
Page 14
Cooling Start−Up
IMPORTANT−The crankcase heater (standard on
some models) must be energized for 24 hours before
attempting to start compressor. Set thermostat so there
is no demand to prevent compressor from cycling.
Apply power to unit.
A−Preliminary C ecks
1− Make sure that unit is installe in accor ance with the
installation instructions an applicable co es.
2− Inspect all electrical wiring, both fiel an factory
installe , for loose connections. Tighten as require .
3− Check to ensure that refrigerant lines o not rub
against the cabinet or against other refrigerant lines.
4− Check voltage at isconnect switch. Voltage must
be within range liste on nameplate. If not, consult
power company an have voltage con ition
correcte before starting unit.
5− Refer to unit iagram locate on insi e of
compressor access oor for unit wiring.
6− A just blower belt or blower spee tap accor ing to
Blower Operation an A justments" section.
7− Make sure filters are in place before startup.
B−Start−Up
1− Set fan switch to AUTO or ON an move system
selection switch to cool. A just thermostat to a
setting below room temperature to bring on the
compressor. Compressor will start an cycle on
eman from thermostat.
2− The refrigerant circuit is charge with HCFC−22
refrigerant. See unit rating plate for correct
amount of charge.
3− Refer to Cooling Operation an A justment section
for proper metho to check refrigerant charge.
C−T ree P ase Scroll Compressor Voltage P asing
Three phase scroll compressors must be phase
sequentially to ensure correct compressor an blower
rotation an operation. Compressor an blower are
wire in phase at the factory
1− Observe suction an ischarge pressures an
blower rotation on unit start−up.
2− Suction pressure must rop, ischarge pressure
must rise, an blower rotation must match rotation
marking.
If pressure ifferential is not observe or blower rotation is
not correct:
3− Disconnect all remote electrical power supplies.
4− Reverse any two fiel −installe wires connecte to
the line si e of S48 isconnect or TB2 terminal strip.
Do not reverse wires at blower contactor.
5− Make sure the connections are tight.
Discharge an suction pressures shoul operate at
their normal startup ranges.
D−C arging/C ecking C arge
WARNING−Do not exceed nameplate c arge under any
condition.
This unit is factory charge an shoul require no further
a justment. If the system requires charge, reclaim the
charge, evacuate the system, an add required
nameplate charge.
NOTE − System charging is not recommended below 60_
(15_C). In temperatures below 60_ (15_C), the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following proce ure:
IMPORTANT − C arge unit in standard cooling mode.
1− Attach gauge manifol s an operate unit in cooling
mo e until system stabilizes (approximately five
minutes). Make sure all out oor air ampers are close .
2− Use a thermometer to accurately measure the
out oor ambient temperature.
3− Apply the out oor temperature to tables 12 through
14 to etermine normal operating pressures.
4− Compare the normal operating pressures to the
pressures obtaine from the gauges. Minor
variations in these pressures may be expecte ue to
ifferences in installations. Significant ifferences
coul mean that the system is not properly charge or
that a problem exists with some component in the
system. Correct any system problems before
proceeding.
5− If ischarge pressure is high, remove refrigerant from
the system. If ischarge pressure is low, a
refrigerant to the system.
SA or remove charge in increments.
SAllow the system to stabilize each time refrigerant is
a e or remove .
6− Use the following subcooling metho along with the
normal operating pressures to confirm rea ings.