Kozi BayWin User manual

Page 1
BayWin®Pellet Burner
* INSTALLATION * OPERATION * SERVICE * PARTS *
CAUTION:
Read all instructions carefully before starting the
installation or operating the heater. Failure to
follow these instructions could result in property
damage, bodily injury or even death. Contact local
building or fire officials about restrictions and
installation inspection requirements in your area.
Save this manual for future reference.
OWNER’S MANUAL
Manufactured By:
APR Industries Ltd.
1354 Waverley Street
Winnipeg, Manitoba, R3T 0P5
Canada
Lithoid in Canada
Rev July 2004
WWW.KOZISTOVES.COM

Page 2
CAUTION: Stove has moving parts. Disconnect power
before servicing.

Page 3
Table Of Contents
I. Installation and Operation Manual ................................................... 4
1. Preamble: Instructions for Safe Installation and Operation ................................................... 4
2. Clearance to Combustible Walls ................................................................................................ 5
2.1 Non-Combustible Floor Protector .................................................................................... 5
2.2 Free Standing Stove .......................................................................................................... 6
2.3 Free Standing Installed in an Alcove ................................................................................ 6
2.4 Insert Installed in an Alcove ............................................................................................. 6
2.5. Insert Installed in a Masonry/Factory Built Fireplace ..................................................... 6
2.6 Other Clearances and Recommendations ......................................................................... 6
3. Electrical Requirements ............................................................................................................. 7
4. Fuel Requirements ...................................................................................................................... 8
5. Venting System ............................................................................................................................ 8
5.1 Exhaust Vent Pipe Requirements ..................................................................................... 8
5.2 Exhaust Vent Termination Requirements ......................................................................... 9
5.3 Combustion Air Intake Requirements ............................................................................ 10
6. Location of the Heater .............................................................................................................. 11
7. Typical Installation Configurations .........................................................................................11
8. KOZIKOZI
KOZIKOZI
KOZI BayWin ® Pellet Insert Additional Considerations .................................................. 13
8.1 KOZI BayWin® Pellet Insert Additional Requirements .............................................. 13
8.2 Surround Assembly ........................................................................................................ 14
8.3 KOZI BayWin® Pellet Insert Installation .................................................................... 14
8.4 KOZI BayWin® Pellet Insert Removal ....................................................................... 15
8.5 Operation and Maintenance ............................................................................................ 15
9. Mobile Home Additional Installation Requirements ............................................................. 15
9.1 Combustion Air Intake Requirements ............................................................................ 15
9.2 Exhaust Vent Requirements ........................................................................................... 16
9.3 Other Installation Requirements ..................................................................................... 16
9.4 Typical Mobile Home Installation Configuration ........................................................... 16
9.5 Recommendations for Mobile Home Installation ........................................................... 17
II. Understanding Your Pellet Burning Heater ................................. 18
1. Component Description ............................................................................................................ 18
1.1 General Overview ...........................................................................................................18
1.2 Exhaust Fan .................................................................................................................... 18
1.3 Burn Pot .......................................................................................................................... 18
1.4 Circulation Fan ............................................................................................................... 18
1.5 Trouble Shooting Module Status Lights ......................................................................... 19
1.6 Auger Cycle Timer ......................................................................................................... 19
1.7 High Temperature Manual Reset Thermal Disk ............................................................. 19
1.8 Pressure Switch ............................................................................................................... 19
2. Heater Operation ...................................................................................................................... 19
2.1 Circulation Fan Speed Control ....................................................................................... 20
2.2 Start Button ..................................................................................................................... 20
2.3 Feed Control ................................................................................................................... 20
2.4 Damper Control .............................................................................................................. 20
2.5 Starting (lighting) your Heater for the First Time ........................................................... 20
2.6 Starting (lighting) your Heater ........................................................................................ 21
2.7 Stopping your Heater ...................................................................................................... 22
2.8 Adjusting your Heater ..................................................................................................... 22
III. Maintenance ................................................................................... 22
IV. Trouble Shooting Guide ................................................................ 25
V. Diagrams and Parts List ................................................................. 27
1. KOZIKOZI
KOZIKOZI
KOZI BayWin® Circuit Diagram ......................................................................................... 27
2. Stove Cross Section ................................................................................................................... 28
3. Equipment Compartment ......................................................................................................... 29
4. Parts List .................................................................................................................................... 30
5. Accessories List ......................................................................................................................... 31
VI. Warranty ......................................................................................... 31

