Land METEK SYSTEM 4 User manual

Landmark Graphic Processor
I/O Card
Installation Guide
Issue 3
30 November 2016
Publication Nº 198.245
Language: English
© Land Instruments International, 2016

Health and Safety Information
Read all of the instructions in this booklet - including all the WARNINGS and CAUTIONS
- before using this product. If there is any instruction which you do not understand, DO
NOT USE THE PRODUCT.
Safety Signs
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or
personal injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or
moderate injury to the user or users, or result in damage to the product or to property.
NOTE
Indicates a potentially hazardous situation which, if not avoided, could result in damage or the loss of
data.
Signs and Symbols used on equipment and Documentation
Caution, risk of electric shock.
Caution, attention to possibility of risk of damage to the product, process or surroundings. Refer
to instruction manual.
Caution, hot surface.
Protective Conductor Terminal.
Observe precautions for handling electrostatic discharge sensitive devices.
Equipment Operation
Use of this instrument in a manner not specied by Land Instruments International may be hazardous.
Read and understand the user documentation supplied before installing and operating the equipment.
The safety of any system incorporating this equipment is the responsibility of the assembler.
Protective Clothing, Face and Eye Protection
It is possible that this equipment is to be installed on, or near to, machinery or equipment operating at
high temperatures and high pressures. Suitable protective clothing, along with face and eye protection
must be worn. Refer to the health and safety guidelines for the machinery/equipment before installing
this product. If in doubt, contact Land Instruments International.
Electrical Power Supply
Before working on the electrical connections, all of the electrical power lines to the equipment must
be isolated. All the electrical cables and signal cables must be connected exactly as indicated in these
operating instructions. If in doubt, contact Land Instruments International.
Storage
The instrument should be stored in its packaging, in a dry sheltered area.
Unpacking
Check all packages for external signs of damage. Check the contents against the packing note.
Lifting Instructions
Where items are too heavy to be lifted manually, use suitably rated lifting equipment. Refer to the
Technical Specication for weights. All lifting should be done as stated in local regulations.
IMPORTANT INFORMATION - PLEASE READ

Health and Safety Information
Read all of the instructions in this booklet - including all the WARNINGS and CAUTIONS
- before using this product. If there is any instruction which you do not understand, DO
NOT USE THE PRODUCT.
Safety Signs
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or
personal injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or
moderate injury to the user or users, or result in damage to the product or to property.
NOTE
Indicates a potentially hazardous situation which, if not avoided, could result in damage or the loss of
data.
Signs and Symbols used on equipment and Documentation
Caution, risk of electric shock.
Caution, attention to possibility of risk of damage to the product, process or surroundings. Refer
to instruction manual.
Caution, hot surface.
Protective Conductor Terminal.
Observe precautions for handling electrostatic discharge sensitive devices.
Equipment Operation
Use of this instrument in a manner not specied by Land Instruments International may be hazardous.
Read and understand the user documentation supplied before installing and operating the equipment.
The safety of any system incorporating this equipment is the responsibility of the assembler.
Protective Clothing, Face and Eye Protection
It is possible that this equipment is to be installed on, or near to, machinery or equipment operating at
high temperatures and high pressures. Suitable protective clothing, along with face and eye protection
must be worn. Refer to the health and safety guidelines for the machinery/equipment before installing
this product. If in doubt, contact Land Instruments International.
Electrical Power Supply
Before working on the electrical connections, all of the electrical power lines to the equipment must
be isolated. All the electrical cables and signal cables must be connected exactly as indicated in these
operating instructions. If in doubt, contact Land Instruments International.
Storage
The instrument should be stored in its packaging, in a dry sheltered area.
Unpacking
Check all packages for external signs of damage. Check the contents against the packing note.
Lifting Instructions
Where items are too heavy to be lifted manually, use suitably rated lifting equipment. Refer to the
Technical Specication for weights. All lifting should be done as stated in local regulations.
IMPORTANT INFORMATION - PLEASE READ
Contact Us
UK - Droneld
Land Instruments International
Tel: +44 (0) 1246 417691
Email: [email protected]
Web: www.landinst.com
USA - Pittsburgh
AMETEK Land, Inc.
Tel: +1 412 826 4444
Web: www.ametek-land.com
China
AMETEK Land China Service
Tel: +86 21 5868 5111 ext 122
Email: [email protected]
Web: www.landinst.com
India
AMETEK Land India Service
Tel: +91 - 80 67823240
Email: [email protected]
Web: www.landinst.com
For further details on all AMETEK Land oces, distributors and representatives, please visit
our websites.
Return of Damaged Goods
IMPORTANT If any item has been damaged in transit, this should be reported to the carrier and to the
supplier immediately. Damage caused in transit is the responsibility of the carrier not the supplier.
DO NOT RETURN a damaged instrument to the sender as the carrier will not then consider a claim. Save
the packing with the damaged article for inspection by the carrier.
Return of Goods for Repair
If you need to return goods for repair please contact our Customer Service Department. They will be able
to advise you on the correct returns procedure.
Any item returned to Land Instruments International should be adequately packaged to prevent damage
during transit.
You must include a written report of the problem together with your own name and contact information,
address, telephone number, email address etc.
Design and Manufacturing Standards
The Quality Management System of Land Instruments International is approved to BS EN ISO 9001 for
the design, manufacture and on-site servicing of combustion, environmental monitoring and non-contact
temperature measuring instrumentation.
Approvals apply in the USA
Operation of radio transmitters, telephones or other electrical/electronic devices in close proximity
to the equipment while the enclosure doors of the instrument or its peripherals are open, may cause
interference and possible failure where the radiated emissions exceed the EMC directive.
The protection provided by this product may be invalidated if alterations or additions are made to the
structural, electrical, mechanical or pneumatic parts of this system. Such changes may also invalidate the
standard terms of warranty.
Copyright
This manual is provided as an aid to owners of Land Instruments International’s products and contains
information proprietary to Land Instruments International. This manual may not, in whole or part, be
copied, or reproduced without the expressed written consent of Land Instruments International Ltd.
Copyright © 2016 Land Instruments International.
MARCOM0311, Issue 7, 01 November 2016
Approvals apply in India

