Lynx LOH36 User manual

Page 1 of 8 P/N 11857.00 Rev A
INSTALLATION INSTRUCTIONS
HOOD MODELS –LOH36, LOH48 & LOH60
IMPORTANT SAFETY INSTRUCTIONS
PLEASE READ ENTIRE INSTRUCTION BEFORE PROCEEDING.
INSTALLATIONS MUST COMPLY WITH ALL LOCAL CODES.
IMPORTANT: Save these Instructions for the Local Electrical Inspector's use.
INSTALLER: Please leave these Installation Instructions with this unit for owner.
OWNER: Please retain these Instructions for future reference
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, HOODS
SHOULD BE INSTALLED WITH VENTILATORS APPROVED FOR USE WITH THE HOOD. SEE TABLE –1 ON
THIS PAGE FOR APPROVED VENTILATORS.
WARNING - TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE
THE FOLLOWING:
A.Installation work and Electrical Wiring
Must Be Done By Qualified Person(s) In
Accordance With All Applicable Codes
& Standards. Including Fire-Rated
Construction. “WARNING” To Reduce
The Risk Of Fire, Use Only Metal Duct
Work.
B.Sufficient air is needed for proper
combustion and exhausting of gases
through the flue (chimney) of fuel
burning equipment to prevent
backdrafting. Follow the heating
equipment manufactures guideline and
safety standard such as those published
by the National Fire Protection
Association (NFPA) and the American
Societyfor Heating, Refrigeration and
Air Conditioning Engineers (ASHRAE),
and the local code authorities.
C.When cutting or drilling into wall or
ceiling, do not damage electrical wiring
and other hidden utilities.
D.Ducted fans must always be vented to the
outdoors.
E. Before Servicing or Cleaning Unit,
Switch Power off At Service Panel And
Lock Service Disconnecting Means to
Prevent Power From Being Switched On
Accidentally. When The Service
Disconnecting Means Cannot be Locked,
securely Fasten A Prominent Warning
Device, Such As A Tag, To The Service
Panel
CAUTION - TO REDUCE THE RISK OF FIRE AND TO PROPERLYEXHAUST AIR, BE SURE TO DUCT AIR
OUTSIDE FOR DUCTED FANS –DO NOT VENT EXHAUST AIR INTO SPACE WITHIN WALLS OR CEILING
OR INTO ATTICS, CRAWL SPACES OR GARAGES.
Read this instruction completely before starting installation. Planning the complete installation before starting any work is
highly recommended. This includes all aspects of the installation including hood location, ducting, electrical requirements, and
adequacy of mounting surfaces.
TABLE - 1
Model LOHI = Internal ventilator
Model LOHE = Remote ventilator
This hood series has been designed to be used with the ventilators shown in Table –1. Before
cutting into cabinets, it is necessary to confirm that the correct ventilator is being used. Your
dealer should have reviewed your needs prior to your purchase. Be sure you have the correct
ventilation system.
CAUTION: To Reduce The Risk Of Fire And Electrical Shock, Install This
Rangehood Only With Blowers Manufactured By Lynx Professional Grills.
DUCTING: Use a minimum 10" round duct for LOHI and LOHE installations. See Page –3. A standard starting transition
(33895) is included with the Hood.
SAFTY WARNING:
Turn off power circuit at the service entrance and lockout panel before wiring the range hood.
NOTE: Unit must be vented
to the outside of the building.

