Livezi Z-Plus User manual

No More
Capacity Dumping
0~100% airow adjustment in
every zone
Touchscreen Controller
Works with Dual,
Digital and Radical
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
Z-Plus Zone Valves provide
airow adjustment in all rooms.
Z-Plus Indoor Unit modulates
ow to precisely match the
requirement for each room.
Z-Plus Touchscreen
Controller provides an
intuitive stylish interface.
Unit + Zone Control
Z-Plus
C-ZPLUS-MPM
C-ZPLUS-LCD

2
Publisher
Livezi
Phone 1300 306 125
Fax 07 3890 8734
Internet www.livezi.com.au
Email [email protected]
Revision 13.10
This Technical Manual describes the installation and commissioning of the Livezi Z-Plus concealed ducted
split air conditioner control systems.
Copyright
This publication is Copyright © 2013 Livezi. All rights reserved. No part of this publication may be repro-
duced, stored in any retrieval system or transmitted, in any form or by any means, electronic, mechanical,
photocopying, recording or otherwise, without the prior written permission of Livezi.
Disclaimer
Livezi reserves the right to make changes and improvements to any of the products described in this docu-
ment without prior notice. Under no circumstances shall Livezi be responsible for any loss of income or any
special, incidental, consequential or indirect damages howsoever caused.
Warranty
The contents of this document are provided “as is”. Except as required by applicable law, no warranties of
any kind, either express or implied, including, but not limited to, the implied warranties of merchantability
-
ment. Livezi reserves the right to revise this document or withdraw it at any time without prior notice.
Sourcing
Proudly designed and manufactured in Australia by Livezi, an independent Australian-owned company.

3
Contents
1 Installation Guidelines .......................................................................5
2 System Overview ..............................................................................5
3 Control System ..................................................................................6
3.1 Z-Plus System Overview ................................................................ 6
3.1.1 Z-Plus Main Processing Module ..............................................................................6
3.1.2 Z-Plus Touchscreen Controller ...............................................................................6
3.1.3 Z-Plus Touchpad Expansion Module .......................................................................6
3.2 Livezi Z-Plus Component Positioning ................................................ 7
3.2.1 MPM DIP Switch Functions ....................................................................................8
3.2.2 Motorised Dampers ..............................................................................................8
3.3 Control Wiring ............................................................................. 8
4 Pre-Commissioning Check List ...........................................................9
5 Commissioning ................................................................................ 10
5.1 Before connecting power ..................................................................... 10
.................................................................... 10
5.3 Initial Power Check ............................................................................. 10
.......................................................................... 10
5.4.1 Set Present Zones ..............................................................................................11
5.4.2 Set Motor Time ..................................................................................................11
5.4.3 Set Maximum Capacity ........................................................................................11
............................................................................................11
5.4.5 Calibrate Touch ..................................................................................................11
.......................................................................................11
..............................................................................................12
5.5 Damper Motor Check .........................................................................13
5.6 Name The Zone ................................................................................. 13
...................................................................... 13
6 Z-Plus Operating Instructions (Zone Menu) ........................................ 14
6.1 Selecting the operating mode ..............................................................................14
6.2 Turning zones On or Off ......................................................................................14
..........................................................................14

4
7 Z-Plus Operating Instructions (unit menu) ......................................... 15
7.1 Turning the unit On or Off ...................................................................................15
7.2 Selecting the Conditioning mode .........................................................................15
7.3 Selecting the Fan mode ......................................................................................15
7.4 Adjusting the Target (setpoint) temperature .........................................................15
7.5 Setting a Timer Program .....................................................................................16
7.6 Setting the Time and Date ..................................................................................16
7.7 Holiday / Away setting ........................................................................................16
8 Z-Plus Connection Diagram .............................................................. 17
Appendix A: Troubleshooting ............................................................. 18
A1. Self Diagnostics / Fault Detection ......................................................... 18
A2. Diagnostic Menu ................................................................................. 19

