Measurlogic DTS IoT Gateway User manual

©Measurlogic R19A Page 1
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
DTS IoT Gateway
Quick Start Guide
Revision R19A
TABLE OF CONTENTS
1SCOPE ..............................................................................................................................3
1.1 IDENTIFICATION................................................................................................................... 3
1.2 INTRODUCTION .................................................................................................................... 3
1.3 ADDITIONAL INFORMATION AND DOCUMENTATION ............................................................... 4
2PACKAGE CONTENTS.........................................................................................................4
3MOUNTING .......................................................................................................................4
4PHYSICAL CONNECTIONS ..................................................................................................5
4.1 POWER SUPPLY..................................................................................................................... 5
4.2 COMMMUNICATIONS ............................................................................................................. 5
4.2.1 Ethernet Meters............................................................................................................... 5
4.2.2 RS-485 Meters................................................................................................................. 6
4.2.2.1
BACnet MS/TP Meters on Port R2............................................................................................... 6
4.2.2.2
Modbus RTU Meters on Port R1 ................................................................................................. 6
4.3 STATUS LEDs ........................................................................................................................ 6
5COMMISSIONING THE DTS IOT GATEWAY .........................................................................7
5.1 POWERING ON...................................................................................................................... 7
5.2 CHANGING THE DTS IOT GATEWAY NETWORK SETTINGS ....................................................... 7
5.2.1 Identifying the DTS IoT Gateway in DTS Toolbox ............................................................... 7
5.2.2 Changing the Network Settings ......................................................................................... 8
5.2.3 Connecting to the Internal Webpage in the DTS IoT Gateway.............................................. 9
5.3 PROFILES CONFIGURATION PAGE ........................................................................................ 10
5.3.1 Configuration Parameters ............................................................................................... 10
5.3.1.1
Modbus RTU Parameters:.........................................................................................................10
5.3.1.2
BACnet MS/TP Parameters: ......................................................................................................11
5.3.2 Active Profiles................................................................................................................ 11
5.4 ADDING METERS................................................................................................................. 12
5.4.1 Common Information for ALL DTS Meters ........................................................................ 12
5.4.1.1
The DTS IoT Gateway as a BACnet_IP Server............................................................................12
5.4.2 DTS “–SM” Modbus Meters ............................................................................................. 12
5.4.3 DTS “–SB” BACnet Meters .............................................................................................. 13
5.4.4 DTS “–Ex” Meters .......................................................................................................... 13

©Measurlogic R19A Page 2
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.4.5 Active DTS Meter Details ................................................................................................ 14
5.4.6 Active Profile Buttons ..................................................................................................... 14
5.5 FINAL THINGS TO SETUP..................................................................................................... 15
5.5.1 Setting the Time Zone.................................................................................................... 15
5.5.2 Synchronizing the Time .................................................................................................. 16
5.6 VERIFY THE OPERATION OF THE DEVICES............................................................................ 17
5.6.1 The “System View” ........................................................................................................ 17
5.6.2 The “Data Log Viewer” or “Historian”............................................................................... 18
6REGISTRATION ON THE CLOUD....................................................................................... 19
6.1 Create a SMC Cloud Account................................................................................................. 19
6.2 Continue with the DTS IoT Gateway Registration.................................................................... 20
6.3 SMC Cloud Login.................................................................................................................. 21
6.4 SMC Cloud Interface ............................................................................................................ 22
6.4.1 Secure Tunnel Connect to your DTS IoT Gateway............................................................. 23

©Measurlogic R19A Page 3
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
1SCOPE
1.1 IDENTIFICATION
This document describes the basic usage of the DTS IoT Gateway, and how to get started by: First
configuring the network settings; Then physically adding DTS Meters to the DTS IoT Gateway ProtoAir; And
finally registering the DTS IoT Gateway with the SMC Cloud.
1.2 INTRODUCTION
The system overview of the DTS IoT Gateway and the SMC Cloud is shown here:
The DTS IoT Gateway hardware is preconfigured for DTS meters and supports:
Multiple simultaneous interfaces: 1 x Ethernet, 2 x RS-485, Wi-Fi
Any Serial or Ethernet, Modbus or BACnet DTS meter
Up to 40 DTS meters per gateway
The Cloud interface is powered by the “SMC Cloud” and provides a “No Cost Cloud Interface”:
Remote monitoring, control and data visualization, providing access to real time and historical data
Cloud alarming via SMS or email
No annual subscription until 2023 for up to 50 data points per minute per gateway

