Maple Systems iR-ETN User manual

User Manual
iR-ETN User Manual
This guide walks through important information about iR-ETN.
AW-10101129_rev00_20220307

Table of Contents
1. Product Overview ...................................................................................................1
iR-ETN.............................................................................................................1
2. Specifications..........................................................................................................2
iR-ETN.............................................................................................................2
3. LED Indicators .........................................................................................................3
L.V LED............................................................................................................3
IO RUN/ERR LED.............................................................................................3
ENET RUN/ERR ...............................................................................................3
RJ45 ................................................................................................................4
4. RJ45 Interface .........................................................................................................4
5. Reset Button ...........................................................................................................4
6. IP Address Setup .....................................................................................................4
7. MODBUS Mapping..................................................................................................5
Bit Mapping....................................................................................................5
Register Mapping ...........................................................................................5
TCP/IP Register ...............................................................................................5
Device Information Register...........................................................................5
iBus Information Register...............................................................................6
Module Information Register.........................................................................6
Module Register.............................................................................................6
Product Code List ...........................................................................................7
Special Register ..............................................................................................7
Life Guarding Register ....................................................................................7
The Default Value...........................................................................................8
Device Error Code List ....................................................................................9
Reading and Writing iR-PU01-P Objects ........................................................9
iR-PU01-P NMT Control Address..................................................................10
8. In Modbus Mapping .............................................................................................11
iBus Information Register.............................................................................11
Digital Input Bit Mapping to Modbus ..........................................................12
Digital Output Bit Mapping to Modbus .......................................................12
Analog Input Mapping to Modbus...............................................................12
Analog Output Mapping to Modbus............................................................12
Module Register Mapping to Modbus.........................................................12
iR-PU01-P Variable Instance Mapping .........................................................13
9. EtherNet/IP Object ...............................................................................................15
Object List ....................................................................................................15

Identity Objects............................................................................................15
9.2.1 Service..........................................................................................15
9.2.2 Class Attributes ............................................................................15
9.2.3 Instance Attributes.......................................................................15
Message Router Object................................................................................16
9.3.1 Class Attributes & Instance Attributes .........................................16
Assembly Object ..........................................................................................16
Connection Manager Object........................................................................16
9.5.1 Class Attributes & Instance Attributes .........................................16
Ethernet Link Object ....................................................................................16
9.6.1 Services ........................................................................................16
9.6.2 Class Attributes ............................................................................16
9.6.3 Instance Attributes.......................................................................16
TCP/IP Interface Object ................................................................................17
9.7.1 Service..........................................................................................17
9.7.2 Class Attributes ............................................................................17
9.7.3 Instance Attributes.......................................................................17
9.7.4 Interface Status ............................................................................17
9.7.5 Configuration Control...................................................................18
Module Register object................................................................................18
9.8.1 Service..........................................................................................18
9.8.2 Class Attribute..............................................................................18
9.8.3 Instance Attributes.......................................................................18
iBus Object ...................................................................................................19
9.9.1 Services ........................................................................................19
9.9.2 Class Attribute..............................................................................19
9.9.3 Instance Attributes.......................................................................19
Axis Register Object .....................................................................................20
9.10.1 Services ........................................................................................20
9.10.2 Class Attributes ............................................................................20
9.10.3 Instance Attributes.......................................................................20
10. iBus Error Handling ...............................................................................................21
11. Power Consumption .............................................................................................22
12. Ethernet Cascading ...............................................................................................23
13. EasyRemoteIO.......................................................................................................23
14. Description File .....................................................................................................26
Weintek HMI Tag..........................................................................................26
EtherNet/IP EDS ...........................................................................................26

iR-ETN User Manual
1
1. Product Overview
a
Reset Button
e
Expansion Connector
b
Ethernet Port LAN 1
c
Ethernet Port LAN 2
d
Power Connector
英文版 簡中版 日文版
iR-ETN
a
b
c
d
81mm [3.19"]
e
109mm [4.29"]
81mm [3.19"]
e
109mm [4.29"]
27mm [1.06"]
a
b
c
d
81mm [3.19"]
e
109mm [4.29"]
英文版 簡中版 日文版
Front View Side View
27mm [1.06"]
a
b
c
d
] 81mm [3.19"]
e
109mm [4.29"]
27mm [1.06"]
a
b
c
d
81mm [3.19"]
e
109mm [4.29"]

