Parametersettinginstructions
KühlaKühltechnik&LadenbauGmbH
AT1‐5BQ6E‐2KU
Parameterlist
Collectionofallparametersrelatingtothefactorysettings
ParameterSettingrangeDescription SetupKühla
1°C/2°C/°FReadingscale 1°C
‐50.SPH°Minimumsetpoint 1°C
SPL...+120°Limitvalue 15°C
SPL...SPH°Setpoint 7°
REF/HEA(HEA)cooling/heating(HEA) REF
1.10.0°Switchinghysteresis 2K
0.30minCompressorbreak 3min
0.30minActivationtimeRL1faultT1 10min
0.30minStoptimeRL1faultT1 5min
0.30minDelaycompressorstopat
Dooropen/DSonly=YES
‐‐‐
0.24Defrostfrequency/24h3/24h
‐50..+120°Temperaturedefrost ‐‐‐
1.120minMaximumdefrostduration 30min
OFF/ELE/GASDefrosttype OFF
0.60minDisplaywhendefrost 5
NON/ABS/RELAlarmtype REL
‐50..+120°Loweralarmthreshold ‐‐‐
‐50..+120°Upperalarmthreshold ‐‐‐
‐12.0°Loweralarmdifferential ‐4K
0...+12°Upperalarmdifferential +8K
0.120minTemperaturealarmdelay 90min
0.30minDooralarmdelay 0min
0.52WeeksMessagecondensercleaning 26
NO./YESActivatestand‐by YES
NO./YESActivatethedoorswitch NO.
NON/0‐1/DEF
LGT/ALR
ModesofoperationAUXoutput 0‐1
SN4/ST1Sensorselection SN4
‐12,5...+12,5°MeasurementvaluecorrectionT1 0°C.
NO./YESActivationT2 NO.
‐12,5...+12,5°T2measurementvaluecorrection 0°C.
1.30minStorageintervalTLO/TLI 10min
0.100Displayslowdown 0
1.255Busaddress 1