
2
GND
COM
METER
SHIELD
0-1mA
SHIELD
BLACK -S
RED +P
GREEN -P
WHITE +S
OUTPUT
354768910 11 12 13
L1
14
L2
115/230 VAC
50/60 Hz
Figure 2 Figure 3
Location of JP1 & JP2 Enclosure Top Removal
4.0 Electrical Connections
Figure 4 shows the wiring connections that are required for the basic system. They are:
115/230 vac power cable
Tension Sensor cables
Output cable
Meter cable
Wiring to and from the TSA must be done with double or
reinforced insulation or protective screening which
provides protective separation. All wiring should
comply with the essential requirements of the
appropriate standard(s) and is the responsibility of the
installer.
Route AC power away from sensor wiring. Run all
wiring in shielded cable. Connect shields to the
terminals indicated as “SHIELD”. Maximum shield
length and maximum length of wires outside of the shield Figure 4
is 3 in. (75 mm). Wiring Connections
5.0 Maintenance
The only maintenance that may be required on the TSA is fuse replacement. Replacement of the fuse(s)
requires first removing AC power, then opening the enclosure, which circumvents the enclosure IP rating.
The enclosure may be opened by inserting a flat blade screwdriver under the retaining tabs in the base
(See figure 3).
6.0 Calibration
Use the “SELECT OUTPUT” switch to choose the desired tension reference output. There are two
choices, 0 to 10 vdc or 4 to 20 madc.
Tension reference output calibration is accomplished by two adjustments (ZERO and GAIN). The ZERO
adjustment is used to cancel the weight of the sensing roll. The ZERO adjustment will adjust out a
sensing roll weight of up to 50% of the sensor(s) load rating(s).