iR-ETN User Manual
2
2. Specifications
iR-ETN
Communication Interface Specifications
Model
iR-ETN
Expansion I/O Module
Number of Bus Terminals
Depends on Power Consumption.
Max. allowable number of iR modules is 16.
Digital Input Point
Max. 256
Digital Output Point
Max. 128
Analog Input Channel
Max. 64
Analog Output Channel
Max. 64
Indicators
ENET ACK (Green)
Device Status Indicator
ENET ERR (Red)
Device Error Indicator
L.V (Red )
Low Voltage Status Indicator
IO RUN (Green)
Module Status Indicator
IO ERR (Red)
Module Error Indicator
Data Transfer Rate
10/100 Mbps
Data Transfer Medium
4 x 2 twisted pair copper cable; category 3 (10 Mbps), category 5 (100 Mbps)
Distance Between
Stations
100 m between hub/switch and Bus Coupler or between Bus Coupler and Bus Coupler
Protocol
Modbus TCP/IP
EtherNet/IP Adapter
Max. Number of TCP/IP
Connections
8
Topology
line or star wiring
Network to Logic Power
Isolation
Yes
General Specification
Power
Power Supply
24 VDC (-15%/+20%)
Power Dissipation
Nominal 100mA @ 24VDC
Current for Internal Bus
Max 2A @ 5VDC
Current Consumption
220mA @ 5VDC
Electrical Isolation
Logic to Field Power Isolation: Yes
Back-up Fuse
≤ 1.6A Self-recovery
Specification
PCB Coating
Yes
Enclosure
Plastic
Dimensions WxHxD
27 x 109 x 81 mm
Weight
Approx. 0.15 kg
Mount
35mm DIN rail mounting
Environment
Protection Structure
IP20
Storage Temperature
-20°~ 70°C (-4°~ 158°F)
Operating Temperature
0°~ 55°C (32°~ 131°F)
Relative Humidity
10% ~ 90% (non-condensing)
Certification
EMC Immunity
Conforms to
EN 55032: 2012+AC: 2013, Class A
EN 61000-6-4: 2007+A1:2011
EN 55024: 2010+A1: 2015
EN 61000-6-2:2005

iR-ETN User Manual
3
3. LED Indicators
L.V LED
L.V LED state
Description
OFF
24V power normal
Blinking
Detect 24V power
ON
24V power error
*iR-ETN40R does not have L.V. LED.
IO RUN/ERR LED
RUN LED
ERR LED
Description
OFF
OFF
Power off or no power
Blinking
OFF
IO initiating
Blinking
ON
IO initiation error
ON
OFF
IO working
ON
Blinking
IO module alarm
ON
ON
IO communication fault
Blinking
Blinking
Exceeding power limit or too many modules
ENET RUN/ERR
Run LED
Err LED
Description
Modbus TCP
EtherNet/IP
OFF
OFF
Power off or no power
Blinking
OFF
Communicating
Pre-operational mode
ON
OFF
The device is in the OPERATIONAL state
OFF
ON
Hardware error,
communication fault
24V power error or
hardware error,
communication fault
ON
Blinking
Reset button is triggered
Reset button is triggered or
a recoverable error has
occurred
ENET Run/ERR indicator can be set to Modbus TCP mode (default) or EtherNet/IP
mode. The communication address for Modbus TCP mode is 1013 (0x03F5 in Hex).
Communication mode setting: In “Config Data”set 0 to use Modbus TCP mode and 1
to use EtherNet/IP mode.