©Measurlogic R19A Page 4
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
1.3 ADDITIONAL INFORMATION AND DOCUMENTATION
Please see the following documents for more detailed information:
ProtoAir FPA-W44 Start-up Guide for Measurlogic
DTS IOT Gateway datasheet R19B
SMC IOT Platform datasheet R19B
2PACKAGE CONTENTS
The DTS IoT Gateway kit contains the following items:
The DTS IoT Gateway is a SMC ProtoAir FPA-W44-1837. The model number FPA-W44-1837 can be
found on the large white label on the side of the unit. Please confirm that this model number ends
with 1837. Only the SMC ProtoAir FPA-W44-1837 will work correctly with the DTS Series of
revenue grade meters.
The following connector plugs are supplied with the DTS IoT Gateway:
o1 x 3-Way BLACK plug for the 24V power
o1 x 3-Way GREEN Plug for the RS-485 Modbus RTU
o1 x 3-Way GREEN Plug for the RS-485 BACnet MS/TP
The WiFi Antenna
Please contact Measurlogic if any of the above items are missing.
3MOUNTING
The DTS IoT Gateway is for indoor use only, and MUST be mounted in a NEC compliant enclosure suitable
for the environmental conditions.
It is DIN rail mountable, so can be mounted onto a normal DIN rail. Alternatively, Measurlogic’s right-angle
bracket may be used. See https://www.measurlogic.com/product/right-angle-mounting-bracket/ for details.

©Measurlogic R19A Page 5
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
4PHYSICAL CONNECTIONS
4.1 POWER SUPPLY
The DTS IoT Gateway accepts 12-24VDC or 24VAC on pins L+ and N-. The
power supply must be able to deliver 125mA @ 24V or 250mA @ 12Vdc
(about 3W).
The MLG-10-24 (CPSU-0011) is a suitable 24Vdc output, 10W, 100Vac -
265Vac, DIN rail mountable power supply. Contact Measurlogic for details.
4.2 COMMMUNICATIONS
The Ethernet and two RS-485 interfaces on the DTS IoT Gateway can be
used simultaneously so that any DTS Ethernet meters and serial Modbus
and BACnet meters may be attached and used together.
4.2.1 Ethernet Meters
The Ethernet port on the DTS IoT Gateway is the RJ-45 connector on the side of the unit.
This is used to connect the DTS IoT Gateway to the local network which has access to the Internet.
Any Ethernet based DTS meters can be placed anywhere on the local network infrastructure.
Power to
ProtoAir
ProtoAir
Pin Label
Pin
Assignment
Power In (+)
L +
V +
Power In (-)
N -
V -
Frame Ground
FG
FRAME GND
Ethernet Port
BACnet MS/TP
Modbus RTU

©Measurlogic R19A Page 6
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
4.2.2 RS-485 Meters
The DTS IoT Gateway has a 3-way green connector for connecting the RS-485 busses for Modbus RTU and
BACnet MS/TP meters. The “+” and “-” polarity of the signal connections is shown on the casing and in the
diagram below. Remember to also connect the “G” common reference conductor.
4.2.2.1
BACnet MS/TP Meters on Port R2
Any serial BACnet MS/TP DTS meters must be attached to the R2 port as indicated
on the white sticker. The default communication parameters for this port are:
38400,8,N,1.
4.2.2.2
Modbus RTU Meters on Port R1
Any serial Modbus RTU DTS meters must be attached to the R1 port as indicated on
the white sticker. The default communication parameters for this port are:
9600,8,N,1.
4.3 STATUS LEDs
The status LEDs are as follows:
PWR –This is the power light and should always show steady green
when the unit is powered.
ERR –The SYS ERR LED will go on solid indicating there is a system
error Report to Measurlogic if this occurs.
SS –The SS LED will light if the unit is not getting a response from
one or more of the configured devices.
TX & RX –These are the green and yellow activity LEDs on the
Ethernet and serial ports. These will flash to show activity on these
ports.
Port R1
Modbus
Port R2
BACnet
RS-485 Pin
Assignment
TX+
+
RS-485 +
RX-
-
RS-485 -
GND
GND
RS-485 GND
G
-
+
Port R2
BACnet MS/TP
Port R1
Modbus RTU