5
1 InstallatIon GuIdelInes
The following guidelines are intended for the installation of Livezi Digital and Inverter air
trade personnel should carry out installations of Split or Package air conditioning systems.
Full compliance with the local codes and regulations, which govern the installation of the
equipment, is the responsibility of the installer.
Before installation, the electrical power should be checked to determine if adequate power is
available with correct voltage to the site. The position of the equipment, after a survey of the
building and the duct layout, should meet the following criteria.
1.1 Electrical
All wiring by the installer must comply with local Energy Authority wiring rules. To make
the correct connection a 240V 50Hz supply must be available in the case of single-phase
units and a 415V 50Hz supply must be available in the case of three phase units.
During transportation the unit’s electrical connections may become loose, therefore it is
the installer’s / electrician’s responsibility to make sure that all electrical connections are
secure or warranty will be void.
Field or installation wiring must be connected as per the connection diagram to ensure the
unit performs as it is designed (Refer to Appendix A).
be calibrated or set to the maximum amp draw on the rating plate of the motor it is
controlling.
2 system overvIew
Livezi Z-Plus provides a central control point from which system capacity can be adjusted in up
to eight individual zones (rooms). Like most residentially orientated concealed split ducted air
conditioning control products, the Z-Plus provides four main system modes (Cooling, Heating,
narrow range of fan speeds as the return air temperature approaches the target temperature
requirement of individual rooms.
controller. The aggregated value is then passed through to the supply air fan controller, and
is to allow localised adjustment of system capacity based on comfort; avoiding the shortfall
apparent on the day of commissioning.

6
3 Control system
The air conditioning plant and control system contain no user serviceable parts. Installation,
technician.
cause serious injury or death.
3.1 Z-Plus System Overview
Livezi Z-Plus provides an unprecedented level of capacity adjustment at each zone. Livezi
Radical Flow, Digital Inverter and Dual Inverter systems automatically adjust refrigerant mass
3.1.1 Z-Plus Main Processing Module
The Z-Plus MPM provides unit support and the ability to control up to eight zones. Two
touchpad ports are provided.
3.1.2 Z-Plus Touchscreen Controller
Livezi Z-Plus utilises a mixture of hard and soft buttons to provide control over the air-
conditioning plant and individual zones.
3.1.3 Z-Plus Touchpad Expansion Module
Livezi Z-Plus can have limitless touchpads connected through the use of touchpad expansion
input. Touchpad sensors are disabled when expansion is used. Care should be taken not to

7
3.2 Livezi Z-Plus Component Positioning
The Livezi Z-Plus control system is a unit control and zone positioning system with a 24 volt AC
supply.
The Livezi Z-Plus Main Processing Module (3) provides a central connection point for the air-
conditioner, zone dampers and user touchpads. The Z-Plus is factory set to take corrective
action based on the return air temperature. The sensor location can be altered to use the
touchpad sensor or an average of any connected sensors. The touchscreen controller (5)
provides the user interface. From the touchscreen controller all system parameters can be
adjusted. The zone dampers (4) can be adjusted to meet the demands of the room. Unlike
the touchpad (5). The air conditioning plant (1) & (2) is connected to the MPM (3).
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
SET
MODE
ZONE
CLOCK
Active:5
Cooling:
4
5
2
3
1
Figure 3.2