Page 2 of 8 P/N 11857.00 Rev A
BEFORE STARTING INSTALLATION, YOU MUST IDENTIFY THE VENTILATOR MODEL BEING USED AND
IF A TOP OR REAR EXHAUST IS TO BE USED.
Prepare cabinet and/or wall for mounting either top (Fig - 1)
or rear (Fig 6 & 7) exhaust. Use furring strips to level cabinet
mounting surface with any cabinet trims.
For knock out removal see Fig- B
Remove See
Ventilator Model Knock out # Transition # Fig
LOHI Top Exhaust 1 33895 1,2,3
LOHE Top Exhaust 1 33895 1,2,3
LOHI Rear Exhaust 2 33895 4,5,6,7
LOHE Rear Exhaust 2 33895 5,6,7
Break the metal webs by placing a screwdriver at one corner
of the plate and hitting screwdriver sharply with a hammer.
After breaking a second web the plate can be flexed to break
other webs.
Wear eye protection when using tools.
Caution: When knock outs are removed the edges willbe
sharp! Sharp Edges should be Filed or Covered with
Metal Tape.
Attach and secure the transition to the hood with #6x3/8 sheet
metal screws and tape all joints prior to installing the hood.
Attach hood to cabinet using #10 wood screws. Holes are
located in the back panel and top panel of the hood for
mounting. Use a minimum of four #10x3/4 wood screws to
mount the hood. Longer screws are required if wall board or
other nonstructural surfaces are used between the hood and
main mounting surface which should be a minimum of 3/4”
thick. When using rear holes for additional mounting use
appropriate anchors if not engaging the wood structure.
HINT: If you find vibration noise is present because of
cabinet structure use additional screws, in holes available, to
make the mounting more ridged.
Connect 120 volt, 60 Hz power through the conduit hole in
top of hood, connecting to pigtail in hood junction box, white
to white, black to black and connect green ground wire to the
power supply ground wire per local codes. See Fig –A.
NOTE: Recommended height over BBQ Grills = 36
inches.
Hood is recommended for use over domestic gas or electric
appliances. Not recommended for use over solid fuel fired
appliances.
After installing the hood, install the internal blower (Top
Exhaust See Fig 2; Rear Exhaust See Fig - 4) unit by
positioning the blower onto bracket-A, notched blower
bracket will center blower. Rotate into position against hood
and secure Bracket –B to Hood with #8 sheet metal screws.
If the remote ventilator is used see related instructions. The
LOHE ventilator will require revision of some wiring in the
hood receptacle box - See LOHE instructions.
NOTE: LOHE requires a dedicated 20 AMP Power
Supply. All other ventilators require a dedicated
15 AMP Power Supply
CAUTION: The hood is of sufficient weight that two
installers are recommended to prevent injury or damage to the
hood in handling.
Turn the power on at the service entrance and check the
operation of the controls.
NOTE: be sure that all dampers are operating properly and
are free to open.
Hood Top
Hood Wiring Access
Mounting Screw
Cover
Knock Outs
Remove Appropriate Knock Outs and Connect Wiring
According to Hood and Blower Installation Instructions.
CAUTION: Always Install Receptacle Box Cover.
RECEPTACLE BOX COVER
Fig –A
2
1
Fig - B

Page 3 of 8 P/N 11857.00 Rev A
Hood Width
4"
60"
48"
Wiring Access
5"
20-3/8
14-3/8
10-3/8
Dim "A"
"A" C
L Top Of Hood
3/4"
FIG - 6
Back Wall
12"
FIG - 5
36"
Bottom View Of Cabinet
HOOD MODELS LOHI
Internal Or Remote Blowers
REAR EXHAUST
C
L Of Hood
14-1/2"
7-1/4"
1-3/4"
10-1/2"
FIG - 7 Rear Exhaust
Center Of Round Duct Using
Transition
ACut Hole In Drywall
To Accept Transition # 33895
Top Of Hood
A
Width Of Hood
Rotate
Into
Position
& Secure
With 2 Screws
B
A
LOHI
Add Furring Strips To Provide An Even
Bottom Surface For The Hood Mounting
Transition
To 10" Duct
Or Wall Cap
Route To Outside
Secure Transition To Hood Using #6 x 3/8"
Sheet Metal Screws. Tape All Joints And Seams.
18"
7-1/8"
FIG - 4
4"
5" "A" C
L
7-1/8"
3/4"
FIG-1
Back Wall
10-1/4" 12"
FIG - 3
Bottom View Of Cabinet -
HOOD MODELS LOHI
Internal Or Remote Blowers
TOP EXHAUST
Air Flow
Remove Knock Out # 1
FIG-2 Secure Transition To Hood Using #6 X 3/8"
Sheet Metal Screws. Tape All Joint & Seams
Wiring Access
Rotate
Into
Position
& Secure
With 2 Screws
LOHI
Transition
To 10" Duct 12"
3"
All Hoods
30"
18"
10" Duct to
Discharge W/Roof Cap
Transition # 33895
Vertical Discharge
The 10" Discharge With Transition
Will Be On The Center Line Of Hood Width
And On Center Line of 12" Dimension.
10-3/8
14-3/8
20-3/8
Dim "A"
48"
60"
Hood Width
36"
Bottom Surface For The Hood Mounting
Add Furring Strips To Provide An Even
7-1/8"
Remove Knock Out # 2
W/Wall Cap - LOHC
Use # 33895
Use # 33895

