LG Multi V Series User manual

P/NO : MFL61971203
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : CONSOLE
ENGLISH ITALIANO ESPAÑOL FRANCAIS DEUTSCH
PORTUGUESE
êìëëäàâüáõä

Console Type Indoor Unit Installation Manual
TABLE OF CONTENTS
o Installation guide map
oConnecting cable
oPipes: Gas side
Liquid side
oInsulation materials
oAdditional drain pipe
oLevel gauge
oScrew driver
oElectric drill
oHole core drill
oHorizontal meter
oFlaring tool set
oSpecified torque wrenches
oSpanner .......Half union
oHexagonal wrench
oGas-leak detector
oVacuum pump
oGauge manifold
oOwner's manual
oThermometer
Installation Parts ....................3
Safety Precautions .................4
Installation
Selection of the Best Location
...7
Indoor unit installation............8
Flaring Work.........................14
Connecting the Piping .........15
Wiring Connection ...............17
Installation of Wired Remote
Controller..............................18
Installer Setting -Thermistor
..............................................20
Dip Switch Setting ...............21
Group Control Setting..........22
Installation Requirements Required Parts Required Tools
2Indoor Unit

Installation Manual 3
ENGLISH
Signal receiver
ON/OFF button
Operation lamp
Air purifier lamp
Signal receiver
Air filter
Allergy filter
Air outlet
Air inlet
Installation Parts
Name
Quantity
Shape
- Allergy Filter
- Fixing screw for Installation
Plate 4*25 mm-5EA
- Wood screw for indoor
fixation -6EA
- Owner's Manual
- Installation Manual
Installation
Plate
1 EA
Other
Drain Hose
1 EA
Clamp
(Tie wrap)
4 EA
Installation Parts

Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
nBe sure to read before installing the air conditioner.
nBe sure to observe the cautions specified here as they include important items related to safety.
nIncorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the
following indications.
nMeanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
nInstallation
Do not use a defective or under-
rated circuit breaker. Use this
appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the
dealer, seller, a qualified electri-
cian, or an Authorized Service
Center.
• Do not disassemble or repair the
product. There is risk of fire or elec-
tric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover
of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated cir-
cuit and breaker.
• Improper wiring or installation may
cause fire or electric shock.
Use the correctly rated breaker
or fuse.
• There is risk of fire or electric shock.
Safety Precautions
4Indoor Unit

Installation Manual 5
ENGLISH
■Operation
Do not modify or extend the
power cable.
• There is risk of fire or electric shock.
Do not let the air conditioner
run for a long time when the
humidity is very high and a door
or a window is left open.
• Moisture may condense and wet or
damage furniture.
Be cautious when unpacking
and installing the product.
• Sharp edges could cause injury. Be
especially careful of the case edges
and the fins on the condenser and
evaporator.
For installation, always contact
the dealer or an Authorized
Service Center.
• There is risk of fire, electric shock,
explosion, or injury.
Do not install the product on a
defective installation stand.
• It may cause injury, accident, or
damage to the product.
Be sure the installation area
does not deteriorate with age.
• If the base collapses, the air condi-
tioner could fall with it, causing prop-
erty damage, product failure, and
personal injury.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Gasolin
Safety Precautions
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge.
Do not compress air or Oxygen and Do not use Flammable gases.
Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.

Installation Manual 7
ENGLISH
Installation
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must have the maintenance space.
Read completely, then follow step by step.
More than 300
250 or below
from the Floor
More than
300
More than
300
(Unit : mm)
Installation
Selection of the Best Location
In case that the unit is installed near the sea, the installation parts may be corroded
by salt. The installation parts (and the unit) should be taken appropriate anti-corro-
sion measures.

Indoor unit installation
1. Preparation / Removing front panel
1. Open the front grille by pulling forward
2. Then pull out the link of grille from groove in front panel.
3. Then pull out 2 hinges of grille from grooves in front panel.
4. Then remove 4 screws, dismount the front panel while pulling it forward.
2. Preparation / For Moldings , Side Piping, and Concealed
Installation
2-1 For Moldings
1. Remove the slit portions on the Rear Panel.
2-2 For Concealed Installation
1. Remove the 6 screws.
2. Remove the Upper Deco cover.
3. Remove the Side Deco covers.
2-3 For Side Piping (Reference 2-2.)
1. Remove the Deco Covers.
2. Remove the slit portions
3. Assemble the Deco Covers.
Remove
Upper Deco cover
Side Deco cover
Installation
8Indoor Unit

Installation Manual 9
ENGLISH
1. The location of hole is different depending on which side of the pipe is taken out.
2. Drill a hole(Ø70mm) in the point indicated by symbol in the illustration as below.
(Unit : mm)
45
90 75
Left bottom piping Right bottom piping
Left/right piping
Right back piping
60
40
50
Wall
45
90 75
Left back piping
Right back piping
45
3. Refrigerant Piping
- The suggested shortest pipe length is 5m,in order to avoid noise from the outdoor unit and vibration.
NOTICE
Installation

