M-system M6DXAR User manual

MODEL: M6DXAR
Euro Terminal Ultra-Slim Signal Conditioners M6D Series
RTD ALARM
(PC programmable)
Functions & Features
• 5.9-mm wide ultra-slim design
• Low profile allows the M6D module mounted in a 120-mm
deep panel
• Provides a relay contact output at preset DC input levels
• PC programmable
• Linearization and upscale and downscale burnout
protection
• High-density mounting
• Power and status indicator LEDs
5.9 (.23)
94
(3.70)
102
(4.02)
mm (inch)
MODEL: M6DXAR–[1]–R
ORDERING INFORMATION
• Code number: M6DXAR-[1]-R
Specify a code from below for [1].
(e.g. M6DXAR-4-R)
• Temperature range (e.g. 0 – 100°C)
[1] INPUT RTD
1: JPt 100 (JIS'89)
(Usable range: -200 to +500°C, -328 to +932°F)
3: Pt 100 (JIS'89)
(Usable range: -200 to +650°C, -328 to +1202°F)
4: Pt 100 (JIS'97, IEC)
(Usable range: -200 to +850°C, -328 to +1562°F)
5: Pt 50 Ω (JIS'81)
(Usable range: -200 to +649 °C, -328 to +1200°F)
7: Pt 1000
(Usable range: -200 to +850°C, -328 to +1562°F)
9: Cu 10 @25°C
(Usable range: -50 to +250°C, -58 to +482°F)
0: Specify (Please provide a resistance table.)
(Configurator software is used to change the input type and
range. Input code 7: Pt 1000 cannot be switched to/from
other input types while its temperature range can be
changed.)
OUTPUT
Relay; SPDT or transfer contact
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
• PC configurator software (model: M6CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
GENERAL SPECIFICATIONS
Connection
Input and output: Euro terminal (torque 0.3 N·m)
Power input: Via the Installation Base (model: M6DBS)
or Euro terminal (torque 0.3 N·m)
Applicable wire size: 0.2 to 2.5 mm2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Burnout: Upscale standard; downscale or no burnout
optional by programming
In case of upscale standard, the alarm operates as if the
input signal has exceeded over the range.
Linearization: Standard
Power LED: Green light turns on when the power is supplied.
Status indicator LED: Orange LED; Flashing patterns
indicate different operating status of the transmitter.
Alarm monitor LED: Red LED turns on when the alarm is
tripped.
Programming: Downloaded from PC
Input type and range
Input fine adjustments
User’s RTD table (max. 300 points)
Burnout (Upscale, downscale or no burnout)
Alarm setpoint (input %)
Trip action (High or Low)
Relay coil (energized or de-energized)
Power ON delay time (0 to 999 sec.)
Alarm ON delay time (0 to 999 sec.)
Hysteresis (deadband) (input %)
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: M6DXAR
Alarm test, and others
Configurator connection: 2.5 dia. miniature jack;
RS-232C level
Factory default setting
Alarm setpoint: 80%
Trip action: High
Relay coil at alarm: Energized
Power ON delay time: 5 seconds
Alarm ON delay time: 0 seconds
Hysteresis (deadband): 1.0%
Burnout: Upscale
INPUT SPECIFICATIONS
INPUT: 2- or 3-wire RTD
Maximum leadwire resistance: 10 Ω per wire
Sensing current: ≤ 1.5 mA (≤ 0.15 mA for Pt 1000)
Minimum span: 20°C or 36°F
If not specified, the input range is 100°C.
OUTPUT SPECIFICATIONS
• RELAY OUTPUT
Relay rating:
250 V AC @2 A (cos ø = 1)
30 V DC @2 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @100 mA
Mechanical life: 5 × 106 cycles (rate 180/min.)
0 50 100
Input
(%) ▲
Setpoint
Output (3–4)ON (3–2)ON
• Setting Example
Hi alarm (coil energized at alarm) or
Lo alarm (coil de-energized at alarm)
Alarm Trip Operation
Terminal No. in parentheses
Trip operation in power failure: Terminals 3 – 4 turn ON.
INSTALLATION
Power consumption: Approx. 0.5 W
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6DBS) or DIN rail
Weight: 65 g (2.3 oz)
PERFORMANCE in percentage of span
Setpoint accuracy (trip point accuracy)
Pt and JPt: Whichever greater ±0.1 % of input range or
±0.15°C
Cu10: ±1°C
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: ≤ 1 sec. (0 – 100 % at 90 % setpoint)
Burnout response time: ≤ 1 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
CALCULATION EXAMPLES OF SETPOINT ACCURACY
[Example] Input type Pt 100, Input range 0 – 100°C
Setpoint accuracy *1 (0.15°C *2) / Span (100°C) × 100 %
*1. Calculate the accuracy in °C
*2. 100 °C × 0.1 % = 0.1 °C ≤ 0.15 °C. 0.15 °C is used as
input accuracy value.
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EN 61000-6-4 (EMI)
EN 61000-6-2 (EMS)
Low Voltage Directive (2006/95/EC)
EN 61010-1
Overvoltage Category II
Pollution Degree 2
Max. operating voltage 250 V (relay output circuit)
Input or power to output: Reinforced insulation
Input to power: Basic insulation
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: M6DXAR
EXTERNAL VIEW
(With the cover open)
Status Indicator LED
Configurator Jack
Power LED
Alarm Monitor LED
DIMENSIONS unit: mm (inch)
94 (3.70)
5.9 (.23)
DIN RAIL HOOK
102 (4.02)
[0.5 (.02)]
8–M3
EURO TERMINAL
DIN RAIL
35mm wide
5 6 7 8
1 2 3 4
• When mounting, no extra space is needed between units.
WIRE INSERTION ANGLE: approx. 7°
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: M6DXAR
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
7
8
2
4
3
NC
NO
COM
A
B
A
B
B
6
1
5
LOAD
Inductive
Load (Coil)
Varistor or CR Circuit
■ Relay Protection
• AC Powered • DC Powered
LOAD
Inductive
Load (Coil)
Diode, Varistor or
CR Circuit
Low Drift
Amplifier
STATUS
LED ALARM
MONITOR LED
POWER
+
–
Digital
Computation
Ry
JACK
CONFIGURATOR
RTD
2-wire 3-wire
OUTPUT
CONNECTOR
POWER
POWER LED
Specifications are subject to change without notice.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

