Kimo PST Series Instruction Manual

Features of the transmitter
Manostats (pressure switches)
PST
Pressure
• Measuring ranges from -500 / +1000 Pa to -1000 / + 2000 mbar
• RCR relay output 3A/230 Vac. Power supply 24 Vac/Vdc
• Visual alarm, red LED in front
• ABS IP65 housing, with display
• Quick and easy mounting with the “1/4 turn” system with wall-mount plate
Measuring range............................see “Part number”
Unit of measurement .....................Pa, mmH2O, mbar, inWG, mmHG (PST-1 and PST-2)
mbar, inWG, mmHG, KPa, PSI(PST-3 and PST-4)
Accuracy * ......................................±2% of reading ± 3 Pa(PST-1)
±2% of reading ± 3 mmH O(PST-2)
2
±2% of reading ± 3 mbar(PST-3 and PST-4)
Response time ...............................0,3 s
Resolution .............1 Pa - 0,1 mmH O - 0,01 mbar - 0,01 inWG - 0,01 mmHG (PST-1 and PST-2)
2
1 mbar - 0,1 inWG - 1 mmHG - 0,1 KPa - 0,1 PSI (PST-3 and PST-4)
Autozero.........................................manual with push-button
Type of fluid ....................................air and neutral gases
Overpressure tolerated .................25000 Pa (PST-1), 7000 mmH O (PST-2),
2
1400 mbar (PST-3), 3000 mbar (PST-4).
Working principle : a piezoresistive sensitive element creates a proportional
voltage from the pressure applied on the sensor.
Features of the housing
Housing .........................................ABS
Fire-proof classification ...............HB as per UL94
Dimensions ..................................see drawing
Protection .....................................IP65
Display ...........................................5-digit LCD. Dimensions 50 x 15 mm
Height of the digits .......................10 mm
Connections ..................................barbed fittings Ø 6,2 mm (PST-1 and PST-2)
compression fittings Ø 4 x 6 mm (PST-3 and PST-4)
Cable grip ......................................for cable Ø 7 mm max.
Weight............................................145 g
Technical specifications
Output............................................1 RCR relay 3A/230 Vac
Relay and alarm status..................red LED in front
Set point.........................................1 configurable set point
Power supply.................................24 Vac/Vdc ±10%
Consumption ................................2 VA
Electro-magnetical compatibility ......EN 61326
Electrical connection Screw terminal block for cables Ø1.5 mm² max.
Communication to PC................... Kimo RS 232 cable
Working temperature ...................0 to +50°C
Storage temperature.....................-10 to +70°C
Environment..................................air and neutral gases
...................
Part number
To order, just add the range code to complete the part number :
PST-
1-500 to +1000 Pa
2 -500 to +1000 mmH O
2
3-250 to +500 mbar
4-1000 to +2000 mbar
Measuring range
Example : PST-3 corresponds to a PST manostat with measuring
range from -250 to + 500 mbar.
100 mm
93 mm
42 mm
Dimensions of the housing
(including the wall-mount plate)
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranted for
measurements carried out In the same conditions, or carried out with calibration compensation.
w
e
N
w
e
N
Technical Data Sheet
Pressure • Temperature • Humidity • Air Velocity • Airflow • Sound level
Av. del Libertador 2221 (1636) Olivos - Buenos Aires.
Líneas rotativas: (5411) 5353-0260
E-mail: [email protected]
Home Page: www.airqualitysrl.com.ar