1. The Outer diameter of Drain Hose
(which is supplied with indoor unit) is
17mm at connecting end, 600mm
long.
2. Use commercial rigid PVC pipe for
extension.
3. Insulate the indoor drain pipe with
10mm or more of insulation material
to prevent condensation.
600
Ø17
[Unit : mm]
103
87
5. Drain piping
- The drain pipe should be inclined downward so that water will flow smoothly without any accumulation.
NOTICE
Do not raise Accumulated
drain water Tip of drain hose
dipped in water
Air
Waving
Water
leakage
Water
leakage Ditch
Less than
50mm gap
Water
leakage
• Drill the piping hole with a ø70mm hole core drill.
Drill the piping hole at either the right or the left
with the hole slightly slanted to the outdoor side.
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
4. Drill a Hole in the wall
Installation
10 Indoor Unit

Installation Manual 11
ENGLISH
6. Installing Indoor unit
6-1 Installation on the Floor.
1. Fix up using 6 screws for floor installation.
6-2 Installation on the Wall
1. Fix up the installation plate using 5 screws and the indoor unit using 4 screws.
2. The installation plate should be fixed on a wall which can support the weight of the indoor unit.
6 screw (M4*25L)
64
159
(700)
(Unit : mm)
26
647
180
140
(600)
574
170
170
210
30.5
30.5
140
160
Installation Plate
Molding
4 screw (M*25L)
Installation

6-3 Half concealed installation.
1. Make a wall hole of the size shown Fig-1.
2. Installation of supplemental plate for attaching main unit
• The rear of the unit can be fixed with screws at the points shown in the Fig-2.Be sure to install the
supplemental plate in accordance with the depth of the inner wall.
670
45
585
200
150
Wall
Hole
Supplemental plate
(Field supply)
200
150
95 Supplemental plate
(Field supply)
647
170
140
170
140
(Unit : mm)
1) Normal concealed 2) Deep concealed
(Unit : mm)
<Fig - 1>
<Fig - 2>
Installation
12 Indoor Unit

Installation Manual 13
ENGLISH
3.Piping Hole
4. Remove the Deco Covers and Fixing Indoor
Unit
1) Remove the Deco Covers.
2) Insert the Indoor Unit to the Wall hole.
3) Secure using 6 screws. (shown in the illus-
tration)
- Check the horizon of Indoor unit with the wall. Please use the leveler on the drain pan guide.
Wall
Wall
75
50
35
75
Left bottom piping
Left pipng
45
50 (Unit : mm)
Right bottom piping
NOTICE
Less than 5mm
Less than 5mm Less than 5mm
Leveler Drain pan
Installation

Flaring Work
Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following proce-
dure.
Cut the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased
locally.
2. Measure the distance between the indoor and the out-
door unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section
of pipe/tube.
2. While removing burrs put the end of the copper
tube/pipe in a downward direction while removing
burrs location is also changed in order to avoid drop-
ping burrs into the tubing.
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit,
then put them on pipe/tube having completed burr
removal.
(not possible to put them on after finishing flare work)
Flaring work
1. Firmly hold copper pipe in a bar with the dimension
shown in below table table below.
2. Carry out flaring work with the flaring tool.
Copper
pipe
90°Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 1.1~1.3
Ø9.52 3/8 1.5~1.7
Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8
Ø19.05 3/4 1.9~2.1
Outside diameter A
Bar
Copper pipe
Clamp handle Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Installation
14 Indoor Unit

Installation Manual 15
ENGLISH
When you connect the refrigerant pipe, it is easier that you connect the gas pipe first.
1. Hold up the Sensor Link.
2. Separate the Pipe Bracket (2 screws)
3. Connect the refrigerant pipe. (Refer to next page)
4. Assemble the Pipe Bracket (2 screws)
5. Put down the Sensor Link
6. After connecting, check the pipe arrangement as per illustration.
7. The piping can be arranged in six ways as shown in the illustration below.
In case of ③ ~ ⑥, The pipe banding can be used in hand-operated banding machine.
Make a pipe of the shape shown pic 8.
Connecting the Piping
3
1
2
6
5
4
Pipe Guide
Pipe Guide
Connecting Pipe must be placed inner
than the pipe guide.
Connecting
Connecting
Pipe
Pipe
Connecting
Pipe
678
12
45
3
Installation

Connecting the installation pipe and
drain hose to the indoor unit.
1. Align the center of the pipes and sufficiently
tighten the flare nut by hand.
2. Tighten the flare nut with a wrench
3. When needed to extend the drain hose of
indoor unit, assembly the drain pipe as shown
on the drawing
Wrap the insulation material around
the connecting portion.
1. Overlap the connection pipe insulation material
and the indoor unit pipe insulation material.
Bind them together with vinyl tape so that there
may be no gap.
2. Wrap the area which accommodates the rear
piping housing section with vinyl tape.
3. Bundle the piping and drain hose together by
wrapping them with vinyl tape sufficient enough
to cover where they fit into the rear piping
housing section.
If the drain hose is routed inside the room insu-
late the hose with an insulation material* so
that dripping from sweating (condensation) will
not damage furniture or floors.
* Foamed polyethylene or equivalent is recom-
mended.
mm inch kgf.m
Ø6.35 1/4 1.8~2.5
Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.5
Ø15.88 5/8 6.3~8.2
Ø19.05 3/4 9.9~12.1
Outside diameter Torque
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide) Wrap with vinyl tape
Indoor unit pipe
Pipe
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Connecting pipe
Connecting
cable
Tape
Drain hose
16 Indoor Unit

