SP9 ServiceManual.docx 06/02/2015 Page 5 of 42
4.INSTALLATION:
Electrical Installation:
Electrical specification: 2.4kW-230VAC-50/60Hz
A moulded 13A IEC power cord is provided. This should be plugged into the IEC connection
on the base of the boiler and plugged into a suitable 13A power outlet.
When installing the machine, always observe the local regulations and standards.
Plumbing Installation:
Mains water pressure required (limits): 5-50psi (35-345kPa) 0.5 –5.0 bar
Fit a stop Valve on a cold water line and attach a 3/4" BSP male fitting, (e.g. 3/4" x 1/2" 311
or washing machine type stop valve).
For US versions use 3/8” NPT male fitting.
Connect straight tailpiece of the hose to the stop valve fitting. Make sure that the pre-
attached sealing washer is fitted.
Turn on the water to flush any impurities, dust etc. from the inlet hose and water pipe. Allow
several litres through.
Connect right-angled tailpiece of the hose to the inlet valve of the boiler (3/4" BSP). Make
sure the sealing washer is fitted here also.
Turn on water and check for leaks.
Installation of SP9 Head Unit:
A full A4 sheet sized version of the counter cut-out template,
seen opposite in Figure 1, can be found on the last page of
this manual.
The cut-out is simply two 80mm holes centred 83mm apart.
Alternatively, the area outlined in red, bounded by the two
circles and the parallel lines (obround shape) can be cut out
using a jig-saw or similar.
Once the cut-out is complete, mount the SP9 Head Unit using
the brackets supplied. See Figure 3, below. Use the
appropriate rubber spacers on the brackets to match the
thickness of the counter.
Attach the electrical connector and the two hoses to the
appropriate ports on the under counter unit.
A goes to A, B goes to B and DIN goes to DIN.
For a Single Head System, use A1, B1 and DIN1.
For a Twin Head System, connect Head Unit 1 as in a Single
Head System. Connect Head Unit 2 to A2, B2 and DIN2.
The hoses should be secured with the supplied hose clips.
The Undercounter Unit should ideally be positioned directly below the Head unit installed position.