To make an autozero, disconnect the 2 pressure connections and briefly press on the push-button.
The following message will display : A. o
Vdc .........direct voltage
GND .......ground
b
Connection
Electrical connections - as per norm NFC15-100
This connection must be made by a qualified technician. To make the connection, the transmitter must not be energized.
!
c
NC..................Normally closed
COM ..............Common
NO .................Normally open
a
Relay
Power supply
or
Vac .........alternative voltage (phase)
Vac .........alternative voltage (neutral)
b
-
+
+
-
Power
supply
terminal block
Relay
terminal
block
Vdc
GND
Power supply
24 Vdc
or Vac
Vac
Power supply
24 Vac
Class II
~
~~ ~
COM
NO
NC
Cable grip : to insert the cable, it is required to
slightly cut the rubber.
Connection to PC via
LCC 100 software
e
DIP switch
d
Pressure
connection
(barbed fittings shown) Cable grip
c
Power supply
terminal block
b
Relay
terminal block
a
f
Set point setting button
+ autozero
Configuration
To configure the transmitter, please unscrew the 2 screws from the housing,
and then open it.
!Caution !
Please follow carefully the combinations beside with the
DIP switch.
If the combination is wrongly done, the following message will
appear on the display of the transmitter “CONF ERROR”.
In that case, you will have to unplug the transmitter, replace the
DIP switches correctly, and then power the transmitter up.
To configure the transmitter, it must not be
energized. Then, you can make the settings
required, thanks to the DIP switches (as shown
on the drawing beside). When the transmitter is
configured, you can power it up.
Identification of the DIP switches
on the electronic board
1
2
3
4DIP
switch 2
}
1 2 3 4
DIP
switch 1 Setting of units
DIP switch
Electronic
board
d
On-off switch
Inactive
Configuration of measuring units by DIP switch
Autozero push button
Configuration of measuring units, set points, can be carried out different ways : DIP switch, push-button and/or software
(connections , and on drawing “connection”).
efd
Power supply
24 Vac
PhaseNeutral
or Vac
Vac
2

Power the transmitter up : it will then display its current configuration.
To modify the configuration, please proceed as follows :
Remove the 2 screws from the housing and open it.
The settings are done with the button located on the electronic board
(see photo beside).
Principle :
- By pressing on this button for more than 3 seconds, you can validate the setting and go to the next setting.
- By pressing quickly on this button, you can increment a value and scroll down the different options or values.
This button enables :
1- to activate/deactivate an alarm (set point)
2- to program the action of the alarm (rising/falling/regulation action)
3- to set the set point value
4- to set the time-delay (temporisation)
• Setting of units
To set the measuring unit, please set the on-off
switches 2, 3 and 4 of the units, as shown beside.
mmH2O inWG mmHG PSI
Configurations Pa mbar KPa
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Combinations
PST-1 and PST-2 X X X X X
PST-3 and PST-4 X X X X X
To set the different options :
1- Activating/deactivating the alarm :
After pressing the set point configuration button for more than 3 seconds, will be displayed, then or
(depending on the last configuration of the transmitter).
Afterwards, by briefly pressing on this button, you can switch between (alarm on) and (alarm off).
To validate your choice, press again for 3 seconds. If you chose , then you will exit the configuration mode and
switch back to the measurement mode. If you chose , you will move to the next parameter.
2- Programming the action of the alarm (rising/falling/regulation action) :
Rising action (1 set point) : the alarm will activate when the measure exceeds the set point and will stop when the
measure goes below the set point.
Falling action (1 set point) : the alarm will activate when the measure goes below the set point and will stop when the
measure goes above the set point.
Regulation mode (2 set points) : the set point values will determine the action type. Two possibilities are available:
Press the button for 3 seconds to confirm your choice. You will then move on to the last parameter.
3- Programming the set point value :
The set point is a limit which, when being reached and/or exceeded, activates the relay and the visual red LED alarm.
The first digit will start to blink, by briefly pressing on the button, you can choose if the set point will be either positive (0) or
negative (-). Then press the button during 3 seconds to confirm your choice. The second digit will start to blink. Press the
button briefly to change the value. Then press the button during 3 seconds to confirm your choice. Repeat this sequence until
you have reached the last digit and then confirm the set point. If you selected regulation mode , you will program the
second set point.
4- Setting of the time-delay (dead band temporisation 60 sec max) :
When the set point is reached and/or exceeded, the time-delay will wait the specified time before energizing the relay, if the
set point is still reached and/or exceeded.
When the first digit starts blinking, press briefly on the button to change the value. Then press the button during 3 seconds to
confirm your choice. Repeat the process until all digits have the desired value and press the button for 3 seconds to confirm
your choice.
The programming is now done and the display switches back to the measurement mode.
CONF AL.ON
AL.OFF
AL.ON AL.OFF
AL.OFF
AL.OFF
Set points configuration with the push-button Set point
configuration
button
Electronic
board
3
Co F. AL.OFF
AL.O
AL.O AL.OFF
AL.OFF
AL.O
AL.OFF
0000.0
00.SEC
AL.O
set point 1 > set point 2 set point 2 > set point 1
set point 1
set point 2
Time
Measurement
<T> <T> <T>
set point 2
set point 1
Time
Measurement
<T> <T> <T>
<T>
Alarme set
Time-delay
Measure > set point 1 ®Alarm activation
Measure < set point 2 ®Alarm stop
set point 2 £Measure £set point 1 ®No change
Measure < set point 1 ®Alarm activation
Measure > set point 2 ®Alarm stop
set point 1 £Measure £set point 2 ®No change