8
3.2.1 MPM DIP Switch Functions
The MPM DIP switch defaults are suitable for the majority of installations. On occasion it may
assist the operation of the system to activate some or all of the additional functionality built in
to the DIP selection. The table below details the effect each combination of DIP positions will
have on system performance.
Z-Plus MPM DIP switch functions
Function Description
DIP switch position
1234
Factory
Default
Eight zone with the return air as the
sensor location. OFF OFF OFF OFF
Touchpad 1
Sensor Point
System will cycle based on the temperature
at the touchpad 1 location. ON OFF OFF OFF
Touchpad 2
Sensor Point
System will cycle based on the temperature
at the touchpad 2 location. OFF ON OFF OFF
Sensor
Averaging
System will cycle based on an average of
both touchpad sensors . ON ON OFF OFF
Sensor
Averaging
System will cycle based on all available
sensors. ON ON ON OFF
Zone 1 link
exclusively on the touchpad 1 sensor. OFF OFF OFF ON
Z-Plus MPM DIP switch functions
Function Description
DIP switch position
5678
Zone 1 Mimic System will be capped at 7 zones with the
eighth output set to mimic output 1. OFF OFF OFF ON
3.2.2 Motorised Dampers
The motorised barrel dampers must all have the same motor type,
3.3 Control Wiring
All control wiring to touchpads and motors is by RJ12 type connectors, with the exception
of the 24 VAC supply to the Livezi Connect main modules.
Data cables are to be kept the maximum practical distance from any LV power supply
Maximum cable length is not to exceed 50 m.
Suggested cabling: Livezi supplies and recommends the following cable:

9
4 Pre-CommIssIonInG CheCk lIst
Electrical
All electrical connections are secure.
Correct phase is connected to the unit.
Fuse or circuit breaker is of the correct rating.
All wires are terminated.
Correct power supply is connected to the unit.
Unit is drawing correct amps.
Outdoor Unit
Condenser fan is discharging air.
All cabinet panels are securely fastened
Indoor Unit
The unit is inclined to the drain outlet (12 mm fall is best).
Condensate lines are properly trapped.
The unit is slung or mounted on suitable anti-vibration devices.
The unit is delivering correct air quantity.
Refrigerant Lines
No leaks.
Both lines are insulated.
Properly supported.
Free of kinks or dents.
Ductwork
Free from leaks.
Filters are cleaned and in place.
Outlets are open.

10
5 CommIssIonInG
INSTALLER TIP: Make up a short cable and perform steps 5.1 to 5.5 with the LCD touchpad
in the ceiling space next to the main modules.
5.1 Before Connecting System Power Supply
1. Ensure that all modules are correctly mounted and the power supply is connected
properly.
2. Ensure that all touchpads and motors are connected as per the connection diagram
supplied.
DO NOT CONNECT Z-PLUS TOUCHSCREEN TO MOTOR OUTPUTS.
3.
1. Additional features can be enabled by setting the 8 way DIP switch at the Z-Plus MPM.
DIP selection table appears in section 3.2.3.
5.3 Initial Power Check
the fully open position, then all dampers will drive to the appropriate position as dictated by
the zone status and set parameters.
1. Connect the 24 VAC power supply to the MyZone system.
2. Check the main modules for fault LEDs (any red LED indicates an excess current fault
on the output - generally a cable short).
correctly with the motors supplied, and that the system safety mechanisms are operating as
button for 10 seconds in the global screen.
Press and hold
the bottom hard
button to access
Screen
Cfg
A/C
Mon
08.23 pm
5
On
Off
4: Zone 4 ...
On
Off
3: Zone 3 ...
On
Off
2: Zone 2 ...
On
Off
1: Zone 1 ...
Cfg
A/C
Mon
08.23 pm
5
On
Off
4: Zone 4 ...
On
Off
3: Zone 3 ...
On
Off
2: Zone 2 ...
On
Off
1: Zone 1 ...

