KwiKool KIB Series User manual

KIB
Operation Manual


KwiKool KIB Iceberg Series
Operation Manual
Table of Contents
Before installing and using your KwiKool Portable Cooling
System, read this manual carefully for instructions and
proper usage and all safeguards.
This manual should be retained for future reference.
Section I / Unit Components - Page: 3
Section II / Assembly and Installation - Page: 4-6
Section III / Operational Safeguards - Page: 6
Section IV / System Operation - Page: 7-9
Section V / Built In Safeguards - Page: 9-10
Section VI / Application Requirements - Page: 10-11
Section VII / Maintenance - Page: 11
Section VIII / Utilizing Your KwiKool System - Page: 11
Section IX / Fault Codes - Page 12
Section X / KIB Troubleshooting Guide - Page: 12-15
Appendix:
Part A: Systems Equipped with a Phase Monitor - Page: 17-18
Part B: Special Section for KIB120 Systems - Page: 19-20


Page 3
I / Unit Components
Power Cord Compartment
Condenser Air Inlet
Condenser Air Outlet
Control Panel
Control Panel
Cold Air Supply
Cold Air Supply
Cold Air Return
Vent Control
Cold Air Return
Access Door
Condensate Nipple
Condensate
Alarm Jack

Page 4
II / Assembly and Installation
Air Chutes (If equipped or as an optional accessory) - Install supply air flanges to the
front of your KwiKool unit above the control panel. (See instructions in the air chute kit
for specific procedures).
A.
B.
Air Chutes - Conditioned air supply,
if equipped or as an optional accessory.
Condensate Tank - 5-gal Condensate
Tank with float assembly for automatic
cutoff.
Condensate Water Outlet -
1/4” OD barbed fitting
Condensate Float Switch Jack -
Connects to the condensate tank or is bypassed by
the factory installed male bypass switch plug pictured
Power cord with plug -
available on 1.1-ton thru 2.5-ton models
Condensate Tank - KwiKool systems come standard with an external 5-gallon
condensate tank. The external condensate tank is equipped with a float switch that
shuts your KwiKool down and alerts operators with an alarm and display CF
(“Condensate Full”) when the condensate tank is full. This prevents accidental water
overflow on the floor. The alarm will clear automatically upon emptying the 5 gallon tank
and reconnecting it. If connecting to a permanent drain, do NOT connect or use the
equipped tank. To use the external condensate tank, remove the factory installed
condensate float switch bypass plug on your KwiKool unit and install the male connector
jack supplied on the condensate tank. Next connect the factory supplied ¼” ID conden-
sate tubing to the ¼” OD barbed condensate water outlet on the back of your KwiKool
and connect the discharge end of the tube to the ¼” barbed connector on the conden-
sate tank. The condensate float jack must be inserted into the female condensate jack
to operate your KwiKool. CF displays if the jack is not connected or the bypass plug is
not inserted properly.
Cord Compartment

Page 5
Ceiling Kit - Discharge Outlet (Condenser exhaust)
& Discharge Make Up (Fresh Air Inlet)
1.
2.
Align the holes of the flange to the holes located on the top of the unit. Attach to the
top of the KwiKool unit using the factory supplied fasteners.
Attach each duct to the flanges on the replacement ceiling panel(s); secure the duct
to each flange using the supplied clamps.
Install the replacement ceiling panel(s) in the ceiling grid with the duct attached,
connect the open end of the duct to the flanges on your KwiKool and secure with
supplied clamps. Be sure the area where you are ducting can absorb the heat load
and is open enough to keep the system from returning its own hot discharge air.
Your KwiKool must have fresh make up air going to the condenser to operate.
**For Ceiling Kit Users** - The standard two duct ceiling kit (CK-XX) is recom-
mended to be used with KIBXX models for optimum performance. KwiKool’s Iceberg
(KIB) units may be used for primary, supplemental or standby cooling. Using
KwiKool’s exclusive ceiling kit ensures that you are able to utilize 100% of the units
rated capacity and without creating a negative pressure in your conditioned space.
KwiKool’s exclusive IO integral condenser system isolates both the condenser
discharge air and the condenser make up air from the conditioned space.
**Note: The space where the make up air and discharge air is directed (normally
above a drop ceiling) must be well ventilated and large enough for the heat load to
be absorbed. Condenser discharge air is prevented from entering the make up air
inlet by way of a factory installed deflector on your Ceiling Kit. Make sure that the
deflector is on the discharge (rear) duct from the unit. However if the condenser
discharge and return space is unventilated, closed off or unable to handle the heat
load, the make up air will continue to get hotter until the system is not able to handle
the high heat buildup. This will lead to the unit tripping its high pressure safety
switch. If this occurs, you will get an “HP” on the control panel. To resolve, fix the
lack of make up air and reset the high pressure switch per the instructions in the
Troubleshooting Guide section. Additionally, the ceiling kit replacement panel is not
limited to ceiling use and may be placed or fastened to any vertical or horizontal
surface providing the discharge and make up air is able to be directed to the space
where it is mounted. For areas with a closed ceiling or no ceiling use the double
flange ceiling kit method or extended duct method.
Visit www.KwiKool.com for more information and a complete set up guide.
Follow these installation steps:
3.
4.
Ceiling Kit (Optional Accessory) - The ceiling kit is comprised of flanges with foam
tape, fasteners, two (2) eight foot lengths of flexible duct, duct clamps, and one
24”X24” replacement ceiling tile for KIB 1411 and KIB1811. All other KIB models use
two (2) 24”X24” replacement ceiling tiles.
C.