iR-ETN User Manual
4
RJ45
Speed LED
OFF
Operating as a 10-Mbps connection
Green ON
Operating as a 100-Mbps connection
LINK /ACT LED
OFF
No communication
Orange
Blinking
There is activity on this port
4. RJ45 Interface
RJ-45
Signal Name
Descriptions
1
TD+
Transmit +
2
TD-
Transmit +
3
RD+
Receive +
4
****
5
****
6
RD-
Receive -
7
****
8
****
Case
Shield
5. Reset Button
Press and hold the reset button for more than 2 seconds after the unit starts running
properly, and wait until ENET ERR LED blinks. The default parameters are shown
below, the settings will take effect after cold reset.
Item
Description
Default
1
IP Address
192.168.0.212
2
Netmask
255.255.255.0
6. IP Address Setup
Network parameters can be configured using EasyRemote IO, and factory defaults
can be restored by pressing the Reset Button. Please see Chapter 13 in this user
manual for more information.
Item
Description
Default
1
IP Address
192.168.0.212
2
Netmask
255.255.255.0

iR-ETN User Manual
5
7. MODBUS Mapping
Bit Mapping
Parameter
Start address
Read/Write
Function Code
Dec
Hex
Digital Input
0~511
0000~
01FF
Read
2
Digital Output
0~511
0000~
01FF
Read
1
Write
5,15
Register Mapping
Parameter
Start address
Read/Write
Function Code
Dec
Hex
Analog Input
0~255
0000~
00FF
Read
3,4,23
Analog Output
256~511
0100~
01FF
Read
3,23
Write
6,16,23
Digital Input
800~863
0320~
035F
Read
3,23
Digital Output
864~927
0360~
039F
Read
3,23
Write
6,16,23
Registers
----------
Read
3,4,23
---------
Write
6,16,23
TCP/IP Register
Address
Read/Write
Data Size
Description
Dec
Hex
1000
03E8
Read
3word
(MAC-address).Ethernet physical address
If 00-0C-26-01-02-03, then 0x000C, 0x2601, 0x0203.
1003
03EB
Read/Write
2word
IP address
if 192.168.0.212, then 0xC0A8, 0x00D4.
1005
03ED
Read/Write
2word
subnet mask
if 255.255.255.0, then 0xFFFF, 0xFF00
1011
03F3
Read
1word
Number of TCP/IP connections
*TCP/IP Register Settings will take effect after cold reset or after giving Device Reset
Warm command.
Device Information Register
Address
Read/Write
Data size
Description
Dec
Hex
3000
0BB8
Read
4word
Vendor name string 8 char: “weintek” (ASCII)
3004
0BBC
Read
1word
Product Code of
iR-ETN: 0x0702
iR-ETN40R: 0x0A73
3005
0BBD
Read
1word
Firmware revision V1.23.4, 0x1234
3006
0BBE
Read
1word
Hardware revision V1.23.4, 0x1234

iR-ETN User Manual
6
3007
0BBF
Read
1word
Power consumption unit mW
3008-
3023
0BC0-
0BCF
R/W
16word
Product name, default:
iR-ETN : “iR-ETN” (ASCII)
iBus Information Register
Address
Read/Write
Data size
Description
Dec
Hex
10000
2710
Read
1word
Slot 0 iR-ETN Product code
10001
2711
Read
1word
Slot 1 Module Product code
10001~
10016
2712~
2720
Read
1word
Slot 2~Slot 16 Module Product code
10033
2731
Read
1word
Number of modules
10035
2733
Read
1word
Number of points of Digital Input
10036
2734
Read
1word
Number of points Digital Output
10037
2735
Read
1word
Number of Analog channels of Input register
10038
2736
Read
1word
Number of Analog channels of Output register
10045
273D
Read/Write
1word
0: ibus stops when one of the modules is disconnected.
1: ibus continues running when one of the modules is
disconnected.
Module Information Register
The data size of the information register of each module is 100word. If the first
module starts from address 30000 to 30099, then the second module starts from
address 30100 to 30199, and so on.
Address
Read/Write
Data size
Description
Dec
Hex
30000
~30099
7530~
7594
Read
100word
Module information of Slot 1
30100
~31599
7535~
7B6F
Read
100word
Module information of Slot 2~16
Ex: Module information of slot 1
Address
Read/Write
Data size
Description
Dec
Hex
30000
7530
Read
1word
Module product code, please see Product Code
List.
30001
7531
Read
1word
Module firmware version V1.23.4, value 0x1234
30002
7532
Read
1word
Module hardware version V1.23.4, value 0x1234
30003
7533
Read
1word
Power consumption unit mW
30038
7556
Read
1word
Number of points of Digital Input
30039
7557
Read
1word
Number of points Digital Output
30040
7558
Read
1word
Number of Analog channels of module
30041
7559
Read
1word
Number of Analog channels of module
Module Register
Each module has its own parameters; please see the corresponding manual of the