M6DXAR
P. 1 / 4EM-7855
RTD ALARM
(PC programmable) MODEL M6DXAR
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner......................................................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
The M6DXAR is programmable using the PC Configurator
Software. For detailed information on the PC configuration,
refer to the M6CFG users manual. The M6CFG PC Con-
figurator Software is downloadable at M-System’s web site:
http://www.m-system.co.jp
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• The relay output circuit is suitable for use in Pollution De-
gree 2 environment in Overvoltage Category II with the
maximum operating voltage 250V.
Prior to installation, check that the insulation class of this
unit satisfies the system requirements.
• Altitude up to 2000 meters
•The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
■ POWER INPUT RATING & OPERATIONAL RANGE
Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 0.5W
■ GENERAL PRECAUTIONS
Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -20 to +55°C
(-4 to +131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

M6DXAR
P. 2 / 4EM-7855
INSTALLATION
Set the unit so that its DIN rail adapter is at the bottom.
■ MOUNTING THE UNIT ON A DIN RAIL
A) Hang the upper hook at the rear side of unit on the DIN
rail.
B) Push in the lower in keeping pressing the unit to the
DIN rail.
■ REMOVING THE UNIT
A) Pull down the DIN rail adaptor using a minus screw-
driver.
B) Pull out the lower part of the unit.
C) Remove the upper part from the DIN rail.
DIN Rail
AB
DIN Rail Adaptor A
B
C
COMPONENT IDENTIFICATION
Body
Front Cover
DIN Rail Adaptor
Spec. Marking
Status Indicator LED
Configurator Jack
Power LED
Alarm Monitor LED
■ FRONT VIEW (with the cover open)
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