Page 4 of 8 P/N 11857.00 Rev A
Outside Patio or Lanai Installation
Construction methods and installation shall comply with all local building codes. Internal
ducting shall be sealed using outdoor rated metal duct tape.
The LYNX hood with stainless steel canopy is approved for installation in an outside patio or lanai area if the area
is covered with a protective roof over the hood (wall style hoods are to be also mounted to a solid protective rear
wall) and installed with a GFCI protected branch circuit. Roof or Wall Caps are to be sealed to prevent moisture
migration to structure interior; use an outdoor rated sealant suitable for adhesion to the installation materials. See
Fig-8 for rear exhaust installation and Fig-9 for top exhaust installation.
A A B
Wall Cap
Rear
Exhaust
Fig - 8
Front View
A = 42" Minimum B = 30" Minimum
Side View
See Fig –10 for structure with elevated roof/ceiling.
The Roof shall cover the top of the hood and extend a minimum of 42” from each side of the hood and 30”
minimum from the outer most edges of the hood front.
Since, outdoor areas are subject to strong cross drafts it is recommended that the hood extend at least 3 –inches, and
preferably 6 –inches, over either side of the cooking area to maximize the cooking discharge capture area. Cross
drafts will affect the efficiency of the ventilation system and cooking discharge can escape capture by the
hood/ventilation system. Be sure to plan for adequate ventilator (blower) capacity to minimize cross drafts
influencing the removal of cooking discharges.

Page 5 of 8 P/N 11857.00 Rev A
The installation instruction that accompanies the hood shall be followed to ensure all safety Instructions and
guidelines are adhered to. NOTE: Hood is recommended for use over domestic gas or electric appliances. Not
recommended for use over solid fuel fired appliances. See Fig-10 for soffit construction
B = 30" MinimumA = 42" Minimum
Front View
A
Side View
Exhaust
Top
B
Soffit
Roof Cap
Fig - 9
A
12"
See Fig –10 for structure with elevated roof/ceiling.
For installations with elevated Roof/Ceiling use a Soffit, or optional stainless steel extension
B = 30" Minimum
Fig - 10
Exhaust
Side View
B
Top
Soffit
Fasten Wall Board
Fasten To Top
Panel To Underside
Of Top Flange
Of Hood
Canopy
Extension
Hood Widths 12"
4"MIN
Stainless Canopy Extension
Constructed Soffit
To Top Of Hood
Enclosed. Fasten
& Front Shall Be
Soffit Top, Sides
Soffit shall be constructed of materials suitable for outdoor installation and be sealed to prevent moisture migration
to structure interior.
Other manuals for LOH36
1
This manual suits for next models
2
Table of contents
Other Lynx Ventilation Hood manuals
Popular Ventilation Hood manuals by other brands

Gorenje
Gorenje S3 IHGC963S4X manual

KOBE
KOBE ISX2136SQB-1 Installation instructions and operation manual

U.S. Products
U.S. Products ADVANTAGE-100H Information & operating instructions

Kuppersberg
Kuppersberg DUDL 4 LX Technical Passport

Framtid
Framtid HW280 manual

Thermador
Thermador HGEW 36 FS installation manual