Kemper 686 02 016 User manual

- 1 -
Installation and operating instructions
KEMPER KHS-USB adapter cable (connection,
KHS- Mini System Control -MASTER- with PC)
with configuration and read-out software
Figure 686 02 016
1. Scope of application
The USB adapter cable with configuration and read-out software facilitates connecting and feedforwarding the customer's
PC to the KHS-Mini System Control -MASTER-.
System settings and configuration of the operating modes, time, temperatures and flushing volumes can be made from the
PC and when complete, can be copied to the control.
To document flushing measures, accruing errors and parameter changes, this data can be read-out from the control and
subsequently saved as csv-files.
2. Software installation
PC system requirements:
Windows XP or higher monitor resolution min. 1024 x 600, on free USB connection
1. Insert the CD ROM in the PC CD-ROM drive
2. Start setup.exe
3. Confirm the welcome window with OK
4. Start the installation with the PC button

- 2 -
5. Confirm Programme Group with next
6. Confirm the installation with OK
7. Open software in – Programmes - Kemper – Kemper KHS Mini-System.exe
The shortcut to the desktop is automatic generated, ICON Kemper KHS Mini-System is displayed, then double
click GO.
8. In the status window, the software indicates in red letters that no connection to –MASTER- has been made

- 3 -
3. Connection, KHS- Mini System Control -MASTER- with PC
Note 1: Before operating the software programme, the first installation on the MASTER has to be completed when starting
for the first time (Language, date, time).
Note 2: The field devices valve, sensor must be connected to the MASTER/SLAVE before configuration.
In addition, make sure that voltage has been applied before configuring with the PC software.
After connecting, the status window displays CONNECTED in green lettering
The programme is now ready for operation and can be configured.
Connection to the -MASTER-:
Remove the black screw cap and insert
the cable plug into the jack on the -
MASTER-.
USB ada
p
ter

- 4 -
4. General system settings
You can set the following general system settings in the boxes in the middle
1. Language: Choose the language for the PC software user-interface
2. Time and date: Apply from the PC into the control, automatic summer/winter time switching
activated or deactivated
3. Alarm buzzer: Activated or deactivated in the control
4. Key press acknowledgement: Signal when pressing keys on the control on or off
5. Language in the master display:Choose the language
5. Load/write the system settings in the control or save/load as a file
The following system settings can be made in the right-hand box and under the File menu in the task bar
1. Load from file: Opens a saved PC configuration, i.e., previously saved configuration data can be opened.
2. Save to file: Saves the PC configuration as "Save file as..."
3. Read from control: Reads-out the current control configuration; the one in the master control current / running
parameter settings
4. Write to control: Apply the current PC configuration to the control; transmit the parameter defaults
5. File: Same functions as in item 1 - item 4 / In addition in the pulldown menu, print configuration as PDF / Close
programme
1
2
3
4
5
1
2
3
4
5

- 5 -
6. Help menu
In the pulldown menu:
Install FTDI USB driver: If you experience connection problems, first delete the driver (under
Delete FTDI USB driver) and then reinstall.
Delete FTDI USB driver: If you experience connection problems, first delete and then reinstall
the driver (with install FTDI USB driver).
PC software owner's manual: Instructions in PDF
KEMPER KHS- Mini System Control owner's manual: Instructions in PDF
About: How to contact KEMPER
7. System - Commissioning with the PC software (configuration)
Only if commissioning with configuration has not yet been performed on the KHS-Mini System Control MASTER.
Commissioning and configuration can be performed at will, either via the KHS-Mini System Control MASTER/SLAVE or
directly with the PC software. If configuration data have already been entered into the KHS-Mini System Control, they can
be copied into the PC software as described in Point 5 "Load control".
7.1 Note for fault-free commissioning:
When installing, be sure to fill out the "System Overview" document!
To make system settings fault-free and simple, the document supplied with the KHS-Mini System Control –MASTER and –
SLAVE- installation and operating instructions, the "System Overview" (see photo), needs to be filled out correspondent to
the example during installation.
The data are subsequently transferred during system commissioning either directly on the -MASTER- or using the PC
configuration into the control.
Table 1: Extract from the "System Overview" document