iR-ETN User Manual
7
module used. The maximum total data size of the registers is 500word. If the first
module starts from address 20000 to 20499, then the second module starts from
address 20500 to 20999, and so on.
Address
Read/Write
Data size
Description
Dec
Hex
20000
~20499
4E20~
5013
Read
500word
Module information of Slot 1
20500
~27999
5014~
6D5F
Read
500word
Module information of Slot 2~16
Product Code List
Item
Product
Code
1
iR-DI16-K
0154h
2
iR-DM16-P
0351h
3
iR-DQ16-P
0251h
4
iR-DM16-N
0352h
5
iR-DQ16-N
0252h
6
iR-DQ08-R
0243h
7
iR-AQ04-VI
0525h
8
iR-AI04-VI
0425h
9
iR-AM06-VI
0635h
10
iR-AI04-TR
0426h
11
iR-ETN
0702h
12
iR-ETN40R
0A73h
Special Register
Address
Read/Write
Data size
Description
Dec
Hex
1013
03F5
Read/Write
1word
Indicator Mode:
0: Modbus TCP
1: EtherNet IP
5000
1388
Read
1word
Device Error code
5001
1389
Read
1word
Reserved
5002
138A
Read
1word
Slot1~16 of Module disconnect
5100~
5612
13EC~
15EC
Read/Write
512word
Setting the time filter (digital input, unit: ms). The
time filter is disabled when it is set to less than 5ms.
The time filter remains at 1000ms when it is set to
longer than 1000ms. (digital input 0-511)
6000
1770
Write
1word
Device Command
0x5269:Reset iBus
0x5250:Parameter to default without TCP/IP
0x5257:Device Reset Warm
Life Guarding Register
If the communication was missing for longer than the Life Guarding Time, a Life
Guard Event is indicated. The output behavior is determined by whether Error Mode

iR-ETN User Manual
8
is enabled or disabled. Enabling Error Mode will output an Error Value when an event
occurs. Disabling Error Mode will keep the last value (for both digital and analog).
Address
Read/Write
Data size
Description
Dec
Hex
6100
17D4
Read/Write
1word
Life Guarding Time, unit: ms, 0: Disabled
6101
17D5
Read/Write
1word
Digital Output Error Mode (bit15-0)
0:Keep last value
1:Error value
6102
17D6
Read/Write
1word
Digital Output Error Mode (bit31-16)
…..
…..
…..
…..
…..
6132
17F4
Read/Write
1word
Digital Output Error Mode (bit511-495)
6133
17F5
Read/Write
1word
Digital Output Error Value (bit15-0)
0: Off
1: On
6134
17F6
Read/Write
1word
Digital Output Error Value (bit31-16)
…..
…..
…..
…..
…..
6164
1814
Read/Write
1word
Digital Output Error Value (bit511-495)
6165
1815
Read/Write
1word
Analog Output Error Mode
(channel 15-0)
0:Keep last value
1:Error value
6166
1816
Read/Write
1word
Analog Output Error Mode
(channel 31-16)
6167
1817
Read/Write
1word
Analog Output Error Mode
(channel 47-32)
6168
1818
Read/Write
1word
Analog Output Error Mode
(channel 63-48)
6169~
6232
1819~
1858
Read/Write
64word
Analog Output Error Value
(channel 63-0)
-32768~32768
The Default Value
Address
Read/Write
Data size
Description
Default
Dec
Hex
3008-
3023
0BC0-
0BCF
Read/Write
16word
Product name
“iR-ETN”or
“iR-ETN40R”
5100~
5612
13EC~
15EC
Read/Write
512word
Setting the time filter
(Digital input 0-511)
0
6100
17D4
Read/Write
1word
Life Guarding Time
0
6101-
6132
17D4-
17F4
Read/Write
32 word
Digital Output Error Mode
0xFF
6133-
6164
17F5-
1814
Read/Write
32 word
Digital Output Error Value
0
6165-
6168
1815-
1818
Read/Write
4word
Analog Output Error Mode
0xFF
6169-
6232
1819~
1858
Read/Write
64word
Analog Output Error Value
0
※After pressing [Reset] button, the Default Value will be filled into corresponding
registers.