©Measurlogic R19A Page 7
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5COMMISSIONING THE DTS IOT GATEWAY
Now that you have been introduced to the physical connections of the DTS IoT Gateway, you can proceed to
power up the device, connecting to its internal webpage, and adding your DTS meters.
5.1 POWERING ON
Connect the power supply to the DTS IoT Gateway as described in section 4.1.
Switch on the power on, and confirm that the “PWR” LED comes ON.
The BACnet “TX2” will also start blinking rapidly.
After 1 to 2 minutes the “SS” will start to blink.
Shortly after this the device will be ready, and will show in DTS Toolbox.
5.2 CHANGING THE DTS IOT GATEWAY NETWORK SETTINGS
Plug an Ethernet cable between the RJ-45 connector of the DTS IoT Gateway and your Ethernet switch to
connect your DTS IoT Gateway to your network. The default IP Address is 192.168.1.24.
5.2.1 Identifying the DTS IoT Gateway in DTS Toolbox
In order to proceed further with the commissioning of the DTS IoT Gateway you will need the Measurlogic
DTS Toolbox software utility, which allows for the discovery of the DTS IoT Gateway on the network, even if
the network parameters do not match your network.
DTS Toolbox can be downloaded from https://www.measurlogic.com/software-drivers/. To install, first
extract all the files in the ZIP file to an actual folder on the hard drive, and then run the setup program.
When you run DTS Toolbox it will automatically discover all Measurlogic meters on you network.
The details of the DTS IoT Gateway device will be shown on the
line with the “CN1837 Measurlogic vx.xx”title. The MAC address
of the device is also shown on the same line.
Confirm that the MAC address shown on the DTS Toolbox line is
the same as the MAC address shown on the label on the side of
the DTS IoT Gateway itself.

©Measurlogic R19A Page 8
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.2.2 Changing the Network Settings
Firstly the network parameters of the DTS IoT Gateway
must be changed to suit your local network.
Press the “Gear” settings button on the line of
the DTS IoT Gateway.
Now press the “Network Settings” button.
Enter network parameters that are suitable for your
network. Measurlogic recommend assigning a fixed (or
static) IP Address to the DTS IoT Gateway. You may
need to contact your network administrator for this
information.
The IP Address must be unique on your subnet.
The subnet Netmask, and default gateway must
match your network.
Ensure that the “DHCP Client” and “DHCP
Server” are both “Disabled”.
Press “Update IP Settings” to accept to proceed
with the change.
Press “Change and restart” to reboot the DTS
IoT Gateway device with the new settings.
The reboot process takes about 15 to 30
seconds.
While the DTS IoT Gateway is rebooting the DTS
Toolbox screen will show the device with the old
settings as “Lost”.
The reboot process takes about 15 to 30
seconds.
Wait for the new line to appear showing the new
network settings.

©Measurlogic R19A Page 9
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.2.3 Connecting to the Internal Webpage in the DTS IoT Gateway
The internal webpages of the DTS IoT Gateway can be accessed by:
1. Typing the IP address of the device directly into the address line of a web browser;
2. Or by first starting DTS Toolbox and pressing the “Connect” button (See section 5.2.1).
Press the “Login” button to login to the internal webserver.
The default username and password are “admin” and “admin” respectively.

©Measurlogic R19A Page 10
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.3 PROFILES CONFIGURATION PAGE
Measurlogic DTS meters are added to the
DTS IoT Gateway using the internal
webpages of the DTS IoT Gateway device.
Connect to the DTS IoT Gateway as
described in section above.
1. Select “Settings” from the menu on
the left hand side of the screen.
2. Now select “Configuration”
3. Then press the “Profile
Configuration” button.
This will open a new tab in your browser with the “Configuration Parameters” and the “Active profiles”.
5.3.1 Configuration Parameters
These are the communication configurations of the two serial ports R1 and R2. The default parameters are
detailed in sections 4.2.2.1 and 4.2.2.2.
Do not change any of these settings unless you have a specific requirement for other parameters. The
default parameters are shown in these two screenshots if you need to revert to the defaults.
5.3.1.1
Modbus RTU Parameters:

©Measurlogic R19A Page 11
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.3.1.2
BACnet MS/TP Parameters:
5.3.2 Active Profiles
This is place where the details for all the active DTS meters are shown. This is also the place where DTS
meters can be added or removed from the “Active Profile”.