- 6 -
7.2 Device settings and network setup
7.2.1. Hardware setup: Select the tab
7.2.2. Enter the Identification -MASTER- place/room e.g. „House Room 2.03“
7.2.3. Select -MASTER- Flush valve type in the pulldown menu:
e.g. "KHS-spring reset servo drive 230V / Figure 686 05“

- 7 -
7.2.4. Select -MASTER- Flow sensor in the pulldown menu:
e.g. KHS flow sensor DN 20 Figure 638
7.2.5. Select -MASTER- temperature sensor in the pulldown menu:
e.g. KHS flow sensor DN 20 Figure 628/629
7.2.6. -MASTER- optionally set the alarm relay / Display valve switching cycles:
1. Starts with "-" and counts the valve switching cycles during operation
2. "Relay reports own errors only": Only the MASTER errors will be detected and evaluated
3. "Relay reports system wide errors": All errors from the MASTER/SLAVE control will be
reported per relay contact, e.g. to a BMS.
1
3
2

- 8 -
7.2.7. Select -SLAVE- in the pulldown menu: SLAVE 1 - SLAVE 31
7.2.8 Enter identification –SLAVE- Place/Room: e.g., House Room 2.05
7.2.9. Assign -SLAVE- serial number address:
Activate (delete check mark next to deactivated) and enter the serial number, e.g., 1007
(you can read it on the side of the –SLAVE- rating plate), see Table 1, Point 7 here „1007“

- 9 -
7.2.10. Assign device settings for –SLAVE- (as described in –MASTER- Item 3-6)
7.2.11. After completing the network and device settings, write the configuration to the control
At this point, remove all components installed in the KHS Flush System (flush valves, MASTER-SLAVE, sensors). Transfer the
data into the MASTER control only subsequently, as described in 12.
7.2.12. Note: Confirm overwrite control data with OK
7.2.13. Testing the network and device settings/error messages
Antenna symbol and symbols for the set devices appear permanently on the display of the MASTER- control in the overview,
LED’s permanently lit green (everything OK) on all devices.
For error messages, please refer to Troubleshooting table

- 10 -
If not, see table listed below: Error description / Troubleshooting
-MASTER- LED SLAVE- LED
Antenna symbol

- 11 -
Recommendation: Perform an valve function test in manual mode:
To ensure that all flushing valves are working properly, it is recommended to perform the function test in manual mode
described in Point 8.3 in the installation operating instructions, KHS-Mini System Control -MASTER- and -SLAVE-
KHS-Mini System Control .
7.3 Operation modes
7.3.1. Operation modes: Select the tab
7.3.2. –MASTER- Timer 01 and the desired type of control: e.g., timer control
To do that, flag the first or the assignment line

- 12 -
7.3.3. –MASTER- Timer 01 time control: Set the start time, duration and day of the week
Start time refers to the time when flushing should start.
The flushing days Mo - Su (entire week) are set as defaults. If necessary, delete the applicable check marks (e.g., only Mo. –>
leave the check mark on Mo.). After entering e.g. Timer 01 (Line 1), perform the "Apply" step. Only then can the entry
Timer 02 (Line 2 etc.) be made.
7.3.4. –MASTER- Timer 01 time control: Apply the settings
7.3.5. Optional enter –MASTER- Timer 02 - 16: e.g. Timer 02 volume control

- 13 -
7.3.6. Copy/shift operation modes (one or more lines) with right mouse button
7.3.7. Insert operation modes (one or more lines) with right mouse button
7.3.8 Change/apply copied operation modes: e.g. adapt type, start time, duration,
volume, days
By marking the individual lines 01 to 16 in combination with "Selection/Type Free",
the contents of the lines can be deleted after selecting with the "Apply" button.