Page 6
III / Operational Safeguards
Do not operate or install your KwiKool unit in a potentially explosive, combustible, or
corrosive gas atmosphere.
Keep your KwiKool system away from flammable materials and open flame.
To avoid electrical shock keep your KwiKool system away from direct contacts with
water and any liquids and do not touch your system with wet hands.
To insure your KwiKool system is stable, the floor on which the system is to be place
should be level, free of vibration and strong enough to support the weight of your
KwiKool model.
Do not move the system while it is operating. Before moving the system, first turn
system to OFF then unplug the system from the power source. Then unlock casters.
Do not tilt or overturn your unit, since this could damage the compressor.
Do not place objects on top of your unit.
Do not insert your hand or any other object into the cold air supply chutes.
Do not operate your KwiKool system with its service doors open.
If your KwiKool system makes abnormal noises or vibrations, call KwiKool at
1-800-594-5665.
B.
A.
C.
D.
F.
E.
G.
H.
I.
J.
Power Connection - Verify that the source power, phase and breaker size is
compatible with your KwiKool serial plate information and that the electrical circuit is
dedicated only for the use of your KwiKool Unit. If you aren’t sure about your power,
contact a licensed electrician. KwiKool systems are factory equipped with 8 feet of
power cable sized to meet the power requirement of your system. Extension power
cable is allowed but cannot exceed 25’ and must be rated to operate your KwiKool.
KwiKool units that come supplied with a factory installed plug require the exact recep-
tacle to match the plug and exact circuit size and power. Cutting the power plug on your
KwiKool unit will void its warranty. All other KwiKool systems over 3-tons are not
equipped with a male plug and must be hard wired by a qualified personal.
**Note: 208/230 volt systems require voltage to be selected to the proper voltage
before operating your unit. This is controlled by a rocker switch located on the top of the
control box in the service door. The factory default selection is 208 volts for KwiKool
systems purchased after June 2016 and 230 volts for equipment purchased before this
date. Always set teh voltage incoming to the correct setting to avoid potential opera-
tional issues. Read the Operational Safeguard section before applying electrical power.
D.
Read the following safeguards carefully before installing your KwiKool:

Page 7
IV / System Operation
Apply Electrical Power - Once power is engaged by plugging in your system
and/or switching the breaker to the on position, your KwiKool display will come alive
and show the current room temperature. The unit is set to OFF and the fan is set to the
default position. A 2 minute time delay starts, indicated by a flashing F on the display. If
you are not seeing anything on the display, refer to the Troubleshooting Guide section
of this manual.
Control Panel - The control panel display shows the current operational status of the
unit.
ON/OFF Button - Pressing this button on your control panel engages or shuts
down your KwiKool system. All settings selected are stored in the microprocessor
board even if the power is lost including the ON/OFF selection. Refer to the
Troubleshooting Guide section of this manual if your KwiKool is alerting an alarm
after selecting ON.
MODE Button - Depressing the MODE button selects your choice of operations.
Cool, for cooling with compressor operation. “Cool” will flash when the compres-
sor is running. “Cool“ will not flash when the room temperature is equal to or lower
than the set temperature or the system is timing out. Fan, for air circulation without
compressor operation.
F/C - Selects the way that room temperature and set point are displayed on the
control panel. Choices are Fahrenheit or Celsius. F is the factory default. This
indicator will flash when the system is in “time out” to prevent compressor short
cycling.
B.
A.
1.
2.
3.
+
-
FAN
F
Cool OFF
Fan
Display Shows - Current Temperature,
Set Temperature, or Alarm Codes
Display Shows - Unit Mode
Cool / Fan
Display Shows - Fan Speed (except single speed)
Display Shows - On / Off
Display Shows - Fan Mode