When the transmitter is powered up, it initializes and displays the digits and then its configuration including :
,
- 1 - the measuring range - 3 - action of the alarm (rising, falling or regulation action)
- 2 - the status of the alarm - 4 - the set point
- 5 - time-delay (dead band temporisation)
1- The measuring range
The following message is displayed : . This is the low value of the measuring range, and its digit value : ex : .
The following message is displayed : . This is the high value of the measuring range and its digit value : ex : .
The arrow displayed (at the bottom or on the right of the screen) is relative to the unit of measurement : ex : from -500 to 1000 Pa.
2 - The status of the alarm
When the alarm is off, the following message is displayed : .
When the alarm is on, the following message is displayed : .
• When the alarm is off, the transmitter displays which confirms
,
the end of initialization and that you can start the measurements .
• When the alarm is on, the transmitter displays the parameters relative to
the relay (set point, program of the alarm, time-delay).
3 - Action of the alarm (rising or falling action)
.
If the relay is programmed in rising action, the following message is displayed :
If the relay is programmed in falling action, the following message is displayed :
This message is displayed : ex : , which means that the alarm
0.0.0.0.0
L- 5 0 0. .
H.10 0 0. . .
al.o ff. . .
al.o.
2 5 0. .
Ref. FT ang - PST - 10/06 D - We reserve the right to modify the characteristics of our products without notice.
Maintenance
Mounting
A
A
ABS
plate
73 mm
68 mm
Ø 4,5 mm
40 mm
50 mm
Ø 8 mm
7 mm
Configuration via software (with optional
LCC100 software)
• To access the configuration via software, you must first position the DIP switches as per the following picture
(shown beside), and then connect the cable to the transmitter (see connection drawing).
• Please refer to the user manual of the LCC 100 to make the configuration.
1
2
3
41 2 3 4
DIP
switch 2
DIP
switch 1
Inactive
Connection tubes
Connection fittings
Wall through connections
Junctions
Coupling nut
Power supply class 2, input 230 Vac,
output 24 Vac, ref.KIAL-100A
Configuration software LCC 100
with RS 232 connection cable
Optional accessories
Options
!Caution !
Once the transmitter is installed and
energized, please proceed to an autozero to
guarantee the correct working of the
transmitter, whatever the position of the
transmitter is.
An easy and friendly way to configure!
You can configure the measuring units, the set point, the time-delay....
Installation : mount the ABS plate on the wall (this plate is supplied with the
transmitter). Drilling : Ø 6 mm, with the screws and pins supplied with the
transmitter. Insert the transmitter into the plate (see points A of the drawing
beside), by tilting it at 30°. Rotate the housing in clockwise direction until you
hear a “click” which confirms that the transmitter is correctly installed.
Please avoid any aggressive solvent.
Please protect the transmitter and its probes from any cleaning product
containing formol, that may be used for cleaning rooms or ducts.
!Caution !
The configuration can be made either by switch, or by software (you can not combine both solutions)
Initialization of the transmitter
4- The set point (alarm on)
This message is displayed : ex : , which means that the alarm
will be activated as soon as the measurement exceeds this value.
5 - The time-delay (alarm on)
This message is displayed : .
The temporisation is in seconds (from 0 to 60 sec.).
,
After having displayed the configuration, the transmitter displays
which confirms that the nitialization is finished and you can start
the measurements.
250. .
i.s e c. .
If you chose regulation mode , the second set point will appear.
If the relay is programmed in regulation mode, the following message is displayed .
Av. del Libertador 2221 (1636) Olivos - Buenos Aires.
Líneas rotativas: (5411) 5353-0260
E-mail: [email protected]
Home Page: www.airqualitysrl.com.ar
This manual suits for next models
4
Table of contents
Popular Switch manuals by other brands

Extron electronics
Extron electronics USB HUB4 AAP user guide

Cisco
Cisco Catalyst 3560-24PS Technical specifications

Shinybow USA
Shinybow USA SB-5612 instruction manual

ATEN
ATEN Master View ACS-1712 user manual

Emos
Emos P5710TG manual

Mellanox Technologies
Mellanox Technologies SB7700 Quick installation guide