manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. AC Power Distribution
  8. •
  9. M-system W2DY User manual

M-system W2DY User manual

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5526 Rev.8 P. 1 / 3
INSTRUCTION MANUAL
CURRENT LOOP SUPPLY MODEL W2DY
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner (body + base socket).............................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES OR UK LEGISLATION
• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in
a panel system. The user may have to review the CE or
UKCA requirements in regard to the whole system and
employ additional protective measures* to ensure the CE
or UKCA conformity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 5 – 7VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V, approx. 3W
■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
• With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten ap-
propriate life duration.
COMPONENT IDENTIFICATION
Model
SPAN
ZERO
SPAN
ZERO
Fixing Screw
Zero Adj.
Span Adj.
Zero Adj.
Span Adj. Connection
Diagram
Specifications
Output 1
Output 2*
*Provided only for dual output.
Body Base Socket
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
W2DY
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5526 Rev.8 P. 2 / 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
4
8 7
10
21.5 (.87)
88.5 (3.48)
84 (3.31)10 (.39)
22 (.87)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
11
–
M3
SCREW
72 (2.83)
29.5 (1.16)
53 (2.09)
2
–
4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
11
56
123
9
6 (.23)
• When mounting, no extra space is needed between units.
4
(.16)
■CONNECTION DIAGRAM
U(+)
V(–)
POWER
10
11
+
–
OUTPUT 1
7
8
+
–
3
6
OUTPUT 2
4
+
–
+
–
2
5
1
2-WIRE
TRANSMITTER
–
+
MONITOR
(1 – 5V DC)
V
The section enclosed by broken line is only with 2nd output option.
W2DY
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5526 Rev.8 P. 3 / 3
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
5) Go through the same procedure for the Output 2.
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.

Other M-system AC Power Distribution manuals

M-system Sentronic Mini-M Series User manual

M-system

M-system Sentronic Mini-M Series User manual

M-system M6SBS Series User manual

M-system

M-system M6SBS Series User manual

Popular AC Power Distribution manuals by other brands

Ametek 251RP Series User and programming manual

Ametek

Ametek 251RP Series User and programming manual

Blue Horizon Proburn instructions

Blue Horizon

Blue Horizon Proburn instructions

Furman Merit Series owner's manual

Furman

Furman Merit Series owner's manual

ETA Systems ETA-C15D manual

ETA Systems

ETA Systems ETA-C15D manual

Furman SPR-20i owner's manual

Furman

Furman SPR-20i owner's manual

Furman AR-1230 owner's manual

Furman

Furman AR-1230 owner's manual

Daikin VRV Series Technical data

Daikin

Daikin VRV Series Technical data

Furman P-240 IT owner's manual

Furman

Furman P-240 IT owner's manual

Bodine Pacesetter 2995 Instructions for installation and operation

Bodine

Bodine Pacesetter 2995 Instructions for installation and operation

Kikusui PCR 500L Operation manual

Kikusui

Kikusui PCR 500L Operation manual

ETA Systems ETA-PD8LA quick start guide

ETA Systems

ETA Systems ETA-PD8LA quick start guide

Furman Prestige Series owner's manual

Furman

Furman Prestige Series owner's manual

Panamax M10-HT-PRO owner's manual

Panamax

Panamax M10-HT-PRO owner's manual

ETA Systems ETA-ECM20 Information sheet

ETA Systems

ETA Systems ETA-ECM20 Information sheet

Atlas ECS-204 owner's manual

Atlas

Atlas ECS-204 owner's manual

Citronic CPD-8C user manual

Citronic

Citronic CPD-8C user manual

Skyrc Ultimate Duo instruction manual

Skyrc

Skyrc Ultimate Duo instruction manual

Pacific Power Source ASX series Operation manual

Pacific Power Source

Pacific Power Source ASX series Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.