Kenyon B83211 User manual

2
ImportantSafetyInstructions
Take care when using cleaning agents or detergents.
Select products suitable for use in household cooking area only.
Certainlocalesrequiremake-upaircalculationsfortotalairflow.
ConsultyourlocalcodesandanHVACprofessionalbeforeinstallingorusingthishood.
CAUTION- To reduce risk of fireandtoproperly exhaust air, be sure toductairoutside – Do not vent exhaustairinto
spaces within walls or ceilings or into attics, crawl spaces, or garages.
CAUTION-FORGENERALVENTILATINGUSEONLY.DONOTUSETOEXHAUSTHAZARDOUSOREXPLOSIVE
MATERIALSANDVAPORS.
WARNING– TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a. Usethisunit only in the manner intended by the manufacturer.If you have questions, contact the manufacturer.
b. Beforeservicingorcleaningunit,switchpoweroffatservicepanelandlocktheservicedisconnectingmeanstoprevent
powerfrombeingswitchedonaccidentally.Whentheservicedisconnectingmeanscannotbelocked,securelyfasten
a prominent warning device, such as a tag, to the service panel.
WARNING– TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
a. Neverleavesurfaceunitsunattendedathighsettings.Boiloverscausesmokingandgreasyspilloversthatmayignite.
Heat oils slowly on low or medium settings.
b. Alwaysturn hoodONwhencookingathigh heat or when cooking flaming foods.
c. Cleanventilatingfansfrequently.Grease shouldnot beallowedtoaccumulateonfanorfilter.
d. Useproperpan size. Always use cookware appropriate forthe size of the surface element.
WARNING–TOREDUCETHERISKOFINJURYTOPERSONSINTHEEVENTOFARANGETOPGREASEFIRE,
OBSERVETHEFOLLOWING:
a. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO
PREVENTBURNS. Iftheflames donot gooutimmediately, EVACUATEANDCALL THEFIREDEPARTMENT.
b. NEVER PICK UP A FLAMING PAN – You may be burned.
c. DO NOT USE WATER, including wet dishcloths or towels – a violent steam explosion will result.
d. Usean extinguisher ONLY if:
1. You know you have a Class ABC extinguisher, and you already know how to operate it.
2. The fire is small and contained in the area where it started.
3. Thefiredepartmentisbeingcalled.
4. You can fight the fire with your back to an exit.
WARNING– TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a) Installationworkandelectricalwiringmustbedonebyqualifiedperson(s)inaccordancewithallapplicablecodesand
standards,includingfire-ratedconstruction.
b) Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning
equipmenttopreventbackdrafting.Followtheheatingequipmentmanufacturer’sguidelineandsafetystandardssuch
as those published by the National Fire Protection Association (NFPA), and the American Society for Heating,
RefrigerationandAirConditioningEngineers(ASHRAE),andthelocalcodeauthorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
d) Ducted fans must always be vented to the outdoors.
WARNING -TOREDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
WARNING-ElectricalShockHazard-Canresultinseriousinjuryordeath.Disconnectappliancefromelectricpower
beforeservicing.Ifequipped,thefluorescentlightbulbcontainssmallamountsofmercurywhichmustberecycledordisposed
of according to Local, State, and Federal Codes.

3
Installation
FORRESIDENTIALUSEONLY
NOTTOBEINSTALLEDOVERGAS GRILLS
PLEASEREADENTIREINSTRUCTIONSBEFOREPROCEEDING.
INSTALLATIONMUSTCOMPLYWITHALLLOCALCODES.
IMPORTANT: Save these Instructions for the Local Electrical Inspector’s use.
INSTALLER: Please leave these Instructions with this unit for the owner.
OWNER: Please retain these instructions for future reference.
SAFETYWARNING: Turn offpowercircuit attheservice entranceandlockout
panel,beforewiringthisappliance.
Requirement: 120 V AC, 60 Hz. 15 or 20 A
Weight:31,3 lbs
Diameterof Transition: 6”
Diameterof exhaust Ductrequired: 6”
Dimensions
Considerations before installing Hood
1. For the most efficient air flow exhaust, use a straight run or as few elbows
as possible.
CAUTION: Vent unit to outside of building, only.
2. If allowed in your area, use metallic flex ducting only to connect rigid duct
directly to transitions.
3. COLD WEATHER installations should have an additional backdraft damper
installed to minimize backward cold air flow and a nonmetallic thermal
break to minimize conduction of outside temperatures as part of the
ductwork. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the ducting enters the
heatedportionofthehouse.
4. Hood installation height above cooktop is the users preference. The lower the
hoodabovethecooktop,themoreefficientthecapturingofcookingodors,grease
andsmoke. Werecommendthehoodbeinstalled30-36"abovethecountertop.
Thelowerheightmaybeinconvenientfortallpeopleandlargecookingvessels.
Checkyourceilingheightandthemaximumhoodheightbeforeyouselectyour
hood.
5. The hood can also be used with a filtering function by fitting one part
B80011 Kenyon activated charcoal filter. The air is filtered and recirculated
throughtheuppergridlocatedonbothsidesofthelowersectionofthecover.This
function is the best solution when is not possible to exhaust air to the outside.
AConversionKitmustbeorderedseparatelytoequipthecookerhoodfor
filtering.
This special kit contains a filtering duct (to be mounted in place of the
transition) and a charcoal filter (for filtering cooking odors).
Figure 1*
Note:Alldimensions are shown in
inches.
*Dimensions are givenfrom
base of hood to ceiling, and
includeclearancerequired for
installation.
Dimensions
A(Rangeofadjustableht.)* 35 1/2 - 41 3/4
B (Min.ht. withone cover)* 27 3/4
W (width)x D (depth) 8 3/16 x6 7/8
AA (Cover adjustable ht.) 23 7/16 - 32 15/16
BB (Cover min. height) 16
WD
20
1/4
"
30" - 36
15 3/16"
B
A
AA
BB