Page 4
I. Installation and Operation Manual
This heater is suitable for both mobile home and conventional home installation. Read all
instructions carefully before starting installation. Save this manual for future reference.
1. Preamble: Instructions for Safe Installation and Operation
1. Read these instructions carefully. Failure to follow them could cause a
malfunction of the heater resulting in damage to the heater, property,
bodily injury and even death.
2. Familiarize yourself with the heater operation. (Refer to the “Under-
standing you Pellet Burning Heater” section) If you are unsure, ask
your dealer to explain how to operate the heater properly.
3. The burn pot of this heater is designed for premium grade wood pellets.
Pellets with too much fines and saw dust must be screened before use.
DO NOT use wet pellets. Refer to the “Fuel Requirements” section for
more information.
4. Oil the circulation fan motor bearings every 6 months. See the “Mainte-
nance” section for more details.
5. Check with the local code authority regarding restrictions or installation
requirements.
6. This heater requires a floor protector beneath the heater and extending a
minimum of 6 inches (150mm) in front of the heater. This is to catch
any spillage, which may occur during opening and closing of the
doors.
7. Use only UL/ULC listed Type Pl or Type L venting for the exhaust
system. This heater is designed to use 3-inch (76 mm) vent pipe. Avoid
long runs and too many bends. It may be necessary to increase the size
of the vent pipe to 4 inches (102 mm) if long runs and too many bends
in the venting system are unavoidable. For details see the “Venting
System” section.
8. Combustion of wood pellet fuel deposits ash in the heater and venting
system. These ashes must be removed from the heater regularly
(approximately once a week, more frequently for high ash content
fuels). Refer to the “Maintenance” section for more information.
9. The heater must be turned OFF and allowed to cool completely before
cleaning. Make sure there are no hot ashes or embers present. Use a
brush and scoop to remove all of the ashes and place them in a metal
container.

Page 5
10. This heater is POWER VENTED. The vent pipes have positive
pressure during operation. It is IMPERATIVE that all joints in the
venting system be sealed to prevent any leakage of exhaust gases
inside the house. All joints must be sealed using high temperature
silicone sealer (RTV). Aluminum tape is not an adequate sealant.
11. Store all pellet fuel at a safe distance (at least 36 inches / 1 meter) away
from the heater and in a sealed metal container.
12. Use of outside combustion air is highly recommended and is manda-
tory in mobile home installations. Connect the air intake of the heater
to the exterior of the building with a non-combustible metal pipe with a
minimum diameter of 2 inches (50 mm) (Use APR Part No AK100).
Use of plastic pipes is not permitted. Where outside air cannot be used
in conventional homes, APR Part No CV100 (Check Valve) must be
used.
13. This appliance is wired and grounded according to the CSA C22.1
code for Canada and the NFPA 70 code for the USA. Also, this heater
meets the fuel burning appliance installation codes NFPA 211 in the
USA and CSA B365 in Canada.
14. Do NOT operate the heater with the door open. Make sure the door is
closed tightly during operation. Inspect the gaskets of the door
periodically to make sure they are in good condition.
15. Replace broken or defective components only with parts provided by
the manufacturer. See WWW.KOZISTOVES.COM or contact your
local dealer to find out how to purchase replacement parts.
16. Follow this manual carefully for proper installation. If you are
uncertain, call your dealer. Most dealers have qualified and trained
installers. We highly recommend the use of their services.
2. Clearance to Combustible Walls
Figure 1. KOZI pellet stove with a non-
combustible floor protector.
The following is a list of all minimum clearances to
combustibles for both the free standing stove as well as the
insert version.
2.1 Non-Combustible Floor Protector
A. Depth of Floor Protector 32 inches (815 mm)
B. Width of Floor Protector 27 inches (680 mm)
C. Floor Protector to Front of Unit 6 inches (150 mm)
D. Width of Unit 25 inches (635 mm)
E. Depth of Unit 25 inches (635 mm)