11
5.4.1 Set Present Zones
Z-Plus Touch can adjust its display so that only present zones appear. Press the + or - soft
keys until the appropriate number of zones is displayed.
5.4.2 Set Motor Time
Z-Plus Touch utilises a time proportional damper positioning algorithm. For the system to
function correctly all zone damper motors must be the same type.
Livezi offers 2 motors with different drive speeds for use with Z-Plus:
The Livezi motors require the motor drive time to be set to 16 seconds (default).
button until the correct motor type is displayed.
5.4.3 Maximum Capacity
Z-Plus provides an ability to adjust the peak system capacity to match perfectly the peak load.
Most residential systems are sized on the peak cooling daytime load. If the standard sizing
calculation has been used, set the Maximum Capacity to equal the area used in the capacity
calculation.
Z-Plus includes the ability to group zones together so they can be controlled simultaneously.
The favourites will appear at the end of the zone names and include individual time clock
the top of the screen the Favourites name will be displayed (default is Fav a ~ Fav d). Group
zones by pressing the button beside each zone name.
5.4.5 Calibrate Touch
Z-Plus Touch utilises a four wire touchscreen. After extended use it may be necessary to re-
calibrate the display. Calibration is completed in the factory before shipping so this process
does not form part of the system commissioning procedure. If calibration is necessary activate
5.4.6 Service Timer
Z-Plus Touch incorporates a service timer that logs the run time of the indoor fan. Programmed
maintenance is required to satisfy the warranty coverage conditions and the Service Timer is
an excellent way of scheduling programmed maintenance. A custom contact number can be
added so that when a service is required the contact details are available to the home owner.

12
1. Select the target zone from the global screen.
2. Press the zone name to access the zone positioning screen.
3.
4. Use the + or - soft keys to adjust the Min, Max and Room Size settings for the zone.
5. Press Done to save and exit.
The Min and Max
ON. If the zone is OFF the damper is fully closed.
The Zone SQM
capacity required calculations.
Zone Adjust Screen
Press the
zone name
to access the
Zone Adjust
Screen
Push and hold
bottom hard
button for 10
seconds to
access the
Screen
Cfg
A/C
Mon
08.23 pm
5
On
Off
4: Zone 4 ...
On
Off
3: Zone 3 ...
On
Off
2: Zone 2 ...
On
Off
1: Zone 1 ...
Global Zone Adjust
Cfg
Pgm
Done
Down
100%
Up
On
Off
1: Zone 1 ...
Cfg
Pgm
Done
Down
100%
Up
On
Off
1: Zone 1 ...

13
5.5 Damper Motor Check
1. Select the appropriate zone and turn the zone off (Make sure that the zone drives to
the off position).
2.
damper drives to the on position)
3.
damper drives to the half way position).
4. Repeat this for each zone.
5. Advanced settings are available by pressing and holding the bottom hard key when
in the Zone Position adjust screen. Damper working range and zone size can be set
trained professional).
5.6 Name the Zones
1. On the Zone Adjust Screen, press and hold the top hard button to change to the Zone
Name Edit Screen.
2. Use the del soft key to remove current zone name and use the keyboard to rename
the zone. The A<- and ->Z soft keys page between the screens to access the full
range of alpha numeric characters.
3. Press done to save and exit.
4. Repeat for all zones.
A minimum of one Z-Plus Touch is required to be connected to the Z-Plus MPM. Care should be
taken to select the appropriate port if the internal sensor is required. Sensor allocation via DIP
selection (see table 3.2.1).
Push and hold
the top hard
button to access
the Zone Name
Edit Screen
Cfg
Pgm
Done
Down
100%
Up
On
Off
1: Zone 1 ...
Zone Adjust Screen Zone Rename Screen

14
6 Z-Plus touCh Zone oPeratIon
6.1 Selecting the operating mode
The Z-Plus Touch system has two operating modes.
Unit Control - Unit target temperature, fan speed and heat/cool mode.
6.2 Turning zones On or Off
1. Press the hardware button adjacent the zone name to toggle the zone from ON to
OFF.
2. Press the hardware button at the bottom of the controller to toggle between zones
1-4 , 5-8 and Favourites.
1. Select the target zone.
2. Press the zone name to access the Zone Adjust Screen.
3. Use the Up or Down soft keys to adjust the target position.
4. Press Done to save and exit.
Zone position range is limited by the Min and Max parameters (see 5.4.7).
Min parameter.
Max parameter.
Press the
zone name
to access the
Zone Adjust
Screen
Cfg
A/C
Mon
08.23 pm
5
On
Off
4: Zone 4 ...
On
Off
3: Zone 3 ...
On
Off
2: Zone 2 ...
On
Off
1: Zone 1 ...
Global Screen Zone Adjust
Cfg
Pgm
Done
Down
100%
Up
On
Off
1: Zone 1 ...