Single Speed Models - KIB 2411, KIB6023, KIB6043, **KIB12023,
**KIB12043. On the single speed models, pressing the fan key cycles the
supply air fan between auto fan and fan on. When the system is in auto fan,
the supply air fan only operates when the compressor is running. When the fan
is set to on, the fan runs continuously as long as the unit is in the ON position.
The fan speed window will be blank on these models.
Three Speed Models – (All other models NOT listed above.) The supply air fan
control button has several functions. First pressing the fan key will cycle
through the fan speeds. Each press cycles from low, med, high, and
multispeed. Multispeed will display all three speeds and flash only the speed
currently in use. The fan speed is automatically adjusted based on demand.
The second function is to change from auto fan to fan (constant fan). To
change this function, press and hold the fan key until the indicator changes
from fan (constant fan) to auto fan. When in FAN MODE, auto fan is not
available. If the unit was set to auto fan before changing the mode to fan, auto
fan will return when the unit is set back to COOL. Factory default is fan
(constant fan) and is the best choice for electronic equipment.
**KIB12023 and KIB12043 - These models are 2 stage systems and have a
fan speed for each stage. This feature is not user settable. This system
always starts in first stage fan speed (low) in COOL or FAN MODE, second
stage fan speed (high) only operates in COOL MODE when the second stage
compressor is running.
a.
C.
Turn On Your KwiKool System - Pressing the ON/OFF button once on your control
panel will put your unit in the ON position and “ON” will be displayed on the right
side of your display as well as the previously chosen mode.
System Operation -
1.
Page 8
Up (+) and Down (-) Arrow Buttons - Raises or lowers the desired set tempera-
ture. When changing the set point, pressing the + or – key, the word SET will
appear on the display and the current set point flashes ON and OFF. The value of
the set point is changed 1 degree each time the + or – is pressed. The adjusted set
point flashes on and off 12 times after the last change and then returns to display
the room temperature.
a.
b.
Lowering or raising the set point will not change the temperature of the
supply air. For best results always adjust the set point to a temperature your
KwiKool can cycle on and off at to avoid operational issues such as freezing or
rapid discharge fan cycling, KwiKool systems are designed to maintain the set
point when sized properly and constant operation without achieving the set
point may shorten the expected operational life of your system.
The lowest set point temperature available for your KwiKool is 60 degrees F,
and the highest setting is 95 degrees F. The control will not allow adjustments
beyond these ranges.
NOTES:
b.
c.
5.
Fan - Pressing the fan button has different operations depending on the model.
4.