Installation GuideLandmark Graphic Processor I/O Card

Installation GuideLandmark Graphic Processor I/O Card
1
2
5
6
3
4
1
2
1
2
3
4
5
1
2
3
4
5
6
7
THERMOMETER OUTPUT CMD ALARMS
1
2
3
4
5
RS 485
RS 232C
200 - 240V
100 - 120V
T 1A 250V35VA MAX.
50-60Hz
1
2
5
6
3
4
1
2
1
2
3
4
5
1
2
3
4
5
6
7
1
2
5
6
3
4
1
2
1
2
3
4
5
1
2
3
4
5
6
7
LANDMAR K G RAPHIC ®
LMG 1 1
S/NO. 123/456/78
MADE IN E NGLAND
1994
1
2
5
6
3
4
1
2
1
2
3
4
5
1
2
3
4
5
6
7
AB
C D
A
A A
A B
B
Fig. 1 Location of I/O Card andscrews on back panel
I/O Card

Page 1
Installation Guide Landmark Graphic Processor I/O Card
1 Introduction
The information contained in this Installation Guide describes the procedures
necessary to either t a new I/O Card or replace an existing I/O Card.
2 Description
An Input/Output (I/O) card serves as a hardware interface between:
• a System 4 thermometer
(or System 4 type Application-Dedicated thermometer)
and
• a System 4 LMG processor
(or Application-Dedicated processor based on LMG)
An I/O card is designed to provide a complete hardware interface for a single
thermometer. The specic thermometer type and its settings are all selected
subsequent to I/O card installation via the processor’s human interface.
All connections to and from a thermometer pass through it’s I/O card. The
I/O card also provides signal-conditioned outputs for connection to third-party
processes.
The array of connections typically include:-
To thermometer:
1. d.c. power supply
2. Signal screens
3. Emissivity setpoint
From thermometer:
1. Measured temperature
To third-party process:
1. Analog output – current
2. Analog output – voltage
3. 2 x alarms
4. Command line for peak-picker reset control, etc.
System 4 thermometers and Application-Dedicated derivatives, provide high-
precision analog outputs of measured temperature. The I/O card samples
these signals, digitises them and removes systematic linearisation errors,
thus improving overall measurement accuracy.

Page 2
Landmark Graphic Processor I/O Card Installation Guide
It should be noted that there are a number of different I/O cards available
from Land for LMG processors or Application-Dedicated processors based on
LMG.
Card ID Nº Description Compatibility
1 S4 I/O Card System 4 & Single-wavelength
System 4-type Application-
Dedicated Thermometers ONLY
2 AETS I/O Card AETS Thermometers ONLY
3 AQTS I/O Card AQTS Thermometers ONLY
4 ASTS I/O Card ASTS Thermometers ONLY
5 GSTS I/O Card GSTS Thermometers ONLY
6 RP4 I/O Card RP4 Thermometers ONLY
It is important to ensure that you have the correct card type for the
thermometer you wish to interface. Refer to the User Guide supplied with
your processor for further information.