Page 6
2.2 Free Standing Stove
Minimum clearance must be:
A. Side Wall to Unit 12 inches (300 mm)
B. Back Wall to Unit 1 inch (25 mm)
C. Corner to Unit 1 inch (25 mm)
2.3 Free Standing Installed in an Alcove
Alcove dimensions must be:
Minimum width 48 inches (1220 mm)
Minimum height 48 inches (1220 mm)
Maximum depth 30 inches (760 mm)
2.4 Insert Installed in an Alcove
Alcove dimensions must be:
Minimum width 48 inches (1220 mm)
Minimum height 38 inches (965 mm)
Maximum depth 30 inches (760 mm)
2.5. Insert Installed in a Masonry/Factory Built Fireplace
Minimum clearance must be:
D. Floor protector 6 inches (150 mm)
E. Combustible side wall to unit 12 inches (300 mm)
F. Mantle to unit 13 inches (330 mm)
G. Top facing to unit 13 inches (330 mm)
H. Side facing to unit 12 inches (300 mm)
Please refer to the “Typical Installation Configurations” section and Figure 2 for more
information. Please note the certification label supersedes any information contained in
this manual.
2.6 Other Clearances and Recommendations
1. This heater must be mounted on a non-combustible material, placed
underneath the heater and extending a minimum of 6 inches (150 mm)
in front of the heater.
2. A safety certification label has been attached to either the back of the
heater or inside the hopper lid. A diagram of a sample label is
provided to aid in the identification of the aforementioned clearances.
3. Clearances can ONLY be reduced by means approved by local building
or fire officials in your area.

Page 7
Figure 2 Certification Label
INSTALLATION COMMENT: We recommend sufficient space be
provided (minimum 20 inches/500 mm) on each side of the heater to
service the equipment area. If this is not possible, a provision must be
made to pull the heater out for service.
3. Electrical Requirements
1. This heater is an electrical appliance. The North American versions of this
appliance require 120 Volts, 60 cycle and 3 Amps of electrical power. The
European versions of this appliance require 230 Volts, 50 cycles and 2 Amps
of electrical power. All heaters with an electric igniter require an additional
300 watts of electrical power during the start up sequence.

Page 8
3. When installed in mobile home, the heater must be grounded to the
steel chassis of the home (unless this is not required by local code).
4. Fuel Requirements
This heater is designed for premium grade, 1/4 inch (6.35 mm) wood pellets. Pellets with
too much fines and saw dust must be screened before use. DO NOT use wet pellets. It is
very difficult to maintain a clean and efficient burn when using high moisture and/or
high ash content fuels. These “poor” fuels cause the burn pot to clog much more
frequently and do not provide the proper air flow for a clean, effective burn. “Poor”
fuels require more frequent cleaning; the ashtray must be emptied and the burn pot must
be cleaned on a weekly possibly daily basis. Please refer to the “Maintenance” section
for further instructions on cleaning your heater.
All pellet fuel should be stored in a clean dry place and at a safe distance (at least 36
inches / 1 meter) away from the heater. DO NOT place the fuel within the installation
clearances of the heater or within the space needed for ash removal and starting of the
heater.
5. Venting System
Before proceeding with the installation, the following sections should be reviewed:
Section 5: Venting System
Section 6: Location of the Heater
Section 7: Typical Installation Configurations
5.1 Exhaust Vent Pipe Requirements
KOZI pellet heaters have a negative pressure combustion chamber. A high pressure,
radial blade, fan pulls the air out of the burn chamber creating negative pressure
(vacuum) inside the burn chamber. Air from outside the heater then rushes through the
intake air tube, burn pot stand and burn pot to fill this vacuum. As this air passes through
the burn pot it is used to burn the pellets. A proper size ULC/UL listed type PL or L
venting should be used to provide the least resistance for movement of the combustion
air.
This KOZI pellet burner is certified for 3 and 4 inch exhaust venting. 3 inch venting is
sufficient for most direct vent installations. However, installations with several elbows,
long horizontal and/or vertical runs may add excessive resistance against the flow of air
which reduces the volume of air movement and creates burn problems. The use of 4 inch
venting will reduce this resistance. A simple technique called ‘EQUIVALENT VENT
LENGTH (EVL)’ can be used to determine whether 3 or 4 inch vent pipe should be used.
2. The heater comes with a 5 ft (1.5 M) long, grounded, electrical cord suitable
to plug into any standard residential electrical outlet. The electrical outlet
must be grounded.