4
Installation
Preparation of mounting surface (Drywall)
1. Select a mounting height comfortable for the user and mark on wall
behind cooktop.
2. Mark center line of cooktop and draw vertical line from bottom of hood
to the ceiling.
3. Tape template, matching center-line and hood bottom as shown in
Figure 2.
4. Mark centers of the 6 fastener locations through template on wall then
remove template.
5. Mark wall with horizontal line 1" above highest and 1" below lowest
fastener location.
6. Findstudsbehinddrywallbytappingwallorusingastudfinder.Markthecenter
ofthestudswithaverticallinetotherightandleftofthemarkedfastenerlocation.
Note: 2 x 6's must span at least 2 studs side to side.
7. Cutout drywall along marked lines. Install 2 x 6's between studs firmly
flush with stud front. Make sure all mounting screws will anchor to added
lumber. Replace drywall and refinish.
8. Remark center line and hood bottom on same location as before and tape
template on wall as in step 3 above.
9. Mount2mountinghookswithwoodscrews(suppliedinmountinghardware
kit) on locations marked on template, then remove template.
10. Install duct cover ceiling bracket to wall flush to ceiling with drywall
anchors supplied. Figure 3.
Figure 2
C
L
Figure 3
Tools required for installation
Screw driver
(flathead,philips n°2 and torx 10)
Allen spanner 4mm
Electric drill with twist bit 13/32”

5
Installation
ApplianceInstallation:
11. Install transition on top of hood if removed for shipping. Mark onto exterior of
transition the ‘V’ location of the damper within. Figure 4.
Note: Duct screws can ONLY GO BELOW this line.
For Filtering Function ONLY:
Installfilteringductontopofhoodinsteadoftransition.Filtering ductis
available only by ordering the conversion kit for filtering function.
Kenyon Part # B80011
12. Hang hood on 2 mounting hooks through the rectangular cutouts on back of
hood.Figure5
13. Level the appliance, using a carpenters level across bottom of hood with
leveling screws in mounting hooks or rectangular cutouts.
14. Secure hood with 2 screws on top and 2 screws on bottom. See Figure 5.
15. Connect ducting (Figure 4).
Note: for blower serviceability, leave a gap of 1" minimum between top
of transition and sheet metal duct and cover gap with a starting collar
wrapped around duct and transition. Locate collar screws so they fit into
corner of duct cover. Secure collar to transition and duct with three sheet
metal screws each. Seal with duct tape.
Do not use duct smaller than the transition.
Starting
Collar
1"
Figure 4
Figure 5
Filtering
duct

6
Installation
Wiring to Power Supply
WARNING!
ELECTRICALGROUNDINGINSTRUCTIONS
THISAPPLIANCEISFITTEDWITHANELECTRICALJUNCTIONBOXWITH
3WIRES,ONEOFWHICH(GREEN/YELLOW)SERVESTOGROUNDTHE
APPLIANCE. TOPROTECTYOUAGAINSTELECTRICSHOCK,THEGREEN
ANDYELLOWWIREMUSTBECONNECTEDTOTHEGROUNDINGWIRE
IN YOUR HOME ELECTRICAL SYSTEM, AND IT MUST UNDER NO
CIRCUMSTANCESBECUTORREMOVED.
Warning: Turn off power circuit at the service panel before wiring this unit.
120 VAC, 15 or 20 Amp circuit required.
16. Remove the knockout and install the conduit connector (1/2") in junction
box.
17. Run 3 wires; black, white and green (#16AWG) in 1/2" conduit from
service panel to junction box.
18. Connect black wire from service panel to black or red in junction box,
white to white and green to green-yellow. Figure 6.
19. Close junction box cover. Check all light bulbs to make sure they are
secure in their sockets. Turn power on in service panel. Check lights and
blower operation per Care & Use section of this manual. Install filters.
FinalAssembly
20. InstallductcoverperFigure3
21. Install the two plastic deflectors to cover the big side slots on the lower duct
cover.
22. Makesure to leave this manual forthehomeowner.
Alternate - reduced ceiling height Installation:
The hood may be installed with only the lower part of the duct cover to
reduce the overall height.
For the duct cover to slide down and engage the top of the hood, the ceiling
bracket must be mounted 1/4" below the ceiling.
The resulting space on top of the chimney can be filled with a 1/4” thick piece
of plywood cut to the inside cross section of the chimney cover and finished
to match the ceiling.
Cut the self-adhesive rubber tape supplied with the hood in 4 identical
sections. Attach two pieces of tape to each side of the ceiling bracket. Figure 7.
Snaplowerchimney duct cover into place around ceiling bracket.
Rear discharge:
A 90° elbow may be installed immediately above the hood. For serviceability,
a mounting similar to the straight up discharge shown in Figure 4 should be
used.
Figure 6
Figure 7
kitchen
accessories
::
U N L I M I T E D
rangehoods
com
::
is a division of
.
Kenyon at
This manual suits for next models
5
Table of contents
Other Kenyon Ventilation Hood manuals