Page 9
V / Built in Safeguards
KwiKool is proud to provide its customers with high quality features and safety devices
that are not found in most other brands.
COOL - If the unit was previously set to the cooling mode (cool) then “cool” will be
displayed. If the compressor is running, the ”cool” on the display will be flashing. If
your unit has been sitting for over 2 minutes, this should happen immediately upon
turning the unit on, unless your set point is lower than the current room tempera-
ture. In this case your unit is ready to automatically turn on once the temperature
rises above the set point. If the unit was recently turned off or the unit turned itself
off because it reached the set point, the compressor will not turn on until the
system waits for approximately 2 minutes. This prevents the compressor from
being damaged do to a condition called short cycling. The indicator that the unit is in
the “time out” condition is that the F (or C) in the display will be flashing. When the
compressor starts, the F will stop flashing and the “COOL” will begin flashing.
Note that the condenser fan will not start immediately with the compressor. And
once the condenser fan kicks in and if the ambient temperature entering the make
up air for the condenser return is below 75 degrees F you may notice the fan
cycling on and off, this is normal. For KIB120 models, the fan will instead speedup
and slowdown in lieu of turning on and off. If the display flashes 99, this indicates
ambient temperature of 99 degrees F or more. This is normal and will stop flashing
when the ambient temperature falls below 99 degrees F.
FAN - If the unit was previously set to the fan mode then “FAN” will be displayed
and the fan will start to run.
2.
3.
Time Delay - Protects your KwiKool from potential damage by delaying the compres-
sor from starting before the pressures in the mechanical system equalize. This always
activates when your KwiKool cycles off, is turned off, power is lost and then restored or
the operational mode is changed. Display flashes C or F if the time delay is activated.
Condenser Fan Cycling or Condenser Fan Speed Control - Part of your
KwiKool limited freeze protection and works by regulating the discharge air flow to keep
the refrigerant pressures at the optimum range.
High-Pressure Switch and Alarm - Protects your Iceberg Series unit from
potential damage to the mechanical system by shutting down, sounding an audible alarm
and displaying a fault code (HP) when the system pressure exceeds safe operating
conditions. The high pressure switch is a manual reset switch and must be reset after
the switch is activated and the condition causing the trip is corrected.
Low Pressure Switch and Alarm - Protects your KwiKool from potential damage
to the mechanical system by shutting down the system, sounding an audible alarm and
displaying a fault code (LP) when the low side pressure is too low. This is normally
caused by low refrigerant charge. This switch is an automatic reset.
Automatic Restart - In the event of a power loss your KwiKool Iceberg resumes
operation when the power is restored. All operational functions are preserved in the
memory of the Microprocessor Board including the ON/OFF selection.
B.
A.
C.
D.
E.

Condensate Pump & High Level Alarm - All KIB Iceberg models are factory
equipped with an internal high lift condensate pump. KwiKool condensate pumps are
able to pump the condensation either to the factory supplied condensate bottle, or to a
drain or other location as required by the application. The internal pump is rated at 20
foot of head pressure. This means it can pump water to a maximum of 20 feet vertically.
Each pump is equipped with an overflow safety cut-off that automatically shuts your
Iceberg unit down, sounds an audible alarm and displays a fault code (CP). This prevents
accidental flooding of the conditioned space.
Condensate Tank & High Level Alarm - All KIB Iceberg models come standard
with an external condensate tank. The tank is equipped with an overflow safety cut-off.
When the tank is full, the safety will automatically shut down your Iceberg unit, sound an
audible alarm and display a fault code (CF) This prevents accidental flooding of the
conditioned space. If you are using the supplied bypass plug and not using the tank this
alarm is nonfunctional.
Power/Phase Monitor (Optional) - The KwiKool Phase Monitor is available as an
option on all 3 phase KwiKool models. The phase monitor samples the power supply for
low or high voltage, out of phase and loss of phase. If any of these power conditions
arise, the Phase Monitor will automatically shut down your Iceberg unit, sound an
audible alarm and display a fault code (A1). This alarm will reset automatically when the
power is restored to normal.
Service Ports - Located in the filter access compartment in the front of your KwiKool
below the control panel. This gives service personal a connection point for service
gauges to monitor the operating pressures of your Icebergs refrigeration system.
Sight Glass/Moisture Indicator - Located in the discharge air make up inlet. This
feature allows operators and service personal to view the condition of the refrigerant
returning to the evaporator coil. Used as a diagnostic tool by qualified personal.
G.
F.
H.
I.
Page 10
VI / Application Requirements
Air Temperature Requirements - The environmental requirements of your
KwiKool unit at the installation site are 60 to 110 degrees F for the condenser make up
air located on the front inlet on the top of the unit. If the unit is operated in an environ-
ment above 110 F the high pressure switch may trip, stopping the unit’s compressor.
You also may notice diminished performance. The High Pressure Switch type is a
manual reset. The reset switch is located in the Return Air grill filter compartment.
Reset the unit by pressing the button labeled HP Reset. Standard air-cooled KwiKool
models are not designed to operate at temperatures below 60 degrees F. Low-
ambient temperature controls must be special ordered at an additional cost.
Temperatures below 60 degrees F will cause the discharge air exhaust fan to cycle
excessively and may damage the fan cycling switch, which requires qualified service
personal to repair and can void your warranty.
Capacity & Temperature Settings - Sizing of our units is based on matching
capacity to a specific heat load while maintaining a 72 degree F temperature. In order
to reach temperatures below 72 degrees F, the unit must have extra capacity. There-
fore, we recommend that you do not set the temperature set point below 70 degrees
F, unless you have excess cooling capacity beyond your heat load, since this may
cause the unit’s evaporator coil to freeze up.
B.
A.
J.

