Length 285 mm / 11 7/32”
Depth 144 mm / 5 21/32”
Height 134 mm / 5 9/32”
Weight 1.65 kg
Capacity 1.7 litres
Max. ow (@ 0 m/ft) 300 L/hr
Max. rec. head 5m
Sound level @ 1m 49 dB(A)
Pump Power supply 230 VAC, 0.8 A, 50Hz
Non Continuous 5mins on, 5mins off
Class I Appliance
Max. AC unit output 733kW - 2.5m Btu/h
Max. water temp 40º C / 104º F
Inlets/Outlets Ø21mm to Ø27mm /
6mm (1/4”) & 10mm (3/8”)
IP Protection IP24
Safety switch 3 A Normally closed
Thermal protection ✓
1This pump has been designed for the removal of pH neutral
air conditioner condensate water ONLY.
2 Conrm condensate production of indoor evaporating coil is
within capacity of condensate pump.
3Ensure 1 Amp fuse is installed.
4 Following installation of the pump the tank should be lled
with water until the motor runs. Pipes and connections should
be checked for leaks and discharge of water checked. The
operation of the safety switch should also be checked.
5Do not use these pumps in oily or very dusty environments.
6Install hose and wiring in accordance with manufacturers
instructions. Do not use discharge hose larger than
3/8”/10mm I.D.
7 Inspect pump, clean oats, and tank regularly checking for
correct operation.
8Do not operate this pump when any unapproved cleaning
chemicals are present in the condensate drainage system.
Operating the pump when unapproved or poorly mixed
cleaning chemicals are present will result in permanent damage
to pump and void warranty. Ensure all cleaning chemicals are
thoroughly ushed out of the pump with clean water.
9 After initial installation and/or maintenance, do not leave site
until pump has been tested for correct operation.
10 Check for any construction debris that has entered the
evaporator coil and/or drain pan prior to initial activation of
pump – this will damage the pump permanently.
11 NOISE: All JET tank pumps operate quietly, however under
certain conditions where an extremely low ambient noise level
is present, the sound of their intermittent operation may still
be perceived as noisy. Always conrm acceptable noise level
before installing any condensate pump in a bedroom or other
noise sensitive area.
Correct sequence of operation:
1 AC unit drain pan lls with water which ows into pumps tank.
2 When the water lifts the oat to the correct level the pump
will activate.
Fault Conditions:
In the unlikely event of a pump failure check the following:
1Power supply: Ensure power is supplied to pump.
2Hi level safety switch: Ensure hi level safety switch has not
operated. If it has, check pump performance is suited to
incoming ow rate.
3 Pump is loud: Pump xing may be loose or the connected
cables and hoses may be vibrating against a hard surface.
4 Outlet Pipe: Check pipe, and outlet barb are not blocked with
debris or kinked.
AC max. unit sizing chart
Head / m L / hr kW
0 300 400
1 215 287
2 159 212
3106 141
4 65 87
5 36 48
5.4 0 0
LITRES PER HOUR
METRES HEAD
6
5
4
3
2
1
0100
Max. rec. head 5m
200 300 400 500 600
6mm (¼”)
Information correct at the time of going to press.
PERFORMANCE
IMPORTANT
2
AC Condensate Pump - Installation Guide
285mm / 11 7/32”
134mm / 5 9/32”
SPECIFICATIONS