Installation Manual 17
ENGLISH
Terminal block of indoor unit
Terminal block of outdoor unit
1(L) 2(N) 3(A) 4(B)
Indoor power input
220V 60Hz
IDU IDU
Outdoor unit Indoor unit
Central controller
SODU SODU
DRY1 DRY2 GND
INTERNET 12V
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Wiring Connection
Make sure that the screws of the terminal are free from looseness.
The Power cord connected to the unit should be selected according to the following
specifications.
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the cir-
cuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function
of a overload protection device.
• Proper starting power is not given to the compressor.
Installation

Installation of Wired Remote Controller
22
1
3
3
<Wire guide grooves>
1. Please fix tightly using provided screw after placing remote controller setup board on the place where
you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends.
Please set up remote controller board fit to the reclamation box if there is a reclamation box.
2. Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller
cable guide groove.
h
Remove guide groove with long nose.
①
Reclamation to the surface of the wall
②
Upper part guide groove
③
Right part guide groove
Wall
Side
Wall
Side
Wall
Side
Wall
Side
<Connecting order>
<Separating order>
3. Please fix remote controller upper part into the
setup board attached to the surface of the wall, as
the picture below, and then, connect with setup
board by pressing lower part.
- Please connect not to make a gap at the remote con-
troller and setup boardʼs upper and lower, right and left
part.
When separating remote controller from setup
board, as the picture below, after inserting into the
lower separating hole using screw driver and then,
spinning clockwise, remote controller is separated.
- There are two separating holes. Please individually
separate one at a time.
- Please be careful not to damage the inside
components when separating.
Installation
18 Indoor Unit

Installation Manual 19
ENGLISH
4. Please connect indoor unit and remote controller using connecting cable.
5. Please use extension cable if the distance between wired remote controller and indoor unit is more
than 10m.
Please check if connector is normally connected.
Connecting cable
Indoor
Unit side
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the
remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.

20 Indoor Unit
Installation
Function Code Thermistor setting
Set Thermistor value by pressing
button. (01: Remote Controller,
02: Indoor, 03: 2TH)
3
Press button to save.
4
5
If moving to room temperature perception
sensor selection menu by pressing
button, it indicates as picture below.
2
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
1
Pressing button will exit settings mode.
❈After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈When exiting without pressing set button,
the manipulated value is not reflected.
PQRCVSLO
Installer Setting -Thermistor
jThe function of 2TH has different operation characteristics according to the product.
Temperature sensor selection Function
01 Remote controller Operation in remote controller temperature sensor
02 Indoor unit Operation in indoor unit temperature sensor
03 2TH
Cooling
Operation of higher temperature by comparing indoor unit's and wired remote
controllerʼs temperature.
(There are products that operate at a lower temperature.)
Heating Operation of lower temperature by comparing indoor unit's and wired remote
controller's temperature.
<Thermistor Table>
This is the function to select the temperature sensor to judge the room temperature.

Installation Manual 21
ENGLISH
Dip Switch Setting
For Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.
That dip switch is used for other models.
Installation
Function Description Setting Off Setting On Default
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
Communication
Cycle
Group Control
Dry Contact Mode
Installation
Heater linkage
Ventilator linkage
Vane selection
(Console)
Region selection
Etc.
N/A (Default)
N/A (Default)
Selection of Master or Slave
Selection of Dry Contact
Mode
Fan continuous operation
N/A
Selection of Ventilator link-
age
Selection of up/down side
Vane
Selection tropical region
Spare
-
-
Master
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Continuous operation Removall
-
Linkage Removal
Up side + Down side Vane
General model
-
-
-
Slave
Auto
-
-
Working
Up side Vane
Only
Tropical model
-
Off
Off
Off
Off
Off
Off
Off
Off
Other manuals for Multi V Series
8
Table of contents
Other LG Air Conditioner manuals

LG
LG LSN090CE, LSN120CE, LSN180CE, LSN240CE, LSN090HE, LSN120HE, LSN180HE, LSN240HE, LSU090CE, LSU120CE, LSU180CE, LSU240CE,... User manual

LG
LG HWC093GBAA0.AWYBLPS User manual

LG
LG AVNQ18GJLA0 User manual

LG
LG LWHD1200FR User manual

LG
LG UVNH36GLLA1 User manual

LG
LG LW1010ER User manual

LG
LG LP1413SHR User manual

LG
LG LP6000ER User manual

LG
LG UV36.NKD User manual

LG
LG AMNH12GAF11 User manual