Page 9
The exhaust vent pipes are located on the exhaust side of the exhaust fan and are under
positive pressure. At least 3 screws are needed for securing all joints for connector pipes.
Care must be taken to ensure that all the joints are completely sealed to prevent any
leakage of exhaust fumes into the house. If you smell smoke, the venting has not been
properly sealed. Use only high temperature RTV silicone for sealing. Aluminum tape is
not considered an adequate sealant.
The venting of this heater is not allowed to pass through any closets, concealed spaces,
through a floor, ceiling or attic space. If the venting is to go through a wall or combus-
tible partition, the installation must conform to the Installation Code for Solid Fuel
Burning Appliance and Equipment CAN / CSA -B365. For more detailed venting
information, please refer to your venting manufacturer’s instructions.
5.2 Exhaust Vent Termination Requirements
1. The exhaust vent must terminate into an open space. Under no
circumstances is the vent allowed to terminate into closed or semi-
closed spaces. Venting into a garage, under a sun deck, porch or any
other space where the concentration of fumes may occur is prohibited.
To calculate EVL use the following formula:
for each 90° Elbow or T fitting = add 5 EVL
for each 45° Elbow = add 3 EVL
for each Horizontal run of vent = add 1 EVL per foot of horizontal venting
for each Vertical run of vent = add 1/2 EVL per foot of vertical venting
DO NOT USE MAKESHIFT MATERIALS OR MAKE COMPROMISES IN
THE INSTALLATION. IT IS A FIRE HAZARD.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS HEATER
DO NOT CONNECT THIS HEATER TO A CHIMNEY
FLUE SERVING ANOTHER APPLIANCE
YOU MUST USE APPROPRIATE 4” VENTING IF:
The EVL is 7 or more AND you are at or above an altitude of 3000 ft
OR
The EVL is 15 or more
OR
Your heater is an Insert
CAUTION: EVL CANNOT EXCEED 25ft (7.6 meters). Installations
using an EVL exceeding 25ft (7.6 meters) are not permitted.

Page 10
2. The exhaust vent must be at least:
* 4 feet (1.2 m) below
* 4 feet (1.2 m) horizontally from
* 1 foot (0.3m) above
any opening in the building such as doors, windows, ventilation air
intakes, etc.
3. The exhaust vent opening must be a minimum of:
* 12 inches (0.3m) from the ground
* 24 inches (0.61m) from any combustible surface i.e. fence, plant, etc.
* 7 feet (2.1 m) from any public walkway
4. The exhaust air is EXTREMELY HOT. Caution must be taken to avoid
contact with children, people, plants, animals, or any other object that
may be affected by heat. It is recommended to use a vertical pipe to
discharge the hot air at a safe elevation.
5. The vent terminal must have an end cap to protect against down-draft
and back-draft created by severe wind conditions.
5.3 Combustion Air Intake Requirements
There are 2 methods of supplying the heater with combustion air. They are as follows:
1. Room Air: Conventional homes may use room air for combustion
provided APR Part No: CV100 (Check Valve) is installed. For
installations where the exhaust pipe incorporates a minimum 3’ vertical
section immediately adjoining the heater, APR Part No: CV100 (Check
Valve) is optional. In this venting configuration it is highly recom-
mended that the total exhaust vertical rise be longer than the total
horizontal run.
2. Outside Air: All installations can be connected to the exterior of the
building using a non-combustible metal pipe, with a minimum 2 inch
(50mm) internal diameter or by using APR Part No: AK100 (Air
Intake Kit). A larger diameter air intake pipe may be required if the
length of intake exceeds 3’ (1 meter) or has several bends. Use of
plastic pipes are not permitted.
In some installations, outdoor combustion air may be needed to ensure proper perfor-
mance. If your heater burns poorly, experiences roll-out or back-drafts, outside combus-
tion air may be required.
The following restrictions apply to any and all installations:
1. Use of plastic pipes is not permitted under any circumstance.
INSTALL ALL VENTING AT CLEARANCES
SPECIFIED BY THE VENT MANUFACTURER