Page 3
Installation Guide Landmark Graphic Processor I/O Card
3 Installation Instructions
This section must be referred to when installing or removing an I/O Card.
Warning
Risk of electric shock.
Disconnect the processor from the a.c. mains power supply before
removing the rear panel.
Caution
Observe precautions for handling electrostatic discharge sensitive
devices.
Note
To disassemble and re-assemble the processor, a 2.5mm AF hexagonal
driver will be required.
1) Refer to Fig. 1. Unscrew the four screws (A). Retain the screws in a
safe place for re-assembly.
2) Remove the rear panel. The thermometer channel Input/Output (I/O)
card(s) and the Serial Communications card (if tted) should now be
clearly visible.
3) Insert/remove the I/O card by sliding it into/out of the appropriate
slot in the rear of the processor.
4) Ensure that the Serial Communications card, if tted, is in the slot
immediately to the left of the power supply unit of the processor.
5) Fit the rear panel onto the processor. Insert and tighten the four
hexagonal screws (A), which secure the rear panel to the processor.

Page 4
Landmark Graphic Processor I/O Card Installation Guide

PRODUCT WARRANTY
Thank you for purchasing your new product from Land Instruments International. This Land
manufacturer’s ‘back-to-base’ warranty covers product malfunctions arising from defects in design
or manufacture. The warranty period commences on the instrument despatch date from the Land
Instruments International Ltd. factory in Dronfi eld, UK.
36 MONTHS WARRANTY
Building upon the reputation for reliability and longevity that System 4 and UNO thermometers
have earned, Land are delighted to be able to provide our customers with an industry-leading
36 month warranty for the following products:-
• SPOT thermometers, accessories and mountings and special instruments based on SPOT.
• System 4 thermometers, processors, accessories and mountings and special instruments
based on System 4.
• UNO thermometers, accessories and mountings and special instruments based on UNO.
• Application-dedicated processors based on LANDMARK®Graphic.
• ABTS/S and ABTS/U
• FTS
• VDT/S and VDT/U
• DTT
• FLT5/A
This 36 month warranty is provided as standard for all orders for the products listed above received from
1st May 2002.
We believe that our customers expect us to set the standard in terms of performance, quality, reliability and
value for money. This 36 months warranty, as a part of an on-going program of continuous improvement,
is just one way in which Land strive to maintain our position as the temperature measurement partner of
choice.
24 MONTHS WARRANTY
The following Land Instruments International products are provided with a 24 months warranty:
• ARC
• FTI-E
• NIR
12 MONTHS WARRANTY
All Land Instruments International products not provided with either a 36 month or 24 month warranty (see
lists above), are provided with a 12 months warranty.

PRODUCT WARRANTY
EXCLUSIONS FROM WARRANTY
It should be noted that costs associated with calibration checks which may be requested during the warranty
period are not covered within the warranty.
Land reserve the right to charge for service/calibration checks undertaken during the warranty period if the
cause is deemed to fall outside the terms of the warranty.
This Land manufacturer’s warranty does not cover product malfunction arising from:-
• incorrect electrical wiring.
• connection to electrical power sources outside the rating of the product.
•physical shock (being dropped, etc.) and impact damage.
•inappropriate routing, support, physical shock & strain protection, etc. of the lightguide (Fibroptic
thermometers only).
•environmental conditions exceeding the IP / NEMA rating of the product.
•environmental conditions outside the Ambient Temperature, Humidity and Vibration rating of the product.
•environmental contamination (solvent vapours, deposition of airborne contamination, cooling liquids of
non-neutral pH, etc.).
•overheating as a result of interruption of water/air fl ow through cooling jackets or of incorrect installation.
•inappropriate modifi cation of product (drilling holes in thermometer bodies, etc.).
•inappropriate recalibration which results in product calibration being taken outside specifi cation.
•improper resealing of thermometer following parameter adjustment (UNO, FLT5/A, etc.).
• attempted repair by a non-Land-authorised repair centre.
Land Instruments International Ltd • Dronfield S18 1DJ • England • Tel: +44 (0) 1246 417691 • Fax: +44 (0) 1246 410585
AMETEK Land, Inc. • 150 Freeport Rd. • Pittsburgh, PA 15238 • U.S.A. • Tel: +1 (412) 826 4444
For a complete list of our international offices, please visit www.landinst.com Issue 4: 23 November 2016
MARCOM0290
Table of contents
Popular I/O System manuals by other brands

DAQ system
DAQ system PCI-DIO64 Series user manual

Unitronics
Unitronics Vision V350-35-TR34 installation guide

BQTEK
BQTEK BQ351 user manual

ABB
ABB AC500 Series installation instructions

Rockwell Automation
Rockwell Automation ArmorBlock Series installation instructions

Siemens
Siemens SIMATIC ET 200SP manual

Beckhoff
Beckhoff EPP4374-0002 manual

Allen-Bradley
Allen-Bradley 1769-IT6 user manual

Rockwell Automation
Rockwell Automation Allen-Bradley Micro800 Wiring diagrams

VILLBAU
VILLBAU EC-84 Installer manual

IFM Electronic
IFM Electronic CR2013 Device manual

Sun Microsystems
Sun Microsystems Fire 6800 Assembly Installation Guide