
16
VENT CONNECTIONS TO BLOWER ASSEMBLY
Figure 15 shows the optimal placement of the 2" to 3" or 3" to
4" reducer; however, the vent can be reduced at any point in the
vent system as long as the maximum and minimum vent length
requirements are met.
FIGURE 15.
VENTING AND INSTALLATION
Planthelayoutof the vent systemfromtheventtermination to thewater
heater considering all of the 90° and 45° elbows plus the number of
feet of pipe that would be needed to install the total vent system. The
water heater must be vented to the outdoors as described in these
instructions. DO NOT connect this water heater to an existing vent
or chimney. It must be vented separately from all other appliances.
The fittings, other than the supplied Vent Termination should be
equivalent to the following: PVC (Schedule 40, DWV,ASTM D-2665),
CPVC (Schedule 40, DWV, ASTM F-438), ABS (Schedule 40 DWV,
ASTM D-2661).
The cement used should be as recommended by the vent pipe
manufacturer. See the instructions on pages 18 and 19 for the proper
method of cutting and cementing the PVC pipe and fittings.
Theunit may beventedhorizontally throughawall orverticallythrough
the roof. Pipe runs must be adequately supported along both vertical
and horizontal runs as follows:
• For Schedule 40, 2" PVC,ABS vent pipe: Every 3 feet (0.9 m).
• For Schedule 40, 3" PVC,ABS vent pipe: Every 3.5 feet (1.1 m).
• For Schedule 40, 4" PVC,ABS vent pipe: Every 4 feet (1.2 m).
• For Schedule 40, 2" CPVC vent pipe: Every 5 feet (1.5 m).
• For Schedule 40, 3" CPVC vent pipe: Every 6 feet (1.8 m).
• For Schedule 40, 4" CPVC vent pipe: Every 6.5 feet (2.0 m).
It is imperative that the first hanger (or support) be located on the
horizontal run immediately adjacent to the first 90-degree elbow from
theverticalrise. Supportmethodused should isolatetheventpipefrom
thefloor joists orother structuralmembers to preventthe transmission
of noise and vibration. Do not support, pin, or otherwise secure the
venting system in a way that restricts the normal thermal expansion
and contraction of the chosen venting material.
If the water heater is being installed as a replacement for an existing
power vented heater in pre-existing venting, a through inspection of
theexisting venting system must beperformed priorto any installation
work. Verify that thecorrectmaterial asdetailedabove has beenused,
and that the minimum or maximum vent lengths and terminal location
asdetailed in this manual have been met. Carefullyinspect theentire
venting system for any signs of cracks or fractures, particularly at
the joints between elbows and other fittings and the straight runs of
vent pipe. Check the system for signs of sagging or other stresses
in the joints as a result of misalignment of any components in the
system. If any of these conditions are found, they must be corrected
in accordance with the venting instructions in this manual before
completing the installation and putting the water heater into service.
Except where instructed in this manual, the mixing of 2", 3" and 4"
vent pipe is NOTALLOWED. If 2" pipe is to be used, then a 2" to 3"
bell reducer is recommended. Figure 15 shows the recommended
location for the bell reducer. If the bell reducer is located at the
rubber boot on the blower assembly, then a short section of 3" vent
pipe needs to be installed in the rubber boot for proper connection of
the 2" to 3" bell reducer. That length can be of the minimum length
required for the connection.
If 4" pipe is to be used, then a 3" to 4" bell reducer is recommended.
Figure 15 shows the recommended location for the bell reducer. If
the bell reducer is located at the rubber boot on the blower assembly,
then a short section of 3" vent pipe needs to be installed in the rubber
boot for proper connection of the 3" to 4" bell reducer. That length
can be of the minimum length required for the connection.
The 40,000, 50,000, 55,000 and 62,500 BTU units are supplied with
a 2" Schedule 40 PVC 22.5° Vent Terminal. If you decide to vent with
3" or 4" pipe, a Schedule 40 DWV 45° Vent Terminal must be used.
For your convenience, we have included a screen for both 3" and 4"
Vent Terminals.
The vent piping should be connected to the blower with a rubber
adapter and secured with hose clamps. The adapter and clamps are
provided with the heater.
Even the flue gas temperature leaving the blower is between
140°F (69°C) and 175°F (79°C), some installations will have water
condensate in the vent piping. If this occurs, then adequate means
of draining and disposing of the condensate needs to be made by
the installer.
CONDENSATE
Condensateformation doesnotoccurinallinstallationsofpowervented
waterheaters, but shouldbeprotected againstoninstallations where it
canform in the venting system.Condensation in the venting systemof
powervented waterheaters isdependent uponinstallation conditions
including, but not limited to ambient temperature and humidity of
installationlocation,ambienttemperatureandhumidityofventingspace,
vent discharge and slope, and product usage. In certain conditions,
installationsinunconditionedspace or havinglonghorizontalor vertical
vent runs may accumulate condensate. In these conditions, the vent
pipe should be sloped downward away from the blower assembly
1/4"(6.4 mm)per fivefeet (1.5m) of pipe but not more than 1 1/2" (3.8
cm) in the total vent length. If the vent piping is vented level or sloped
upwards away from the blower assembly, then adequate means for
draining and disposing of the condensate needs to be made by the
installer (if condensate is detected). If you have condensate, then a
3/8"drain hose canbe connected tothe built-indrain port ofthe rubber
boot on the blower assembly. For your convenience, the rubber boot
is supplied with a removable cap on the built-in drain port. Prior to
operating the water heater, make sure the removable cap is installed
on the drain port (if a drain hose is not needed).