 receives a 24 volts signal, the satellite
module detects the change and closes its corresponding channel 1, 2 or 3
contact which outputs 24 volts.
When satellite module channel 4 receives a 24 volt signal, the base module
detects the change and closes its channel 4 contact which outputs 24 volts.
Both modules use a redundant transmission protocol. If either module loses
24 volts or does not receive a valid ON or OFF transmission signal within 60
seconds, all outputs will be turned off.
WR-400-SM
Wireless Transceiver
1 Send - 3 Receive
CH1 REC
CH2 REC
CH3 REC
CH4 SEND
E
E
WR-400-BM Base Module WR-400-SM Satellite Module
3
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
06-1061-051911
WR-400-BM Base Module
Power: 24VC, 2.8VA
Channels: 4 (3 Send - 1 Receive)
Contact Rating: 1 Amp per channel
Addresses: Up to 6 kits using
4-channels each can be installed
in the same building
Frequency: 915MHz proprietary protocol
Range: Up to 200 feet from receiver
Dimensions: 2.25” x 2.50” x 1.00” (WxHxD)
WR-400-SM Satellite Module
Power: 24VAC, 2.8VA
Channels: 4 (1 Send - 3 Receive)
Contact Rating: 1 Amp per channel
Frequency: 915MHz proprietary protocol
Range: Up to 200 feet from transmitter
Dimensions: 2.25” x 2.50” x 1.00” (WxHxD)
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference and (2) this device must accept any interference received, including interference that may cause
undesired operation.
Specifications:
Typical Heat Pump Application:
WR-400-BM
Wireless Transceiver
3 Send - 1 Receive
CH1 SEND
CH2 SEND
CH3 SEND
CH4 REC
WR-400-SM
Wireless Transceiver
1 Send - 3 Receive
CH1 REC
CH2 REC
CH3 REC
CH4 SEND
C
R
W2
Y1
Y2
O/B
G
C
R
W2
Y1
Y2
O/B
G
THERMOSTAT
INDOOR UNIT
WIRE TO INDOOR
UNIT TERMINAL
STRIPS
C
R
W2
Y1
Y2
O/B
G
OUTDOOR UNIT
C
R
Y1
Y2
O/B
W2
24V LINE
VOLTAGE
WR-400-SM
SATELLITE
MODULE
WR-400-BM
BASE
MODULE
A separate 24 volt
transformer may be
required if there are no
wires to provide 24 volts
from the indoor unit
USE SEPARATE ISOLATION RELAYS IF LOADS EXCEED 30 VAC, 1 AMP PER CHANNEL
4
When satellite module is used outdoors, a WR-400-E weather
proof, plastic enclosure is recommended. When used with a condensing
unit, mount the enclosure on a non-metallic surface when possible.

Popular Relay manuals by other brands

FMX FSR-TDUV Series quick start guide

FMX

FMX FSR-TDUV Series quick start guide

Dossena DER3B-DUAL Series manual

Dossena

Dossena DER3B-DUAL Series manual

Contrel ELRC-B user manual

Contrel

Contrel ELRC-B user manual

Danfoss Link BR installation guide

Danfoss

Danfoss Link BR installation guide

Alstom MX3IPG2A Technical manual

Alstom

Alstom MX3IPG2A Technical manual

Emirel W 40 quick start guide

Emirel

Emirel W 40 quick start guide

urmet domus 788/54 manual

urmet domus

urmet domus 788/54 manual

teko ASTRA-BRA user guide

teko

teko ASTRA-BRA user guide

ABB SSR42 product manual

ABB

ABB SSR42 product manual

U-Prox Relay DC user manual

U-Prox

U-Prox Relay DC user manual

Reer SR ONE Installation, use and maintenance

Reer

Reer SR ONE Installation, use and maintenance

GMI D5095-105 instruction manual

GMI

GMI D5095-105 instruction manual

ZIGBEE ENVILAR ZG302 manual

ZIGBEE

ZIGBEE ENVILAR ZG302 manual

Pilz PNOZ mmc7p CC operating manual

Pilz

Pilz PNOZ mmc7p CC operating manual

Bpt VLS/101M manual

Bpt

Bpt VLS/101M manual

Sel SEL-300G Quick start installation guide

Sel

Sel SEL-300G Quick start installation guide

LSIS GIPAM 115 FI manual

LSIS

LSIS GIPAM 115 FI manual

GE MFAC 14 user manual

GE

GE MFAC 14 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.