KMC Controls HPO-9005 User manual

HPO-9005 Room Sensor Adapter
Installation Guide
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 /877.444.5622 /Fax: 574.831.5252 /www.kmccontrols.com
The sensor must be a Type II or III, 10K ohm
thermistor. The setpoint adjustment must be a
0–10K ohm potentiometer. The sensor or pot
may have wire leads or (with user supplied wiring)
screw terminals.
NOTE: Conquest controllers automatically
congure Type II thermistors
connected to the Room Sensor
port. Type III thermistors require a
quick conguration change using
KMC Connect, KMC Converge, or
TotalControl. See Conguration on
page 2.
MOUNTING
The adapter’s dimensions are 1-5/16 x 11/16 x
5/8 inches (33 x 17 x 16 mm), and its weight is 1/3
ounce (9 grams).
If using the center hole 2in the circuit board for
surface mounting with a (#8) screw:
Tighten the screw loosely (to avoid cracking
the board or any of its connections).
Fasten to a metal surface only after insulating
the board appropriately.
2
CONTENTS
Introduction .............................................. 1
Mounting.................................................. 1
Connections.............................................. 1
Sample Wiring ........................................... 2
STE-6011 or STE-1430 (Thermistor Only) 2
STE-6019 (Thermistor and Potentiometer)2
Conguration ............................................ 2
Temperature (Device Type II or III) .......... 2
Setpoint Offset (Range and Multiplier)..... 3
Maintenance ............................................. 4
Important Notices ...................................... 4
INTRODUCTION
1
The Room Sensor port 1in KMC Conquest
controllers is designed to automatically connect
and congure a digital STE-9000 Series
NetSensor or an STE-6010, STE-6014, or STE-
6017 analog (thermistor) sensor using a standard
Ethernet patch cable.
The HPO-9005 room sensor adapter allows
the use of other sensors and optional setpoint
potentiometers to be used instead. This provides
the means of reusing an existing suitable sensor
and wiring in a retrot or using a different kind of
sensor (e.g., a flat plate sensor such as a STE-
1430) for new installations.

HPO-9005 Room Sensor Adapter Installation Guide 2902-019-20A
CONNECTIONS
NOTE: The terminals are marked T
(Temperature), GND (Ground/
Common), and SP (Setpoint) 3under
the terminal block on the bottom of the
circuit board.
3
1. Connect wires from the thermistor to the
Temperature 4and Ground/Common 5
terminals on the adapter. (See Sample Wiring
on page 2.)
Temperature
Ground/Common
Setpoint
6
5
4
2. Connect an optional 10K ohm setpoint
potentiometer between the Ground/Common
5and Setpoint 6terminals.
3. Plug an Ethernet patch cable 7into the RJ-
45 jack on the adapter.
7
4. Plug the other end of the Ethernet cable into
the ROOM SENSOR port 1of the controller.
(See Introduction on page 1.)
NOTE: The total length of wiring between
the sensor and the Room Sensor port
should be a maximum of 150 feet (45
meters).
SAMPLE WIRING
STE-6011 or STE-1430 (Thermistor Only)
Common (“Ground”)
Temperature
T
S
GND
Setpoint
Thermistor
(10K Ohms)
(Wires are interchangeable)
STE-6019 (Thermistor and Potentiometer)
Common Common (“Ground”)
Thermistor Temperature
T
S
GND
Pot. (0–10K) Setpoint
A
B
C
D
Up (Toward Ceiling
at Installation)
CONFIGURATION
Temperature (Device Type II or III)
KMC Conquest controllers automatically
congure the Room Sensor port’s AI1 (Space
Sensor) 8for Type II, 10K ohm thermistors 9.
If a Type II thermistor is used, no conguration by
the user is needed.
NOTE: For thermistors (in default Conquest
applications), AI1 is mapped to AV1
(Space Temperature), and AV1 is
used as the temperature reference for
controlling the outputs.
9
8
To select a Type III thermistor device type:
1. Start KMC Connect, KMC Converge, or
TotalControl. (KMC Connect screens are
shown here.)

HPO-9005 Room Sensor Adapter Installation Guide 3902-019-20A
10
11
12
13
15
14
2. Click the +10 in front of the controller.
3. Click the +11 in front of Input Objects to
expand the folder.
4. Double-click AI1 12 to open it.
5. Click the drop-down box 13 under Device
Type.
6. Select KMC Type III Deg F (or C) 14 .
7. Click Save Changes 15 .
8. Click the Xin the tab to close the tab.
NOTE: See the software help system for any
additional information.
Setpoint Offset (Range and Multiplier)
For a setpoint adjustment with a 0–10K ohm
potentiometer, AI2 provides an offset range of
approximately plus or minus 1° (F or C, according
to the application) 16 . The present value is
dependent on the position of the dial.
16
In default Conquest applications, AI2 is mapped
to AV2 (with a multiplier AV12) for the setpoint
offset 17 , and AV2 is the value used in room
temperature control programming (not AI2
directly). AV2 = AI2 x AV12.
17
The factory default for the multiplier (AV12) is
3 for °F applications (or 1.5 for °C applications),
which gives a user a setpoint adjustment range of
approximately plus or minus 3° F.
NOTE: In the example shown, AI = 0.5 at that
dial position (about halfway between
the center position and the extreme
CW position), which is multiplied by
(the default) AV12 value of 3 to give the
offset of 1.5 °F above (warmer than)
the scheduled active setpoint.
To adjust the setpoint range by editing the
present value of AV12:
1. Start KMC Connect, KMC Converge, or
TotalControl. (KMC Connect screens are
shown here.)
18
19
20
2. Click the +18 in front of the controller.
3. Click the +19 in front of Analog Value Objects
to expand the folder.

HPO-9005 Room Sensor Adapter Installation Guide 4902-019-20A
© 2018 KMC Controls, Inc. Specifications and design subject to change without notice 902-019-20A
IMPORTANT NOTICES
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no
event shall KMC Controls, Inc. be liable for any
damages, direct, or incidental, arising out of or
related to the use of this document.
The KMC logo is a registered trademark of KMC
Controls, Inc. All rights reserved.
TEL: 574.831.5250
FAX: 574.831.5252
EMAIL: [email protected]
4. Double-click AV12 20 to open it.
21
22
5. Edit the Relinquish Default value 21 to be the
desired multiplier.
NOTE: If AV12 = 1, then AV2 = AI1.
6. Click Save Changes 22 .
7. Click the Xin the tab to close the tab.
NOTE: See the software help system for any
additional information.
MAINTENANCE
No routine maintenance is required. Each
component is designed for dependable, long-term
reliability and performance. Careful installation will
help ensure long-term reliability and performance.