©Measurlogic R19A Page 12
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.4 ADDING METERS
Meters are commissioned by adding then to the “Active Profile”. Press the “Add” button at the bottom of the
“Active Profile” section, as shown in section 5.3.2 above. The information required for the different
communication types of DTS meter is described below, together with some example values.
5.4.1 Common Information for ALL DTS Meters
This section explains the parameters that are common for all DTS meter types.
Meter Profile –Select the DTS meter model and communication interface type from the “Profile”
drop down list.
Node ID –This must be unique on the DTS IoT Gateway for ALL the different meter interface
types. Choose a number that you have not already used, and a number that does not clash with the
address of any Modbus RTU meters.
bac_srv_id –BACnet_IP Server Device ID –See Section 5.4.1.1 below for details.
5.4.1.1
The DTS IoT Gateway as a BACnet_IP Server
The DTS IoT Gateway is capable of exposing all the DTS meters attached to it as BACnet_IP devices on the
Ethernet network. This parameter is necessary even if you are not planning to access the meters as
BACnet_IP devices on the DTS IoT Gateway.
bac_srv_id –All DTS meters added to the DTS IoT Gateway must have the bac_srv_id defined,
even if you are not using the BACnet Server feature. This number must be unique for all devices on
your BACnet_IP network. You may need to ask your network administrator for this information. In
the absence of any other networking restrictions due to an existing BACnet_IP network, we
recommend that you start numbering from 2 as you add your various devices.
5.4.2 DTS “–SM”Modbus Meters
When adding a DTS serial Modbus RTU (-SM) meters, the following parameters are needed:
Node ID –This is the IP Address of the serial meter on the network segment. All Modbus RTU
meters on the Modbus serial RS-485 bus must have unique Modbus Addresses, and the Node_ID
that you enter here must match the Modbus Address of the meter. The Measurlogic DTS Config tool
may be used to change the Modbus Address of the meter.
bac_srv_id –BACnet_IP Server Device ID.

©Measurlogic R19A Page 13
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.4.3 DTS “–SB”BACnet Meters
When adding a DTS serial BACnet MS/TP (-SB) meters, the following parameters are needed:
Node ID –This must be unique on the DTS IoT Gateway. Choose a number that you have not
already used, and a number that does not clash with the address of any Modbus RTU meters.
bac_dev_id –This is the Device ID or Object Identifier of the BACnet MS/TP meter on the network
segment. All BACnet MS/TP meters on the BACnet serial RS-485 bus must have unique BACnet
Device IDs.
bac_srv_id –BACnet_IP Server Device ID.
5.4.4 DTS “–Ex”Meters
When adding a DTS Ethernet (-Ex) meters, the following parameters are needed:
Node ID –This must be unique on the DTS IoT Gateway. Choose a number that you have not
already used, and a number that does not clash with the address of any Modbus RTU meters.
ip_address –This is the IP Address of the Ethernet meter on the network.
tcp_id –This is the Modbus address of the Ethernet meter, which defaults to 100 for all DTS
Ethernet meters.
bac_srv_id –BACnet_IP Server Device ID.

©Measurlogic R19A Page 14
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.4.5 Active DTS Meter Details
As you add DTS meters, the details will show under “Active Profiles.
The screenshot above shows examples of DTS “-SB”, “-SM” and “-Ex” meters. The meaning of the various
parameters is discussed in more detail in section 0 above.
ATTENTION
After changes have been made to the “Active Profile” press
the “System Restart” button to reboot the DTS IoT
Gateway to finalise and accept the changes.
5.4.6 Active Profile Buttons
The following buttons are useful for the “Active profiles”:
Remove –Used to completely remove the corresponding existing DTS meter.
Add –Used to add additional DTS meters to the DTS IoT Gateway. This will be discussed in more
detail in section 0 below.
System Restart –The DTS IoT Gateway will be rebooted. A reboot is necessary after changes
have been made to the “Active Profile”.
Clear Profiles and Restart –This function removes ALL the DTS meters in the Active Profile and
restarts the DTS IoT Gateway.