Page 11
7. Typical Installation Configurations
The following figures describe some typical installations. Variations of these are
possible. Common sense, safety and compliance with local codes must be respected in
any variation.
2. The combustion air intake must terminate into a vented space, i.e.
outside, vented attic, vented crawl space. This heater cannot draw air
from a closed space such as a closed garage, airtight crawl space or any
other sealed room.
3. The elevation of the combustion air intake must be below the exhaust
vent. An elbow may be used to lower the air intake point below that of
the exhaust vent.
4. Excessive lengths and elbows on the air intake pipe will cause airflow
restrictions. A minimum of 2 inch (50 mm) or larger venting should be
used for lengths exceeding 3’ (1 meter). Increase the venting size as
needed.
6. Location of the Heater
A. This heater is NOT approved for bedroom installations.
B. If installed in a mobile home, the heater must be anchored to the floor.
C. When installed in a conventional or mobile home, check for:
a. Clearance to combustibles. d. Power within 5 feet (1.5 m).
b. Sufficient room to service the unit. e. Access for exhaust venting.
c. Access for outside combustion air. f. EVL not exceeding 25 ft (7.6 m).
See Exhaust Venting Requirements.
Figure 3. Typical floor plan - corner installation

Page 12
Figure 5. Free standing through the roof
installation
Figure 7. Free standing basement
installation
Figure 8. Free standing through a
masonry chimney installation
Figure 6. Free standing through the
wall and the roof installation
Figure 4. Free standing through the wall installation

Page 13
Figure 9A. Factory built zero clearance or
masonry fireplace insert installation
8. KOZIKOZI
KOZIKOZI
KOZI BayWin ® Pellet Insert Additional Considerations
The KOZI BayWin®Pellet Insert can be installed in a masonry or listed factory built
fireplace. The insert’s overall dimensions are 25” (635 mm) in width, 25” (635 mm) in
depth and 23” (585 mm) in height. The minimum opening of a fireplace that is suitable
for a KOZI pellet insert is 22” (560 mm) wide, 19.5” (500 mm) high and 16” (410 mm)
deep. The minimum clearances for an insert installed in a masonry or listed factory built
fireplace can be found in the “Clearance to Combustible Walls” section.
Figure 10. Minimum Fireplace opening for the KOZI pellet insert.
8.1 KOZI BayWin®Pellet Insert Additional Requirements
When installing and removing a KOZI pellet insert in a masonry or listed factory built
fireplace, the following requirements must be met:
1. The room air must be sealed from the exterior. This can be achieved by
sealing the chimney cavity to the liner either at the terminal (see figure
9A) or at the chimney damper (see figure 9B).
2. When installing the insert and its surround, the air flow of the existing
fireplace must not be altered. Make sure no louvers, cooling air or
outlet ports are blocked.
Figure 9B. Factory built zero clearance or
masonry fireplace insert installation

Page 14
8.3 KOZI BayWin®Pellet Insert Installation
Please follow the following steps when installing a KOZI pellet insert:
1. Verify that the fireplace opening meets the insert’s minimum require-
ments.
Working from the exterior of the building:
2. Attach and seal the exhaust venting to the terminal using sheet metal
screws and high temperature (RTV) silicone sealant.
3. Insert the venting into the existing chimney and secure the terminal to
the chimney. Ensure that the venting and chimney are properly sealed.
4. If outside combustion air is being used, install the air intake as
necessary.
3. When installing an insert, a full height listed chimney liner must be
attached to both the insert flue collar and to the chimney top as shown
in figure 9A or a partial chimney liner may be attached to the insert
flue collar and extending a minimum of 6 inches into the chimney
cavity as shown in figure 9B. The junction of the chimney liner to the
seal plate must be properly sealed. This chimney liner must be
stainless steel.
4. A permanent metal tag must be attached to the back of the fireplace.
The metal tag will state the following “After removal of this pellet
insert, the fireplace must be restored to its original state for safe use”.
5. The fireplace can NOT be altered in any way except for the following
situations:
A. For installation of a chimney liner, the chimney damper may be
removed.
B. External trim pieces of a fireplace can be removed only if they do
not affect the operation of the fireplace upon removal and they can
be reassembled when the insert is removed.
8.2 Surround Assembly
The KOZI pellet insert surround can be seen in
Figure 11. The surround comes in 3 separate
pieces and needs to be assembled before being
attached to the heater. Layout the top and sides of
the surround on the floor as shown in figure 11.
Verify that each side piece mounting holes are
aligned with the top piece mounting holes. Using
the supplied 1/4” bolts, secure the side pieces to
the top. Your surround is now ready to mount to
the insert.
Figure 11. KOZI pellet insert surround

Page 15
Working from the interior of the building:
5. Verify that an electrical outlet is available for the pellet insert. If not,
have one installed.
6. Place the insert part way into the opening.
7. Attach and seal the free end of the exhaust venting to the pellet insert
using sheet metal screws and high temperature (RTV) silicone sealant.
8. If the top of the chimney was not sealed to the vent terminal in step 3,
seal the existing chimney damper to the new pellet venting to prevent
drafts to and from the home.
9. Plug the power cord into the electrical outlet.
10. Assemble the surround (if not previously assembled) and slide it on
the insert (see the “Surround Assembly” section).
11. Push the insert into the cavity until the surround touches the existing
fireplace.
8.4 KOZI BayWin®Pellet Insert Removal
There may be some situations where the KOZI pellet insert needs to be removed from
the fireplace. For example, venting may need to be resealed, parts may need to be
replaced on the insert, or maintenance may need to be either on both the insert and the
fireplace. Removal of the KOZI pellet insert heater from a fireplace is the reverse of
installation with the following exceptions: make sure the insert is not operating, has had
sufficient time to cool down and that power to the insert has been removed. Now you
can pull the insert all the way out and do the maintenance on the insert or fireplace.
8.5 Operation and Maintenance
A KOZI pellet insert operates in the same manner as a free standing stove. The only
difference between the stove and the insert is the method of loading the fuel into the
hopper. On a KOZI pellet insert, the hopper opening is much smaller than the stove
version. To load fuel into the insert, remove the cover plate from the top of the insert,
pour fuel into the opening and replace the cover plate. DO NOT place hands inside the
opening to the hopper. There are moving parts in the hopper which can cause bodily
harm.
Maintaining the KOZI pellet insert is the same as maintaining a free standing pellet
stove. Please read the “Maintenance” section for instructions on cleaning your insert,
venting and other maintenance precautions.
9. Mobile Home Additional Installation Requirements
9.1 Combustion Air Intake Requirements
It is MANDATORY for heaters being installed in a mobile home to have the combustion
air taken from the outside. The APR Part No: CV100 (Check Valve) CAN NOT be used
to provide internal combustion air from the mobile home to the heater. This heater must
be connected to the exterior of the mobile home using a non-combustible metal pipe,
with a minimum 2 inch (50 mm) diameter. Use of plastic pipes are not permitted. Please
read the “Combustion Air Intake Requirements” section for more information.

Page 16
9.2 Exhaust Vent Requirements
Venting a KOZI pellet burner for a mobile home is similar to that of a conventional
home. Please refer to the “Typical Mobile Home Installation Configuration” section for
typical venting configurations. It is highly recommended that a minimum vertical
venting of 3 ft be used (as shown in Figure 13). This will reduce the chance of smoke
spillage into the mobile home in case of a power failure.
9.3 Other Installation Requirements
1. The heater must be securely anchored to the floor of the mobile home.
There are 2 holes located on the base of the stove near the back. Use
two 1/4” lag bolts (not supplied) in these holes to anchor the stove to
the floor of the mobile home.
Figure 12. Anchoring Holes for Mobile Home Installations
2. There must be a non-combustible floor protector placed underneath the
heater and extending a minimum of 6” (150 mm) in front of the heater.
3. This heater can not be installed in any sleeping room of the mobile
home.
4. The heater must be grounded to the steel chassis of the mobile home
(unless this is not required by local code).
9.4 Typical Mobile Home Installation Configuration
The following figures describe some typical installations for mobile homes. Variations of
these are possible. Common sense, safety and compliance with local building codes must
be respected in any variation.
WARNING: DO NOT INSTALL IN A BEDROOM OF A MOBILE HOME
CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOOR, WALL
AND ROOF OF THE MOBILE HOME MUST BE MAINTAINED.

