
2. ASSEMPLY AND INSTALLATION
a. Air Chutes (If Equipped) – Using the quick connect clamps (supplied); install two
cooling air chutes to your KwiKool portable air conditioner. Slide the plastic
flexible air chutes onto the metal flanges on the top front of the unit and tighten
the screw part of the clamps until snug to secure the chute. If the chute does not
fit, adjust the chute by a slight twist counter clockwise to open it further.
b. Condensate Tank – KwiKool units come with an external 5-gallon condensate
tank, except for the KPAC units, which have a built in tank. Both the internal and
external condensate tanks are equipped with a float assembly for automatic unit
shut down, when the condensate tank is full. The external tank’s condensate line
is attached to ¼-inch nipple located next to the power cord on the back of the
unit. The tank also has an attached plug jack, which is inserted into the female
hole above the nipple on the unit. If the plug jack is not inserted, the unit will
go into alarm and will not operate until the jack is inserted. An independent
condensate line can be used instead of the condensate tank. (See section 3.e.
Condensate Pump.)
c. Ceiling Kit (Optional Accessory) – The ceiling kit is comprised of two flanges
with screws, two 8-foot lengths of duct, duct clamps, and one (for 1.5-ton units
and below) or two (for all other air-cooled units) 2-foot by 2-foot replacement
ceiling tiles. Attach the flanges to the top on the unit, and then attach the duct to
each flange using the hose clamp. The other end of the duct is attached to the
replacement ceiling tile. If the optional ceiling kit is used, follow these guidelines
carefully. First, check above the ceiling to make sure that it is open to the whole
floor. If the sheet rock surrounding the room extends to the next floor
above the ceiling, above ceiling ducting is required through the sheet rock,
using a double flange ceiling kit. If the hot condenser air is ducted to dead
air space, the pressure will back up into the machine shutting it down, due
to high head pressure. If above ceiling ducting is used, check the model
specifications for the maximum condenser duct length. After you have
determined that the area above the ceiling is open to the whole floor, attach the
supplied duct to the replacement ceiling tiles using the clamps in the kit. Then
remove the appropriate ceiling tile above the unit position and insert the
replacement-ceiling tile. If there are two ceiling panels with your kit, make sure
that the deflector is facing the opposite direction to the other opening. This
prevents the intake and exhaust air streams from directly mixing. Attach the
hanging ducts from the ceiling panel to the collars on top of the unit and attach
with the supplied hose clamps. Split-system (SPLAC) models use a housing with
a single flange, which is attached to the condenser hot air exhaust. A single 12-
inch duct is attached to the flange and extended to a 2-ft by 2-ft replacement
ceiling tile, using the screw clamps.
d. Power Connection – Follow all safeguards as listed in this manual. For all units
that come with a factory-supplied plug, make sure that the voltage, amperage,
and receptacle type are consistent with the model specifications. For units 3.5-
tons and above a qualified electrician is required for connection of the 6-foot
pigtail lead on the recommended circuit for the specific model. For three-phase
units, it is important that the rotation of the evaporator fan (cold air supply) is
correct. Make sure the fan rotation is counter-clockwise in relation to the drive
motor. If it is going clockwise, switch two of the power leads. This should correct
the problem. Note: If the unit runs with the evaporator motor turning
backwards, the unit will overheat and either trip the high pressure
compressor switch or burn up the condenser motor.