©Measurlogic R19A Page 15
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.5 FINAL THINGS TO SETUP
The final thing to do is to setup the time zone where the DTS IoT Gateway is to be installed, and synchronize
the time. If the DTS IoT Gateway is registered to the SMC Cloud (see section 6 below) then it will
synchronize with the SMC Cloud.
5.5.1 Setting the Time Zone
A. Connect to the internal Webpage in the DTS IoT Gateway using either of the methods described in
section 5.2.3 above.
B. Click on “Diagnostics” at the bottom on the “System View” screen.
C. If you are still on the “Profiles” page (where the DTS meters are added) then you can press the
“Diagnostics & Debugging” button (as can be seen in the screenshot in section 5.4.5 above).
1. Expand the “Navigation”
tree to get to “Setup >
Time Settings”.
2. Select the desired time
zone from drop down list
and press “Submit”.

©Measurlogic R19A Page 16
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.5.2 Synchronizing the Time
A. Click of the “CN1837 Measurlogic vx.xx” title in the navigation tree.
B. The present time and time zone can be seen on the “Status” tab page. It is near the bottom of the
information, so you will need to scroll down to the bottom.
C. Press the “System Time Synch” button to synchronize the time in the DTS IoT Gateway.
If the DTS IoT Gateway is registered to the SMC Cloud (see section 6 below) then it will synchronize with the
SMC Cloud in the future..

©Measurlogic R19A Page 17
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.6 VERIFY THE OPERATION OF THE DEVICES
Once you have finished adding all your DTS meters, press the “Device List” button to see the “System View”.
This is the easiest way to verify that all the meters you added are present and the live measurement values
alongside each meter will show if the meter is operating correctly.
5.6.1 The “System View”
Once you have added DTS meters to your
DTS IoT Gateway this “Device List” screen will
show the DTS meters you have attached to your
device, together with some live operational
information for each device.
Notice that the “Energy” is available on this screen,
so you can easily see the energy figures for all
your meters.
Clicking on any of the DTS meters in the list will
bring up the “Device List” for that meter (as shown
on the right).
This list contains other live measurement data, as
well as configuration information like the
“CT_Ratings” that can be edited.

©Measurlogic R19A Page 18
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
5.6.2 The “Data Log Viewer” or “Historian”
Data is logged and buffered locally in the DTS IoT Gateway. This enables logged history of up to 30 days to
be viewed and graphed locally on the DTS IoT Gateway. If the DTS IoT Gateway is registered to the cloud,
this buffering will prevent logged data loss if the Internet connection to the cloud is lost.
To view the logged data on the DTS IoT Gateway itself:
Click on “Data Log View” on the side menu.
Press the “Settings” button.
A popup list will appear showing all the available data points from all the attached devices.
Select one or more data points that you would like to plot
Press the “Submit” button at the bottom of the list.
The DTS IoT Gateway will then show a separate plot for each data point selected.
Each plot consists of two parts:
a) The small timeline below shows a thumbnail of the data for the past 30 days. The two window
handles (show by the red arrows) can be dragged to select the time period of interest.
b) The main plot above shows the logged detail. Hovering over a particular part of the plot will
show the date/time and the value on the plot at that position. This position is shown by a vertical
grey line, and a blue dot on the plot curve.
The above assumes that the DTS IoT Gateway has been running for sufficient time to allow logged data to
accumulate. Logged history of up to 30 days may be viewed.

©Measurlogic R19A Page 19
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
6REGISTRATION ON THE CLOUD
Once your DTS IoT Gateway has been setup as described above, it is time to register it on the SMC Cloud.
Press the “SMC Cloud” button, and press “Close” to dismiss the information popup page that appears. If your
DTS IoT Gateway is NOT already registered on the SMC Cloud the following screen will appear.
6.1 Create a SMC Cloud Account
In order to create a SMC Cloud Account:
Press the “Create a SMC Cloud
Account” button.
Enter your email address as the
username when requested.
The dialog shown here confirms
that you have requested an SMC
Cloud Account, and that an
email has been sent to the
address you specified.

©Measurlogic R19A Page 20
7334 S. Alton Way, Suite 14M, Centennial CO 80112
Tel: 877 777-6567 Fax: 425-799-4780
web: www.measurlogic.com
The email that you receive will look like this:
Press “Complete Registration” and fill
in the details requested.
The username and password that you have
just created will be used to:
Registered your DTS IoT Gateway on
the SMC Cloud.
Login into the SMC Cloud from
anywhere to view the DTS meters
that you have attached to your DTS
IoT Gateway.
6.2 Continue with the DTS IoT Gateway Registration
1. Enter your existing or newly created username and password under “User Credentials” as indicated
in the screenshot above. Scroll down the page so that you can see the information shown below.
Table of contents