15
7 Z-Plus touCh Plant Control oPeratIon
Press the A/C soft key on the bottom right of the global screen next to the clock, to access
the plant control screen.
7.1 Turning the unit On or Off
1. Press the soft key in the top left hand corner of the display and the unit state will
toggle between ON and OFF.
7.2 Changing the unit operating mode
1. Press the soft key in the top centre of the display and the unit operating mode will
toggle between Vent, Cool, Heat and Auto.
7.3 Changing the fan speed
1. Press the soft key in the top right hand corner of the display and the fan speed will
toggle between High, Medium, Low and Auto.
7.4 Adjusting the target temperature
1. Use the + and - soft keys to adjust the desired target temperature. The actual
temperature is displayed below the target in brackets.
Cfg
A/C
Mon
08.23 pm
5
On
Off
4: Zone 4 ...
On
Off
3: Zone 3 ...
On
Off
2: Zone 2 ...
On
Off
1: Zone 1 ...
Plant Control Screen
Global Screen
Press A/C
to access
System
Screen

16
Plant Control Screen
Press the “Plant
Timer Programme”
Button to access
System Timer Screen
System Timer Screen
7.5 Adjusting the system timeclock program
1. Press the Pgm soft key to enter the system timer screen.
2. Press the soft keys at the top of the displays to activate the days of the week the
timeclock should be active.
3. Use the +hh and +mm, and, -hh and -mm soft keys to adjust the Start and Finish
times.
116.50
73
1
1
of
Original Issue
C
A
B
Date
Modifications
Weight
Colour
Part No :
Scale
Sheet
Size
Drawn
Finish
Material
Product :-
Product & tooling design
Plastic Developments Pty Ltd
CEH
NTS
A.4
116.50
73
1
1
of
Original Issue
C
A
B
Date
Modifications
Weight
Colour
Part No :
Scale
Sheet
Size
Drawn
Finish
Material
Product :-
Product & tooling design
Plastic Developments Pty Ltd
CEH
NTS
A.4
7.6 Setting the time
1. Press the Livezi soft key on the home screen to enter the Real Time Clock screen.
2. Press the soft keys positioned above and below the time and date to select the
7.7 Holiday / Away setting
1. Press the RTC programs: Enabled soft key to disable all time based ON &
OFF events.
Plant Control Screen
Press the “Livezi”
soft Button to access
the Real Time Clock
Screen. Press the
“RTC: program
Enabled Button to
disable all time based
ON and OFF events.
System Timer Screen
116.50
73
1
1
of
Original Issue
C
A
B
Date
Modifications
Weight
Colour
Part No :
Scale
Sheet
Size
Drawn
Finish
Material
Product :-
Product & tooling design
Plastic Developments Pty Ltd
CEH
NTS
A.4
116.50
73
1
1
of
Original Issue
C
A
B
Date
Modifications
Weight
Colour
Part No :
Scale
Sheet
Size
Drawn
Finish
Material
Product :-
Product & tooling design
Plastic Developments Pty Ltd
CEH
NTS
A.4