iR-ETN User Manual
9
Device Error Code List
Refer to special register address 5000/1388H
Bit Number
Description
Bit0
Low power alarm
Bit1
iBus initialization fault
Bit2
Hardware error
Bit3
Module lost connection
Bit4
Module alarm
Bit5
Number of iBus exceeds 16
Bit6
Power consumption exceeded at iBus system
Bit7~15
Reserved
Reading and Writing iR-PU01-P Objects
Please see iR-PU01-P user manual for more information on index, sub-index, and
length.
R/W
Address
(Hex)
Description
Write
Object
0xFFF0
Index
0xFFF1
Sub-index (High Byte)
Length (Low Byte)
0xFFF2
Hi Byte
0x56
WORD
DWORD
Lo Byte
0x78
BYTE
0xFFF3
Hi Byte
0x12
Lo Byte
0x34
Sequentially writes data into 0xFFF0~0xFFF3. Data will be sent to iR-PU01-P when written
into 0xFFF3.
Read
Object
0xFFF4
Index
0xFFF5
Sub-index (High Byte)
Length (Low Byte)
0xFFF6
Hi Byte
0x56
WORD
DWORD
Lo Byte
0x78
BYTE
0xFFF7
Hi Byte
0x12
Lo Byte
0x34
Step1: Sequentially writes data into 0xFFF4~0xFFF5. Reading iR-PU01-P object starts when
data is written into 0xFFF5, and the data will be placed in 0xFFF6~0xFFF7.
Step 2: Read data of 0xFFF6~0xFFF7 Object.

iR-ETN User Manual
10
iR-PU01-P NMT Control Address
NMT Address
State
Value
0xFFF8(65528)
Stop
0x0001
Operation
0x0002
Pre-operational
0x0080
Reset application
0x0081
Reset communication
0x0082

iR-ETN User Manual
11
8. In Modbus Mapping
The following is an example showing that when iR-ETN is connected with multiple
modules, the address mapping and input/output bit mapping can be as follows:
item
Product
Slot#1
iR-DI16-K
Slot#2
iR-DQ16-P
Slot#3
iR-DM16-P
Slot#4
iR-DQ08-R
Slot#5
iR-AI04-VI
Slot#6
iR-AQ04-VI
Slot#7
iR-PU01-P
Slot#8
iR-PU01-P
Slot#9
iR-PU01-P
Slot#10
iR-PU01-P
iBus Information Register
Address
Description
Value
Dec
Hex
10000
2710
Slot 0 Product code (Coupler)
0702h (iR-ETN)
10001
2711
Slot 1 Product code (Module)
0x0154 (iR-DI16-K)
10002
2712
Slot 2 Product code (Module)
0x0251 (iR-DQ16-P)
10003
2713
Slot 3 Product code (Module)
0x0351 (iR-DM16-P)
10004
2714
Slot 4 Product code (Module)
0x0243 (iR-DQ08-R)
10005
2714
Slot 5 Product code (Module)
0243h (iR-AI04-VI)
10006
2714
Slot 6 Product code (Module)
0243h (iR-AQ04-VI)
10033
2731
Number of modules
10
10035
2733
Point of Digital Input
24
10036
2734
Point of Digital Output
32
10037
2735
Channels of register input
4
10038
2736
Channels of register output
4