Page 11
VIII / Utilizing your KwiKool System
In contrast to conventional air conditioners, which circulate air conditioning capacity evenly
to an entire floor, KwiKool systems are designed for cooling an area with a high concentra-
tion of heat load, usually from electrical or computer equipment. Understanding the capabili-
ties of your KwiKool can help you avoid problems. For example, if you add heat-generating
equipment to the room after purchasing a KwiKool system, you may be short of the
necessary cooling capacity. Your KwiKool system offers an effective affordable solution for
many applications. It can also provide spot cooling for workers or process cooling within a
large space without the use of condenser ducting, such as a warehouse factory, or produc-
tion areas. If the system is used in this manner, the cold air supply must be within 5 feet of
the person or equipment being cooled, since the hot ambient air will mix with the cool air
very quickly. Your KwiKool system is specifically designed to adapt to today’s high tech
environments such as telecommunication or computer rooms and is equipped with the
necessary controls to maintain those special environments. Call your nearest KwiKool
Distributor or 1-800-594-5665 for help or for questions about other applications.
VII / Maintenance
Air Filters - Your KwiKool unit comes from the factory with filters installed on the
evaporator inlet to prevent dust and debris from entering the system and circulating in
the conditioned space, factory installed filters are a disposable type and must be
periodically checked and replaced based on the air quality of your conditioned space.
Failure to maintain the filters will cause restricted air flow and low overall unit
performance. The air filter is located on the front of your KwiKool unit below the
control, release the 2 slotted fasteners on the access door to open.
Conditioned Air Supply Drive Belts - Your KwiKool KIB120 models moves air
over the evaporator coil to remove heat and moisture from the conditioned space by
way of a motor attached to a blower wheel, this wheel turns by way of a pulley and belt
system. Inspect/adjust these belts every 60 days of operation, replace as needed.
Failure to maintain the drive belts will cause low performance, coil freezing or in
extreme cases damage to the blower/motor in the event of a belt breaking. Located in
the left side evaporator access door as you face the control panel. When adjusting the
belts, adjust them from the base of the motor. Do NOT adjust the sheave (pulley).
B.
A.
Positioning of Unit - Do not place your KwiKool unit in direct sunlight, The unit
should be positioned so that the output of the unit can be focused as close to the heat
generating equipment as possible with the front grill fully exposed. Do not block the
front of the unit, since this will cause a restriction in the airflow and can cause low
performance and/or evaporator coil freezing.
C.

IX / Fault Codes
Your KwiKool Iceberg System incorporates a self-diagnostic system that sounds an audible
alarm, stops your system and displays a fault code to indicate the nature of the problem on
the display panel. See the troubleshooting guide later in this manual for further information.
CF = Condensate Tank Full
CP = Condensate Pump Fault
HP = High Pressure Switch Tripped
LP = Low Pressure Switch tripped or tripping
A1 = Phase Monitor Senses power problem (if equipped)
FP = Freeze Protection
Page 12
X / KIB Troubleshooting Guide
Fault Possible Cause Possible Solution
Unit displays CF, Audio
alarm fails to clear on start
up or while operating
External Condensate Tank is
full. Condensate bypass jack
or condensate float switch
jack is not installed or not
positioned correctly. Water
level switch is engaged
Empty External Tank (if
using). Make sure thank is
upright and level. Unplug
bypass plug or tank plug and
reinstall to assure good
connections. System
automatically resets when
fault condition is corrected.
Unit Displays CP and Audio
alarm is sounding during
start up or while operating.
Microprocessor board has
detected high water level in
the condensate pump.
Inspect condensate pump for
over flow and proper
operation, check condensate
line for a clog or crimping.
Resets automatically upon
fault correction, or call
1-800-KwiKool if the problem
persist.

