6.1.Electrical Connections
6.1.1. General
All electrical works must be done by qualified electricians. All main
electrical equipment must be earthed. Failure to heed this warning may
cause lethal accident. Make sure that the earth lead is correctly
connected by testing it.
Use MASDAF RLE-1C Motor Protection and Control Relay which is
supplied with the pump. We do not guarantee the pumps running
without RLE-1C *
Motor Control Panels must be manufactured according to the circuit
diagrams in this booklet. If you use a different circuit diagram, please
contact our technicians and have their approval.
Make sure the currents and cable diameters of contactors, overload
relays and fuses are suitable for motors nominal currents.
Check the mains voltage and be sure it corresponds to the value on
motor label.
Check the connection of motor cable socket and secure the tightness
before initial operation.
Connect the energy and control cable to the motor control panel
complying with the colors and diameters stated in the diagrams.
Make sure the outer cover of the energy cable is protected against
damages that might be caused by sharp metal or concrete corners and
prevent it from being squeezed in narrow spaces.
Do not use the energy and control cable to lift the pump.
*It is not valid, in cases where the panel is supplied with the pump by
MAS DAF MAKINA SANAYI A.Ş.
6.1.2. RLE-1C Motor Protection and Control Relay
MASDAF RLE-1C Motor Protection and Control Relay is very important
part of ENDURO Series submersible sewage pumps. It is supplied with
the pump and it shall be used to secure smooth operation of motor and
the pump.
When the device is switched on, all indicator lights blinks in order and the
control unit makes a self-check. If there is not any failure, NORMAL
indicator light switches on in green indicating it is ready to run the motor.
Water Leakage: In case of water leakage into the motor casing or oil
chamber, red indicator light switches on and the relay shuts down the
motor. Alarm relay becomes activated and until the RESET button, which
located on RELAY, is pressed, alarming goes on by blinking of red
indicator light in short periods. In this fault, if the RESET button is not
pressed, motors is not stepped in. In this case, must do maintenance by
removing the pump and repair the case of water leakage. The sign by
blinking continues until you press the RESET button. When RESET
button is pressed, the lamp goes out and alarm relay is deactivated.
Overheat: In case of overheating of motor windings, in which the
temperature exceeds 130°C, the red indicator light switches on and the
relay shuts down the motor. Indicator light blinks in short periods at
alarming position. When motor has cooled down, relay restarts the motor
while alarming goes on until the RESET button is pressed. Pressing the
RESET button disables the alarm relay and indicator light stops blinking.
Overload: The relay shuts down the motor, if the current overload limit is
exceeded. Alarm relay becomes activated and until the RESET button,
which located on RELAY, is pressed, alarming goes on by blinking of red
indicator light in short periods. As the failure is fixed, pressing the RESET
button will disable the overload and the alarm relay, so the system turns
back to normal conditions.
Maximum Level: When water level reaches the maximum level, which is
set by the user, float switch sends on alarm signal. MAX yellow indicator
light starts blinking. This alarm does not affect the current state (run or
stop) of the pump. Pressing the RESET button disables the alarm relay
and indicator light stops blinking. When RESET button is pressed, the
lamp goes out and the alarm relay is deactivated.
Phase Failure: An external phase protection relay, mounted in the
control panel, is connected to RLE-1C for checking phase sequence and
phase failures. When there is a failure in mains voltage or in phase
sequence, the motor is shut down by the relay and red indicator light
starts blinking. By the time the failure is fixed, the motor restarts
automatically while alarming goes on until the RESET button is pressed.
When RESET button is pressed, the lamp goes out and the alarm
relay is deactivated.
Ready By the time all red indicator lights on RLE-1C switch off, green
indicator light switches on, meaning that it is ready to run the motor. In
case of failure, green indicator light switches off and the relay shuts down
the motor.
Figure 10 - RLE-1C Motor Protection And Control Relay
6.1.3. Control Panel
The control panel is designed in order to safer operation of ENDURO
submersible pump can be claimed as extra. Single-pump or the 2 and 3
pump groups can be operated by the control panel.
In the pump operating principle of a multi-pump panel, all pumps can be
operated simultaneously or as a backup.
The control panel is in protection class IP 55 and it is isolated from dust,
splashing water and wastewater environment gas. Short circuit protection,
phase failure and protection against phase sequence, thermistor
protection, water leakage protection, over current protection, the indicator
lights, manual-automatic paco, start-stop as manual and the main switch
equipments are available control panel.
Floater is included in the package of submersible pump.
When the pump is supplied with control panel, there will not need a relay.
In this case the control panel will make the protection task of the motor.
When the pump is supplied without control panel, relay is sent with the
pump.
If the control panel is not supplied from our company, MAS DAF
MAKINA SANAYI A.Ş. is not responsible for the malfunction
resulting from electricity supply. In this case the pump and the relay
will remain out of warranty.