TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
76 (2.99) dia. 40 (1.57)
52.5 (2.07)
1 (.04)
60.9 (2.40)
46 (1.81)
50 (1.97)
4–M3 (.12) TAP
6 (.24) deep
1 2 3 4
5 6
■CONNECTION DIAGRAM
+
–
INPUT
1
2
+
–
LOAD
6
5
OUTPUT
24V DC
4 – 20mA DC
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.6 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check current with an ammeter. Check that the
input current is within 0 – 100% of the full-scale.
3) Supply voltage for differential pressure transmitter:
Check that the voltage drop per loop during the use of
this unit is no more than 5V. Be sure to supply adequate
voltage using calculation based on the performance of the
differential pressure transmitter and the load applied.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following. Zero and Span adjustments are located behind
the top cover. Release the knurled knobs and open the cover.
1234
56
VR1 VR2
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 1% input and adjust output to 10% with
VR1.
2) SPAN: Apply 100% input and adjust output to 100% with
VR2.
3) Check ZERO adjustment again with 1% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 4%,
16%, 36%, 64% and 100% input signal. Check that the out-
put signal for the respective input signal is 0%, 20%, 40%,
60%, 80% and 100% in order, or remains within accuracy
described in the data sheet. When the output is out of toler-
ance, recalibrate the unit according to the “ADJUSTMENT
PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.