Page 13
Audio alarm fails to clear on
start up or while operating,
unit displays FP.
Microprocessor has
detected freezing on the
evaporator coil if the system
has a factory installed freeze
sensor. (Special order)
Check for freezing on the
evaporator coil and turn the
system off to let it thaw out,
call 1-800-KwiKool if your
system is not equipped with
a freeze sensor. Auto resets
upon correction.
System is ON and display is
showing ON but unit is not
supplying conditioned air.
System is in time out (F or
C is flashing), control is set
above room temperature or
control is adjusted out of
operating parameters or not
in the correct operational
MODE.
Wait 2 minutes, review
System Operations guide.
Unit Displays LP, Audio
alarm is sounding during
start up or while operating.
Microprocessor board has
detected low pressure. This
alarm might cycle on and
off.
Check air filter and replace
if dirty. Make sure nothing is
blocking the filter inlet.
Check for icing on coil.
Resets automatically when
fault condition is corrected.
Call 1-800-KwiKool if
condition continues.
Unit Displays A1, Audio
alarm is sounding during
start up.
Phase Monitor (if equipped)
has detected incoming
power issue on equipped
systems.
See Troubleshooting Guide
for systems equipped with a
phase monitor (Appendix -
Part B).
Unit Displays HP, Audio
alarm is sounding during
start up or while operating.
Microprocessor board has
detected high pressure. The
High Pressure switch is
tripped.
High pressure is normally
caused by reduced
condenser air flow. Check
for restriction in ducting.
Check for condenser air
system ventilation (See
Section II. C. 4). Check
condenser motors and/or
blowers for proper opera-
tion. On KIB12023 or
KIB12043 check VFD
(motor drive) for trip. Reset
if necessary. High pressure
is a manual reset type. To
reset, open filter door. The
button is located above the
filter. Press button to reset
(you should feel a click).
Fault Possible Cause Possible Solution

System is ON but the
microprocessor board
resets the time delay
(flashing F or C) when the
compressor attempts to
start.
Microprocessor board
detects voltage drop below
operating parameters.
Confirm the integrity of
your source power, check
for proper wire size and
length of power extension
cable. Be sure the circuit is
dedicated to only the
operation of your KwiKool.
Power is supplied but
control is blank
Low voltage circuit is not
engaged
Check source power
breaker and verify incoming
power to connector, reset
switch on low voltage
transformer in KIB120XX
and KIB6043 systems. Call
1-800-KwiKool for assis-
tance.
System trips breaker on
start up
Incoming power is incorrect,
breaker is undersized or
faulty, and or power cable is
too long and or undersized.
Verify the circuit and power
cable is within the systems
specifications, consult with
your electrician or call
1-800-KwiKool for
guidance.
System starts up and cools
but the condenser discharge
air exhaust fan ramps up and
slows down or the
condenser discharge fan
stops and starts.
Normal operating condition
especially in low tempera-
tures. Only the KIB120 or
units with optional ultra-low
ambient temperature
controls ramps up and
slows down. All other
models stop and start.
No action required, see
sections IV C. 2
Note: To avoid excessive
fan cycling, discharge
return air must not be
below the specifications of
your KwiKool system.
Page 14
Supply air flow is limited, and
or water is dripping from the
front of the system
Supply or return air is
blocked or restricted, and or
the evaporator coil is
freezing.
Verify that supply and
return air are not blocked
and duct work is installed
to specification, remove or
add duct as needed, check
air filter for blockage.
KIB120xx users check
supply air fan for correct
rotation, refer to Appendix
B.
Fault Possible Cause Possible Solution
Display shows 32 and unit
will not turn on cooling.
No connection of tempera-
ture sensor to Micropro-
cessor. Temperature
Sensor malfunction.
Call 1-800-KwiKool for
instructions.

Page 15
Condensate is not pumping. Water is below pumping
level, external line
restricted, line installed with
too high of lift.
Reservoir fills, and then
pumps. Check for line
crimping or restrictions and
proper line run height. Refer
to the user guide Section 5:
Built in Safeguards.
Evaporator coil is freezing Low or restricted air flow.
Undersized capacity, unit
constantly on, unable to
achieve set point. Low
return air temperature out
of factory specifications.
Evaporator door open,
mechanical system
malfunction.
Direct supply return air to
area of highest heat load,
check for blocked air flow
from the supply air, replace
air filters, adjust set point to
allow the unit to cycle, add
another KwiKool system or
larger capacity model, close
evaporator compartment
door, check for correct
rotation and inspect drive
belts on KIB120XX supply
air blower for worn condi-
tion or breaking, Install
service gauges to view
pressures.
Call 1-800-KwiKool
Chatter or hum is heard
from the control box while
the system is operating.
Incoming source power is
poor or low voltage compo-
nent is faulty.
Check for proper voltage
selection on 208/230 volt
units, remove excess or
undersized power cable, and
check incoming power.
Call 1-800-KwiKool.
Discharge air exhaust fan
stops and the system
alarms HP during operation.
KIB120XX only.
Condenser drive has
detected a fault with the
incoming electrical power or
is not receiving an operating
signal.
Check condenser motor
drive (VFD) for trip, reset if
needed. Note displayed fault
code on the drive and call
1-800-KwiKool if the problem
persist.
Fault Possible Cause Possible Solution
99 Flashes on display Ambient room temperature
over 99 degrees F.
Unit is working properly.
Lowering of room tempera-
ture will rectify the flashing.
60 Flashes on display Ambient room temperature
under 60 degrees F.
Limits of unit have been
reached. Operating tempera-
tures are 65 - 105 degrees F.

