When the transmitter is powered up, it initializes and displays the digits and then its configuration including :
,
- 1 - the measuring range - 3 - action of the alarm (rising, falling or regulation action)
- 2 - the status of the alarm - 4 - the set point
- 5 - time-delay (dead band temporisation)
1- The measuring range
The following message is displayed : . This is the low value of the measuring range, and its digit value : ex : .
The following message is displayed : . This is the high value of the measuring range and its digit value : ex : .
The arrow displayed (at the bottom or on the right of the screen) is relative to the unit of measurement : ex : from -500 to 1000 Pa.
2 - The status of the alarm
When the alarm is off, the following message is displayed : .
When the alarm is on, the following message is displayed : .
• When the alarm is off, the transmitter displays which confirms
,
the end of initialization and that you can start the measurements .
• When the alarm is on, the transmitter displays the parameters relative to
the relay (set point, program of the alarm, time-delay).
3 - Action of the alarm (rising or falling action)
.
If the relay is programmed in rising action, the following message is displayed :
If the relay is programmed in falling action, the following message is displayed :
This message is displayed : ex : , which means that the alarm
0.0.0.0.0
L- 5 0 0. .
H.10 0 0. . .
al.o ff. . .
al.o.
2 5 0. .
Ref. FT ang - PST - 10/06 D - We reserve the right to modify the characteristics of our products without notice.
Maintenance
Mounting
A
A
ABS
plate
73 mm
68 mm
Ø 4,5 mm
40 mm
50 mm
Ø 8 mm
7 mm
Configuration via software (with optional
LCC100 software)
• To access the configuration via software, you must first position the DIP switches as per the following picture
(shown beside), and then connect the cable to the transmitter (see connection drawing).
• Please refer to the user manual of the LCC 100 to make the configuration.
1
2
3
41 2 3 4
DIP
switch 2
DIP
switch 1
Inactive
Connection tubes
Connection fittings
Wall through connections
Junctions
Coupling nut
Power supply class 2, input 230 Vac,
output 24 Vac, ref.KIAL-100A
Configuration software LCC 100
with RS 232 connection cable
Optional accessories
Options
!Caution !
Once the transmitter is installed and
energized, please proceed to an autozero to
guarantee the correct working of the
transmitter, whatever the position of the
transmitter is.
An easy and friendly way to configure!
You can configure the measuring units, the set point, the time-delay....
Installation : mount the ABS plate on the wall (this plate is supplied with the
transmitter). Drilling : Ø 6 mm, with the screws and pins supplied with the
transmitter. Insert the transmitter into the plate (see points A of the drawing
beside), by tilting it at 30°. Rotate the housing in clockwise direction until you
hear a “click” which confirms that the transmitter is correctly installed.
Please avoid any aggressive solvent.
Please protect the transmitter and its probes from any cleaning product
containing formol, that may be used for cleaning rooms or ducts.
!Caution !
The configuration can be made either by switch, or by software (you can not combine both solutions)
Initialization of the transmitter
4- The set point (alarm on)
This message is displayed : ex : , which means that the alarm
will be activated as soon as the measurement exceeds this value.
5 - The time-delay (alarm on)
This message is displayed : .
The temporisation is in seconds (from 0 to 60 sec.).
,
After having displayed the configuration, the transmitter displays
which confirms that the nitialization is finished and you can start
the measurements.
250. .
i.s e c. .
If you chose regulation mode , the second set point will appear.
If the relay is programmed in regulation mode, the following message is displayed .