M6DXAR
P. 3 / 4EM-7855
■ CONNECTION DIAGRAM
■ WIRING INSTRUCTIONS
• Applicable wire size
Solid: 0.2 to 2.5 mm2(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm2(Tinning wire ends may
cause contact failure and therefore is not
recommended.)
Ferruled: 0.2 to 1.5 mm2(0.55 to 1.35 dia.)
• Expose wire conductors by 8 mm (0.31”).
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■ EXTERNAL DIMENSIONS unit: mm (inch)
94 (3.70)
5.9 (.23)
DIN RAIL HOOK
102 (4.02)
[0.5 (.02)]
8–M3
EURO TERMINAL
DIN RAIL
35mm wide
5 6 7 8
1 2 3 4
• When mounting, no extra space is needed between units.
WIRE INSERTION ANGLE: approx. 7°
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
7
8
2
4
3
NC
NO
COM
A
B
A
B
B
6
1
5
RTD
2-wire 3-wire
CONFIGURATOR JACK
+
–
OUTPUT
POWER
8 mm 8 mm
3.7 mm dia.
max.
3.7 mm dia.
max.
Wire exposure Recommended
ferruled wire
How to Connect Wires
Insert a wire. Confirm that the wire tip hits the bottom and
tighten the screw with a screwdriver.
Confirm that the wire’s insulation tube is not caught in the
terminal.
Screwdriver
Wire
Screwdriver
Wire
8 mm
6 mm
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

M6DXAR
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7– 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
If the RTD or its extension wires are broken, the output
goes over 100% (below 0% with downscale protection)
due to the burnout function. Confirm the status indica-
tor LED pattern and check leadwires in such a case.
4) Alarm operations: Check the alarm operations referring
to the figure below.
5) Output load: Check that the output load is 250V AC/
500VA or 125V DC/60W. For maximum relay life with
inductive load, external protection is recommended.
LED FUNCTIONS
■ STATUS INDICATOR LED
The M6DXAR is provided with a status indicator LED
which flashes in different patterns indicating various op-
erating status.
The following figure indicates typical patterns.
■ ALARM MONITOR LED
The M6DXAR is provided with an alarm monitor LED
which flashes in different patterns indicating various alarm
status.
The following figure indicates typical patterns.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes.
• H Setpoint
Increase the input signal from a value lower than the set-
point and check that the relay trips at the H setpoint within
the setpoint accuracy described in the data sheet.
• L Setpoint
Decrease the input signal from a value higher than the set-
point and check that the relay trips at the L setpoint within
the setpoint accuracy described in the data sheet.
When the setpoints are shifted, recalibrate the unit using
the PC Configurator Software (model: M6CFG).
LIGHTNING SURGE PROTECTION
In order to protect the unit from lightning surges entering
through power supply cables, use of appropriate lightning
surge protectors are recommended. Please contact M-Sys-
tem.
0 50 100
Input
(%) ▲
Setpoint
Output (3–4)ON (3–2)ON
• Setting Example
Hi alarm (coil energized at alarm) or
Lo alarm (coil de-energized at alarm)
Alarm Trip Operation
Terminal No. in parentheses
Trip operation in power failure: Terminals 3 – 4 turn ON.
TRANSMITTER STATUS LED ON-OFF PATTERNS
Normal operating mode
Abnormal operating mode
Burnout mode
ON OFF
80 milliseconds
Power ON delay
ALARM STATUS
ON OFF
LED ON-OFF PATTERNS
Alarm ON delay
Alarm OFF
Alarm ON
160 millisec.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG
This manual suits for next models
3
Table of contents
Other M-system Industrial Electrical manuals
Popular Industrial Electrical manuals by other brands

Murata
Murata GJM0335C1E3R5BB01 Series Reference sheet

Murata
Murata GRM0225C1ER70WA03 Series Reference sheet

Hartmann
Hartmann T1HCK3F installation guide

Siemens
Siemens 3RK1901-1MX00 operating instructions

Murata
Murata GJM1555C1H8R5WB01 Series Reference sheet

Murata
Murata GJM1555C1H150GB01 Series Reference sheet

Murata
Murata GRM0335C1H4R7BA01 Series Reference sheet

Kilowatt Labs
Kilowatt Labs Sirius user manual

Rockwell Automation
Rockwell Automation Allen-Bradley 100-C60 quick start guide

Siemens
Siemens Gigaset S2 Professional operating instructions

Murata
Murata GRM0225C1E6R2BA03 Series Reference sheet

Murata
Murata GQM1555C2D130FB01 Series Reference sheet