iR-ETN User Manual
12
Digital Input Bit Mapping to Modbus
Slot
Module
Bit Offset
Function
Code
iR-ETN (0000h~0017h)
Slot#1
iR-DI16-K
0000h~000Fh (Digital Input 0~15)
2
Slot#2
iR-DQ16-P
N/A
Slot#3
iR-DM16-P
0010h~0017h (Digital Input 0~7)
2
Slot#4
iR-DQ08-R
N/A
Digital Output Bit Mapping to Modbus
Slot
Module
Bit Offset
Function
Code
iR-ETN (0000h~0020h)
Slot#1
iR-DI16-K
N/A
Slot#2
iR-DQ16-P
0000h~000Fh (Digital Output 0~15)
5,15
Slot#3
iR-DM16-P
0010h~0017h (Digital Output 0~7)
5,15
Slot#4
iR-DQ08-R
0018h~001Fh (Digital Output 0~7)
5,15
Analog Input Mapping to Modbus
Slot
Module
Description
Address
Function Code
Slot#5
iR-AI04-VI
Channel 0 analog input
0
3, 4, 23
Channel 1 analog input
1
Channel 2 analog input
2
Channel 3 analog input
3
Analog Output Mapping to Modbus
Slot
Module
Description
Address
Function Code
Slot#6
iR-AQ04-VI
Channel 0 analog output
256
6, 16, 23
Channel 1 analog output
257
Channel 2 analog output
258
Channel 3 analog output
259
Module Register Mapping to Modbus
Slot
Module
Description
Modbus Address
Module Register
Slot#5
iR-AI04-VI
Channel 0 Input Mode
22020
20
Channel 1 Input Mode
22021
21
Channel 2 Input Mode
22022
22
Channel 3 Input Mode
22023
23
……
……..
……
Slot#6
iR-AQ04-VI
Channel 0 Output Mode
22500
0
Channel 1 Output Mode
22501
1
Channel 2 Output Mode
22502
2

iR-ETN User Manual
13
Channel 3 Output Mode
22503
3
……
……..
……
16# Error Code
22516
16
iR-PU01-P Variable Instance Mapping
Slot
Module
Description
Address
Function Code
Slot#7
(Axis 0)
iR-PU01-P
Axis 0 variable instance input
40000~40015
23
Axis 0 variable instance output
40500~40515
Slot#8
(Axis 1)
iR-PU01-P
Axis 1 variable instance input
40016~40031
23
Axis 1 variable instance output
40516~40531
Slot#9
(Axis 2)
iR-PU01-P
Axis 2 variable instance input
40032~40047
23
Axis 2 variable instance output
40532~40547
Slot#10
(Axis 3)
iR-PU01-P
Axis 3 variable instance input
40048~40063
23
Axis 3 variable instance output
40548~40563
*The following are examples explaining variable instance mapping. In these examples,
Axis 0 is used.
Axis 0 variable instance input:
Item
Address
Description
Data Type
Dec/Hex
1
40000
High Byte
Axis 0 Mode of Operation Display
USINT
Unsigned 8
Dec
Low Byte
Axis 0 Digital Input
BYTE
Unsigned 8
Hex
2
40001
Axis 0 StatusWord
UINT
Unsigned 16
Hex
3
40002
Axis 0 Position actual value (Lo word)
DINT
Signed 32
Dec
4
40003
Axis 0 Position actual value (Hi word)
5
40004
Axis 0 Velocity actual value(Lo word)
DINT
Signed 32
Dec
6
40005
Axis 0 Velocity actual value(Hi word)
7
40006
Axis 0 Position demand internal value(Lo word)
DINT
Signed 32
Dec
8
40007
Axis 0 Position demand internal value(Hi word)
9
40008
High Byte
Axis 0 Digital Output Status
BYTE
Unsigned 8
Hex
Low byte
Axis 0 Capture Channel Status
BYTE
Unsigned 8
Hex
10
40009
Axis 0 Error code
UINT
Unsigned 16
Hex
11
40010
Axis 0 2nd additional position actual value (Lo
word)
DINT
Signed 32
Dec
12
40011
Axis 0 2nd additional position actual value(Hi
word)
40012
~40015
Reserved