Page 17
Figure 14. Mobile home installation
through roof
Figure 15. Mobile home installa-
tion through wall
9.5 Recommendations for Mobile Home Installation
1. Make sure there is an effective vapor barrier where the venting
penetrates to the outside of the mobile home. Seal all openings in the
vapor barrier as required.
2. Make sure the mobile home has adequate ventilation. Your stove is a
solid fuel burning appliance. As such, there is a possibility of smoke
entering the room. By making sure the mobile home is adequately
vented, you reduce the chances of smoke remaining in the mobile
home.
3. Make sure the venting is properly installed and sealed. Leaking venting
may set off smoke detectors in the mobile home. Also, some fuels may
produce carbon monoxide which, in large amounts, can be fatal. Make
Figure 13. Mobile home installation
through wall

Page 18
sure the venting is installed properly to prevent leakage of carbon
monoxide into the mobile home.
4. If parts become damaged or need to be replaced, please contact your
local dealer or visit WWW.KOZISTOVES.COM. Do NOT replace
parts with any other parts not specified by your local dealer or
manufacturer.
II. Understanding Your Pellet Burning Heater
1. Component Description
1.1 General Overview
The first step in understanding your new KOZI heater is to familiarize yourself with its
operation. Your heater has 3 main systems: Combustion, Circulation and Feed. The
combustion system includes the air intake, burn pot, exhaust fan and exhaust venting.
The circulation system consists of a circulation fan, fan speed control and heat ex-
changer. The feed system is made up of an auger motor and various safety devices.
Each part of these systems will be described later in detail. A description of the
operation and the controls for your heater is provided in the section entitled “Heater
Operation”.
1.2 Exhaust Fan
The purpose of the exhaust fan is to remove the smoke from the combustion chamber.
The exhaust fan sucks air from the air intake, through the burn pot, around the heat
exchanger and pushes it through the venting. This fan is a fixed speed fan which turns
ON whenever the heater starts and remains ON until the heater is cool. THIS FAN
CANNOT BE TURNED OFF MANUALLY. Failure of this fan will result in a feed
system shut down.
1.3 Burn Pot
The burn pot is the receptacle in which the pellet fuel is burned. This portion of the
heater requires frequent cleaning since it controls the efficiency of the combustion
process. It is recommended the burn pot be cleaned every time the hopper is filled and
thoroughly scraped periodically. DO NOT over fill the burn pot with too much fuel.
This can cause the heater to overfire and create damage to your heater.
1.4 Circulation Fan
The purpose of the circulation fan is to circulate the unheated room air through the heat
exchanger and back into the room as hot air. The circulation fan speed can be controlled
by the fan speed control (described later). The control system has a built-in safety that
allows it to override the fan speed control in the event the heater overheats. As your
heater begins to overheat, the circulation fan will come on high to remove some of the
excess heat. As your heater cools, the circulation fan will return to it’s original setting.
If the circulation fan cannot remove the heat fast enough, a second safety, the high
temperature manual reset disk, will shut the feed system OFF.