- 14 -
7.3.9. Select -SLAVE- in the pulldown menu:
SLAVE 1 - SLAVE 31
7.3.10. Assign operation modes for –SLAVE- (as described in –MASTER- Item 2-9):
e.g. temperature flushing

- 15 -
7.3.11. Cycle flushing: If only one temperature control is set for one device, the control automatically sets a changeable time
control (cycle flushing)! This is used for regular flushing, 1 x per week, to prevent stagnation taking place for over a week.
The time of the cycle flushing duration can be set individually (dependent on the water volume in the piping system). Adapt
the flushing time for the routine flushing according to the capacity volume!
At this point, apply the default of the operation modes in "Write configuration to the
control" in the MASTER control.
7.3.12. After entering the operation modes, write the configuration into the control

- 16 -
7.4 Programme switch (chapter only important if you need to stop the flushing process, do maintenance or if there are 2
different flushing programmes)
Switching the programme facilitates entering two different flushing programmes (e.g., school-holidays operation): More
flushings / School-holiday operation: Fewer flushings) and the facility to block the system for maintenance work (all
operation modes are discontinued and locked).
Switching can be done directly on the -MASTER- (submenu switch programme) or through an external 230 V switch input on
the -MASTER- (see installation and operating instructions, KEMPER KHS-Mini System Control, Point 8.6 Switching
programme in the MASTER menu or with an external 230 V switch input on the -MASTER). The configuration can be
performed with the software according to the instructions.
7.4.1. Programme switching:
Select the tab
7.4.2. Programme 2 not active:
It is possible to switch operation modes between "Programme 1" and "System blocked"

- 17 -
7.4.3. Switching programmes with the external 230 V switch input:
It is possible to switch between "Programme 1", "Programme 2" (Programme 2 only if activated)
and "System blocked". To do that, the appropriate programme must be selected in the menu item
"External input". If 230 V are now permanently applied to the input, the programme is controlled as set.
7.4.4. Programme 2 active: It is possible to switch between "Programme 1", "Programme 2" and "System blocked"
7.4.5. Enter identification for Programme 1 and Programme 2: e.g. school and holidays

- 18 -
7.4.6. Set operation modes for Programme 1 and Programme 2:
If Programme 2 is active, in the operation modes there is now a selection box to determine to which programme the
operation mode applies.
7.4.7. After entering the programme switch and the allocated operation modes,
overwrite the entries in the file "Write configuration to control".
8. Printout journal (select steps 1-6)
Display all events and flushing measures.
Read journal and error memory (evaluation)
The journal, as described in Table 2 in the installation and operation instructions, KHS-Mini System Control –MASTER and –
SLAVE-, writes and comprehensibly lists all possibly performed flush operation modes, error messages and configuration
changes. The individual steps are documented with the date, time and description, so they are accordingly comprehensible
(flush journal). In the journal, in a roll-over process the most recent 4000 entries are saved: starting from > 4000 entries, the
first data entries are deleted.
Recommendation: Regularly map the memory to prevent losing data!

- 19 -
8.1 Reading the journal from the control: Select the tab / Click "Read from the master",
optionally set the number of data
8.2. Filter the journal based on events
8.3. Select the event filter: e.g., only flush logs, after selecting change by clicking
the event button filter for a tabular view
If you only want to view certain events, specific events can be selected using the 5 laterally arranged buttons. The check
marks are automatically set for each button. Furthermore, individual, additional event criteria can be manually added or
removed using check marks at any time.

- 20 -
8.4. Activate the event filter:
Selecting this box with a check mark displays solely the selected events.
8.5. Filter the journal based on devices
The data from the flushing log can now be saved in a target directory as a csv file in Excel.
Selecting this box with a check mark displays solely the selected devices.
Table of contents