Part VI Trouble Shooting
Table 6.1
Fault
Code
Fault Possible Causes Treatment
01E Hydraulic pressure
switch protection
(protect when
interrupts)
◇Hydraulic switch destroyed
◇Inadequate water-flow
◇There is air in the circulating
water inlet tube
◇Circulating pump destroyed
◇Water tank lack of water
◇Replace the hydraulic switch
◇Clean the wye strainer, increase the
water-flow
◇Discharge the air
◇Check and repair the pump and the
capacitor
◇Ensure the tank is fully filled and the
water pressure is over 0.15Mpa
02E Current protection ◇Over-current ◇Check the power supply
03E High pressure switch
fault (protect when
interrupts)
◇High pressure switch destroyed
◇Inadequate water-flow
◇The system is jammed, the probe
of sensor falls down
◇Circulating pump damaged
◇Excessive refrigerant
◇Some un-condensable gas in the
refrigerant system
◇Replace high pressure switch
◇Increase the flow
◇Check and clean the system, retighten
the probe
◇Check and repair the circulating pump
and the capacitor
◇Drain out the superfluous refrigerant
◇Drain out the un-condensable gas
04E Low pressure switch
fault (protect when
interrupts)
◇Low pressure switch destroyed
◇Inadequate refrigerant
◇The fins of the evaporator are
dirty
◇Replace low pressure switch
◇Leak hunting and fill in standard
quantity of refrigerant
◇Clean the fins
05E Overheating of the
outlet water
◇Clogged water line
◇water outlet temperature sensor
fault
◇Check the water system and the pump
◇Check the electric resistance of the
sensor
09E Communication error
( the control panel
can’t receive
information from the
PCB)
◇Open circuit or short circuit
between the operation panel and
PCB
◇Renovate or Replace the wire between
control panel and PCB
11E Coil sensor fault
(open circuit or short
circuit)
◇The sensor open circuit
◇The probe of the sensor falls
down
◇the sensor short circuit
◇Reconnect the wirings of the sensor
◇Retighten the probe
◇Renovate wirings and remove faults
12E Environment sensor
fault (open circuit or
short circuit)
◇The sensor open circuit
◇The probe of the sensor falls
down
◇the sensor short circuit
◇Reconnect the wirings of the sensor
◇Retighten the probe
◇Renovate wirings and remove faults
13E Water outlet sensor
fault (open circuit or
short circuit)
◇The sensor open circuit
◇The probe of the sensor falls
down
◇the sensor short circuit
◇Reconnect the wirings of the sensor
◇Retighten the probe
◇Renovate wirings and remove faults
15E Water-tank sensor
fault (open circuit or
short circuit)
◇The sensor open circuit
◇The probe of the sensor falls
down
◇the sensor short circuit
◇Reconnect the wirings of the sensor
◇Retighten the probe
◇Renovate wirings and remove faults
Note: when the fault arises, the correspondent fault code will be flashing on the screen and alarm sounds.