Appendix
Part A: Systems Equipped with a Phase Monitor - Page: 17-18
Part B: Special Section for KIB120 Systems - Page: 19-20
Page 16

Page 17
Unit displays A1 Audio
alarm sounding during start
up, phase monitor displays,
lock out “Front Fault” red
light
Phase monitor detects
reverse phasing, lost phase
or improper power incoming.
Exchange any line voltage
wire with the other, verify
incoming power. Auto reset
upon correction.
Unit displays A1, Audio
alarm is sounding during
start up, phase monitor
displays, lock out “Front
Fault” low volt red light.
Phase monitor detects
voltage lower than factory
setting.
Verify incoming power,
slowly raise voltage adjust
knob on the phase monitor
to match incoming power.
Auto reset upon correction.
Unit displays A1, Audio
alarm is sounding during
start up, phase monitor
displays, lock out “Front
Fault” high volt red light.
Phase monitor detects
voltage higher than factory
setting.
Verify incoming power,
Slowly lower voltage adjust
knob on the phase monitor to
match incoming power.
System starts up but goes
into visual and audible alarm
A1 when the compressor
starts.
Phase monitor detects
voltage drop.
Observe the phase monitor
on start for fault lights and
adjust the monitor accord-
ingly, verify incoming power.
Auto reset upon correction.
Check wire size and voltage
drop.
Unit displays A1, Alarm is
sounding during start up or
during operation, phase
monitor displays “Back
Fault” red light.
A fault has been detected
from one of the unit’s
condenser motors.
Inspect motor components
for faulty or loose connec-
tions and proper operation,
Call 1-800-KwiKool for
guidance.
A: Systems Equipped with a Standard Phase Monitor
Fault Possible Cause Possible Solution

LED Lights -
Used to indicate failure cause.
Voltage Adjustment Knob -
Set knob to match correct unit voltage.
Fault Interrogation Knob - Never Adjusted.
Factory set to 8 seconds for the time it takes
for non-critical fault to be analyzed & before
de-energizing load.
Lock-out Time Delay Knob - Never Adjusted.
Used for time between de-energizing and
re-energizing the load with a factory setting
of 1 minute.
Line Side -
Incoming voltage from the contractor.
Load Side -
Outgoing voltage from the contractor
b.
a.
c.
d.
e.
f.
% Voltage Unbalanced Knob -
This is the allowable voltage unbalanced
between the 3 phases with a factory
setting of 10%.
Reset Switches -
Position 1: Full Manual Reset (MAN-MAN).
Manual control reset used for highly critical
loads. The system will not reset until the fault
is corrected and then manually reset by
personnel.
Position 2: Leave In Full Automatic Reset
(AUTO-AUTO). Auto Front/Manual Back
Reset (AUTO-MAN). Automatic reset is used
on the front line side only (Power coming into
the unit). Back load side requires manual
reset. This setting is typically used with a
reliable power source (Power to condenser
& evaporator motors, and compressor).
g.
h.
b.
a.
c.
d.
e. f. g.
h.
Page 18
The KwiKool Phase Monitor is factory installed and is located
inside the Control Box. The Phase Monitor can be accessed
through the right side service door as you face the unit and
removing the cover to the control box.
This manual suits for next models
11
Table of contents
Other KwiKool Freezer manuals
Popular Freezer manuals by other brands

Sharp
Sharp SJ-SF226E2W-EU user manual

Mondial Elite
Mondial Elite KIC NX 60 datasheet

REMKO
REMKO RWT Series Operating and installation instructions

ThermoFisher Scientific
ThermoFisher Scientific CryoMed TSCM17XA Operating and maintenance instructions

Electrolux
Electrolux FCW 200 user manual

Beverage-Air
Beverage-Air HF Series Installation and operating instructions