iR-ETN User Manual
14
Axis 0 variable instance output:
Item
Address
Description
Data Type
Dec/Hex
1
40500
High Byte
Axis 0 Mode of Operation
USINT
Unsigned 8
Dec
Low Byte
Axis 0 Digital Output
BYTE
Unsigned 8
Hex
2
40501
Axis 0 Controlword
UINT
Unsigned 16
Dec
3
40502
Axis 0 Target Position (Lo word)
DINT
Signed 32
Dec
4
40503
Axis 0 Target Position (Hi word)
5
40504
Axis 0 Profile velocity (Lo word)
DINT
Signed 32
Dec
6
40505
Axis 0 Profile velocity (Hi word)
7
40506
Axis 0 Target velocity (Lo word)
DINT
Signed 32
Dec
8
40507
Axis 0 Target velocity (Hi word)
9
40508
Axis 0 Profile acceleration (Lo word)
DINT
Signed 32
Dec
10
40509
Axis 0 Profile acceleration (Hi word)
11
40510
Axis 0 Profile deceleration(Lo word)
DINT
Signed 32
Dec
12
40511
Axis 0 Profile deceleration (Hi word)
40512
~40515
Reserved

iR-ETN User Manual
15
9. EtherNet/IP Object
Object List
Name
Object Type
Object Code (Hex)
Identity
Standard Object
01
Message Router
Standard Object
02
Assembly
Standard Object
04
Connection Manager
Standard Object
06
TCP/IP Interface
Standard Object
F5
Ethernet Link
Standard Object
F6
Module Register
Manufacturer Defined Object
70
iBus Object
Manufacturer Defined Object
71
AXIS Object
Manufacturer Defined Object
80~87
Identity Objects
Class Code: 01HEX
9.2.1 Service
Service Code
Class
Instance
Name
Value
0x01
●
●
Get Attribute All
0x05
X
●
Reset
0: Reset
0x0E
X
●
Get Attribute Single
9.2.2 Class Attributes
Instance ID
Attribute ID
Read/Write
Name
Data Type
Value
0
1
Read
Revision
UINT
1
2
Read
Max Instance
UINT
1
6
Read
Maximum ID Number
Class Attributes
UINT
7
7
Read
Maximum ID Number
Instance Attributes
UINT
7
9.2.3 Instance Attributes
Instance ID
Attribute ID
Read/Write
Name
Data Type
Value
1
1
Read
Weintek Vendor ID
UINT
1596
2
Read
Device Type-
Communications Adapter
UINT
12
3
Read
iR-ETN Product Code
UINT
1794
4
Read
Revision
Major
USINT
1
Minor
USINT
1
5
Read
Device State
WORD
6
Read
Serial Number
UDINT
7
Read
Product Name
STRING
“iR-ETN”

iR-ETN User Manual
16
Message Router Object
Class Code: 02HEX
9.3.1 Class Attributes & Instance Attributes
None
Assembly Object
Class Code: 04HEX
Please refer to the EDS file generated by EasyRemote IO.
Connection Manager Object
Class Code: 06HEX
9.5.1 Class Attributes & Instance Attributes
None
Ethernet Link Object
Class Code: F6HEX
9.6.1 Services
Service Code
Class
Instance
Name
0x01
●
X
Get Attribute All
0x0E
●
●
Get Attribute Single
9.6.2 Class Attributes
Instance ID
Attribute ID
Read/Write
Name
Data Type
Value
0
1
Read
Revision
UINT
4
2
Read
Max Instance
UINT
1
9.6.3 Instance Attributes
Instance ID
Attribute ID
Read/Write
Name
Data Type
Value
1
1
Read
Interface
Speed
UDINT
100:Speed 100M
2
Read
Interface Flags
DWORD
Bit 0 : Link Active
Bit 1 : Full Duplex
Bit 2~4 : Auto
negotiation
Bit 5 : Manual Setting
required Reset
Bit 6 : Local Hardware
Fault
Others : 0
3
Read
Physical
Address
6 USINTs
MAC address
1
11
Read
Interf
ace
Capa
bility
Capability
Bits
DWORD
Interface capabilities,
other than
speed/duplex
Table of contents