Page 19
1.6 Auger Cycle Timer
In conjunction with the feed control, the auger cycle timer controls the feed rate. This is
achieved by turning the auger motor ON and OFF. Failure of this component will result
in a status light change. Refer to the “Trouble Shooting” section for more details.
1.7 High Temperature Manual Reset Thermal Disk
The manual reset thermal disk is a high temperature safety switch. If the heater should
reach an unusually high temperature, this switch will shut the feed system OFF. The
exhaust and circulation fans will continue removing heat until the heater is at room
temperature. Once this switch has been tripped, the control system will not allow any
more fuel to feed into the burn pot until it has been manually reset. DO NOT RESET
THIS UNIT UNTIL THE CAUSE HAS BEEN FOUND AND REPAIRED. Failure of
this component will result in a status light change. Refer to the “Trouble Shooting”
section for more details.
1.8 Pressure Switch
The pressure switch is a safety device that senses whether or not the combustion chamber
is under vacuum. Failure of the exhaust fan or leakage in the heater (such as opening the
door) will activate this safety component resulting in a status light change and a shut-
down of the feed system. Refer to the “Trouble Shooting” section for more details.
2. Heater Operation
In order to use your heater, you should be familiar with the 4 controls of your heater: Fan
Speed, Feed Rate, Damper and Start button. These 4 controls will allow you to adjust
and operate your heater safely and efficiently. The location and method of adjustment
for each of these is described next.
1.5 Trouble Shooting Module Status Lights
Figure 16. Trouble shooting
lights at the back of the heater
Your heater is equipped with 3 status lights. Each
light indicates a different safety device. Together,
these lights are intended to keep you informed as to
what is happening in the feed system. The top light
indicates the status of the auger cycle timer, the
middle light indicates the high temperature manual
reset thermal disk and the bottom light indicates the
pressure switch. In normal operation, all 3 lights will
be blinking ON and OFF in proportion to the feed
control setting (see “Heater Operation”). Should any
problem arise in the feed system, some or all of the
lights will either go out or be pulsing BRIGHT -
DIM. If this occurs, please refer to the “Trouble
Shooting” section.

Page 20
2.1 Circulation Fan Speed Control
The fan speed control is located on the top center of the control panel (see diagram).
Turning this knob counter-clockwise turns the circulation fan OFF. Rotating the knob
clockwise decreases the speed of the circulation fan from High to Low. It is NOT
recommended to leave this knob in the OFF position. When left in the OFF position, the
heater becomes over heated and the control circuit automatically overrides this switch
and puts the circulation fan on high speed.
2.4 Damper Control
The damper control rod is located on the left side of the heater. This rod controls the
amount of air passing through the burn pot. By pushing the control rod in, you reduce
the amount of air passing through the burn pot. By pulling the rod out, you will increase
the amount of air passing through the burn pot.
2.5 Starting (lighting) your Heater for the First Time
Once your heater is properly installed, complete the following steps to light it for the first
time or whenever your heater runs out of fuel:
1. Fill the hopper with pellet fuel. At this time the auger tube is empty. It
needs to be filled before the heater can be operated properly.
2. Turn the feed control knob clockwise to high.
3. Press the start button. The exhaust and circulation fan should come ON
and all 3 status lights should begin to blink.
4. Monitor the burn pot (located inside the burn chamber, see “Stove
Cross Section” diagram for exact location). Once pellet fuel begins to
drop into the burn pot, turn the feed control knob to medium (approxi-
mately 12 o’clock setting.). If the heater turns OFF before fuel begins
to drop into the burn pot, repeat steps 3 and 4.
Figure 17. Control panel
with controls
2.2 Start Button
The start button is located in the middle of the
control panel (see diagram). Pushing the start
button is the first step in starting the heater. The
heater will now run in manual operation mode
for 15 minutes. The heater will switch to the
automatic mode only if the heater reaches a
preset temperature. If this temperature is not
reached within 15 minutes the heater will shut
OFF. To allow the heater to run for another 15
minutes, simply press the start button once again
after the heater has shut OFF.
2.3 Feed Control
The feed control is a round knob located at the bottom of the control panel (see diagram).
Turning the knob in the counter-clockwise direction will turn the feed OFF. As the knob
is turned clockwise, the feed rate into the burn pot is increased, resulting in a bigger fire.
Table of contents
Other Kozi Pellet Stove manuals
Popular Pellet Stove manuals by other brands

Whitfield
Whitfield ADVANTAGE PLUS Owner's manual & operating instructions

Harman
Harman XXV Installation & operating manual

IronStrike
IronStrike WINSLOW PS40 quick start guide

Ravelli
Ravelli Powrmatic MONICA quick start guide

RIKA
RIKA DOMO MultiAir Assembly instructions

Harman Home Heating
Harman Home Heating P61A owner's manual

EdilKamin
EdilKamin VYDA AIR TIGHT Installation, use and maintenance

Ferroli
Ferroli SALERNO PELLET Assembly and exploitation manual

IKOS
IKOS MONO user manual

St. Croix
St. Croix PRESCOTT EX Operation & maintenance manual

Harman
Harman PELLET P61A Installation and operating manual

Ravelli
Ravelli RBC 8010 Use and maintenance manual