17
Spill Zones
&
Plu
P
765
Zone Motors
4321
Zone Motors
www.metalflex.com.au
MPCBT8
Touchpads
24VAC Supply
AN
Clock Option
Fujitsu Bridge
MOTOR OUTPUTS MOTOR OUTPUTS
Cfg
A/C
Mon
08.23 pm
5
On
4: Zone 4 ...
On
3: Zone 3 ...
On
2: Zone 2 ...
On
1: Zone 1 ...
Cf
g
A/C
Mo
n
08.23
p
5
O
n
4: Z
o
n
e
O
n
3
: Z
o
n
e
O
n
2: Z
o
n
e
O
n
1: Z
o
n
e
Cfg
Pgm
Done
Down
100%
Up
On
1: Zone 1 ...
Cf
g
P
gm
Do
n
e
Dow
n
1
00
%
U
p
O
n
1: Z
o
n
e
ON
1 2 3 4 5 6 7 8
Included
Transformer
GPO
Zone 4
Damper
Zone 3
Damper
Zone 2
Damper
Zone 1
Damper
Zone 8
Damper
Zone 7
Damper
Zone 6
Damper
Zone 5
Damper
Connection to Unit
1300 306 125
www.livezi.com.au
CENTRAL Z
+
Z
L
Z
+
Z
+
om.au
R
A
L
Z
+
T
A
R
L
Z
+
m
u
1300 306 125
www.livezi.co
C
E
N
T
R
A
C
E
N
T
T
A
T
R
R
w
w
5
06
C
E
8 Z-Plus ConneCtIon dIaGram

18
aPPendIx a.1: troubleshootInG
D1. Digital Inverter System Self Diagnostics / Fault Detection
Livezi systems are able to detect a number of problems and display a fault message to aid in
troubleshooting.
Fault D1 - 3 Phase error Digital Outdoor
Line 1 = Fault D1:
Line 2 scrolls one of the following:
3 Phase, L2 & L3 lost
3 Phase, L2 lost
3 Phase, L3 lost
3 Phase, rotate L2 & L3
Line 1 = Fault D2:
Line 2 scrolls one of the following:
Outdoor coil sensor o
p
en circuit
Outdoor coil sensor short circuit
Indoor coil sensor o
p
en circuit
Indoor coil sensor short circuit
Fault D3 - High Pressure or Low pressure Fault
Line 2 scrolls one of the following:
HP com
p
ressor safet
y
LP com
p
ressor safet
y
HP/LP com
p
ressor safet
y
Fault D4 - Interconnect Indoor > Outdoor
Line 1 = Fault 4:
Line 2 scrolls one of the following:
AHU and Condenser Interconnect
Fault D5 - Contact Manufacturer
Line 1 = Fault 5:
Line 2 scrolls = Contact Manufacturer
Fault D6 - Contact Manufacturer
Line 1 = Fault 6:
Line 2 scrolls = Contact Manufacturer
Fault D7 - Zoning to Indoor Board Communications Lost
Line 1 = Fault D7:
Line 2 scrolls = AHU and Zoning interconnect
Fault D8 - Contact Manufacturer
Line 1 = Contact Manufacturer

19
aPPendIx a.2: troubleshootInG
D2. Dual Inverter System Self Diagnostics / Fault Detection
Livezi systems are able to detect a number of problems and display a fault message to aid in
troubleshooting.
Fault I1 - Indoor unit and outdoor unit not compatible
Line 1 = Fault I1:
Line 2 scrolls one of the following:
AHU and Condenser not compatible
Line 1 = Fault I2:
Line 2 scrolls one of the following:
Outdoor coil sensor o
p
en circuit
Outdoor coil sensor short circuit
Indoor coil sensor o
p
en circuit
Indoor coil sensor short circuit
Fault I3 - Contact Manufacturer
Line 2 scrolls one of the following:
Contact Manufacturer
Fault I4 - Interconnect Indoor > Outdoor
Line 1 = Fault 4:
Line 2 scrolls one of the following:
AHU and Condenser Interconnect
Fault I5 - Contact Manufacturer
Line 1 = Fault 5:
Line 2 scrolls = Contact Manufacturer
Fault I6 - Contact Manufacturer
Line 1 = Fault 6:
Line 2 scrolls = Contact Manufacturer
Fault I7 - Zoning to Indoor Board Communications Lost
Line 1 = Fault D7:
Line 2 scrolls = AHU and Zoning interconnect
Fault I8 - Contact Manufacturer
Line 1 = Contact Manufacturer

Livezi
Phone 1300 306 125
Fax 07 3890 8734
Email: [email protected]
Registration: www.livezisupport.com
This manual suits for next models
2
Table of contents
Other Livezi Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual