Merlin Gerin itm 4c 6e User manual

1
2
3
cat. no 15270
ITM 4C 6E
Discover your ITM
9 possible functions
b
Weekly time programming
b
Yearly time programming
b
Impulse programming
b
Close delay
b
Open delay
b
Timer
b
Flash device
b
Time counter
b
Impulse meter
First energisation
b
select the language
b
adjust date and time
Press the "Menu" key to select:
bb
bb
"ADJUST DATE ANDTIME"
b
"MODIFYTIME RANGE"
, to modify the operating time
ranges,
b
"PROGRAM"
to program the functions,
b
"EXIT"
to return to the permanent display of time and
channel status.
Discover the display and the keys of your ITM
Main menu
en
(switch, pushbutton, light sensitive switch, thermostat,
movement detection control switch, etc.)
6 x 230V inputs
4 x 230V, 10A output channels
C1-C2 C3-C4
ON
OFF
Loads
(lamp, small motor,
bell, luminous sign,
etc.).
Sealed swivel cover
Manual holder slot
Removable memory cartridge (cat. no. 15280, optional)
Main menu access
Time Day
Date
Output channel
status
(ON and OFF)
Validating flashing data
Browsing
ITM basic principles
b
4 x 230V, 10A output channels
v
1 programmable function per channel
v
the same function can be repeated on several channels.
b
6 x 230V inputs used to:
v
control
the functions for close delay, open delay, timer
and counter resetting,
v
count
hours or impulses for the time counter and
impulse meter functions,
v
condition
the weekly time, yearly time programming
functions and the flash device.
b
The same input can be associated with one or more
functions.
!
It is recommended that larger
loads are switched using a
contactor.
NEW PRO/ADD
MODIFY
CLEAR
DUPLICATE
MEM SPACE
SUM/WIN TIME
LANGUAGE
EXIT
Programming menu
WEEKL. PROG.
YEARL. PROG.
IMPULS PROG
CLOSE DELAY
OPEN DELAY
TIMER
FLASH DEVICE
TIME COUNT
IMPUL. METER
Function menu
b
The programming menu is accessed by selecting
"PROGRAM"
in the main menu.
It is protected by a fixed code: 111.
b
The programming menu lets you:
v
"NEW PRO/ADD"
to program functions or add parameters to an already programmed function (time range, condition),
v
"MODIFY"
to change the parameters of a programmed function.You cannot add a parameter that has not been created
(see
"NEW PRO/ADD"
),
v
"CLEAR"
to completely delete the programmed function or to clear some parameters
(date, time and language are kept),
v
"DUPLICATE"
to copy the entire memory cartridge program (optional) to the product or the product to the memory
cartridge,
v
"MEM SPACE"
to view the remaining memory space for weekly, yearly programming and for impulse programming.
This memory is consulted function by function,
v
"SUM/WINTIME"
to select your summer/winter time changeover,
v
"LANGUAGES"
to select the programming language,
v
"EXIT"
to return to the main menu.
b
If you activate no key for 5 minutes, the ITM will return to permanent display of time and channel status.
Access programming
LN
LNLNL
NLN
230V~ 50Hz 1...6 =
Entrées / Inputs 230V~
C1......C4
Canaux / Channels 10A10A / 230V~
C1 C2 C3 C4
menu OK
+
-
LN 123456
Modifying flashing data
230V ±5%

4
5
6
7
ON
OFF 30/04/01 02/05/01
ON
OFF 2 4 6 8 10 12 14 16 18 20 22 24
Output channel status
hours
SELECT
CONDITIONAL
INPUT?
YES
ON O8:00 MO
OFF 14:00 MO
COPY: YES
-TWTF--
b
This function is used to program time ranges:
v
different for each day of the week:
- ON: Monday 8H00 - ON: Tuesday 20H00
- OFF: Monday 14H00 - OFF: Tuesday 23H00
v
identical for several days of the week using the copy
function:
- ON: Monday 8H00 copyable from Tuesday to Friday
- OFF: Monday 14H00
v
spread out over several days of the week:
- ON: Tuesday 8H00 - OFF: Thursday 20H00
b
Optional programming of an override input*.
b
Optional conditioning of the function by an input*.
b
Inthe
"PROGRAM"
mode,select"
NEWPRO/ADD"
then
"WEEKL. PROG."
Discover the time programming function
bb
bb
For example: weekly
"ON" output channel from 08H00 to 14H00 from Monday to Friday and when the selected input
is closed.
Weekly time
bb
bb
Example: yearly
Output channel status
ON 15:00
30/04/01
OFF 08:00
02/05/01
days
"ON" output channel from
15H00 on 30/04/01 to 08H00
on 02/05/01.
b
This function is used to program time ranges dated and
spread out over the year.
b
Optional programming of an override input*.
b
Optional conditioning of the function by an input*.
b
In the
"PROGRAM"
mode, select
"NEW PRO/ADD"
then
"YEARL. PROG."
Yearly time
DURATION:
15s
At 12:00
-----SS
DURATION:
45s
At 16:00
MTWTF--
DAUER:
10s
UM 08:00
MDMDF--
b
This function is used to program impulses
(from 1 to 59 seconds) at different times of the week.
b
An impulse can be programmed over 1 or more days.
b
Impulses of different durations can be programmed on
the same day.
b
In the
"PROGRAM"
mode, select
"NEW PRO/ADD"
then
"IMPULS PROG."
Discover the impulse programming function
bb
bb For example: Output channel status (except Saturday and Sunday)
time
"ON" output channel for 10s at 08:00 Monday to Friday, 15 s at 12H00 on Saturday and Sunday,
and 45 s at 16H00 from Monday to Friday.
ON
OFF 08h 16h
12h
10 s 45 s
ON
OFF 0
15 s
operating duration
DURING A
TIME
RANGE?
YES
ON
OFF
ON
OFF
FROM 08:00
TO 12:00
MT-TF--
DURATION
0H00min20s
ACTIVATED BY
INPUT 5
bThis function is used to delay energisation of the output
channel.
bThe duration of the delay is programmable in h/min/s.
bThe delay starts on activation of the associated input*.
bDe-activation of the input cancels the delay or
de-energises the output channel.
bThisfunction can beapplied permanently or restrictedto
a particular time range programmable over one or more
days of the week.
bIn the "PROGRAM" mode, select "NEW PRO/ADD"
then "CLOSE DELAY."
Discover the open delay and close delay functions
bb
bb For example: close delay Status of input 5
"ON" output channel, 20 s after activation of input 5, from 0800
to 12H00 on Monday, Tuesday, Thursday and Friday.
Output channel status time
time
Close delay
Open delay
bThis function is used to delay de-energisation of the
output channel.
bThe duration of the delay is programmable in h/min/s.
bThe delay starts on de-activation of the associated
input*.
bActivation of the input energises the output channel
or cancels the delay.
bThis function can be applied permanently or restricted to a particular time range
programmable over one or more days of the week.
bIn the "PROGRAM" mode, select "NEW PRO/ADD" then "OPEN DELAY."
DURATION:
0H01min30s
ACTIVATED BY
INPUT 3
ON
OFF
ON
OFF
Discover the timer function
bThis function is used to control an output channel for a
programmable duration on activation of an input (impulse
control).
bRe-activation of the input restarts the operating duration.
bThisfunction can beapplied permanently or restrictedto
a particular time range programmable over one or more
days of the week.
bIn the "PROGRAM" mode, select "NEW PRO/ADD"
then "FLASH DEVICE."
bb
bb For example: Status of input 3
"ON" output channel for
00H01min30safteractivation
of input 3. Output channel status
1 mn 30 s
20 s
Output channel status (at weekends)
time
operating duration
*(latched control)

8
8
9
ON
OFF
Ctrl Count. Cond. ON override RESET Connected item
E1 vvv v v.................................................
E2 vvv v v.................................................
Function programmed: E3 vvv v v.................................................
vWeekl. prog. vClose delay vFlash device E4 vvv v v.................................................
vYearl. prog. vOpen delay vTime count. E5 vvv v v.................................................
vImpuls. prog. vTimer vImpul. meter E6 vvv v v.................................................
Time ranges 12345
Time Date Time Date Time Date Time Date Time Date
ON
OFF
Days MTWTFSS MTWTFSS MTWTFSS MTWTFSS MTWTFSS
vvvvvvv vvvvvvv vvvvvvv vvvvvvv vvvvvvv
Circuit controlled: .................................................
Function configuration (delay duration, impulse, timer, counting threshold...):....................................................................................................................
.................................................................................................................................................................................................................................................
Channel 2
"
SELECT
CONDITIONAL
INPUT?
YES
Ctrl Count. Cond. ON override RESET Connected item
E1 vvv v v.................................................
E2 vvv v v.................................................
Function programmed: E3 vvv v v.................................................
vWeekl. prog. vClose delay vFlash device E4 vvv v v.................................................
vYearl. prog. vOpen delay vTime count. E5 vvv v v.................................................
vImpuls. prog. vTimer vImpul. meter E6 vvv v v.................................................
Configuration Sheet
Time ranges 12345
Time Date Time Date Time Date Time Date Time Date
ON
OFF
Days MTWTFSS MTWTFSS MTWTFSS MTWTFSS MTWTFSS
vvvvvvv vvvvvvv vvvvvvv vvvvvvv vvvvvvv
Circuit controlled: .................................................
Function configuration (delay duration, impulse, timer, counting threshold...):...................................................................................................................
.................................................................................................................................................................................................................................................
ON DURATION:
00min 01s
OFF DURATION:
00min 10s
FROM 20:00
TO: 05:00
MTWTF--
bThis function is used to repeatedly control an output
channel during a period of operation and a period of
non-operation.
bOptional conditioning of the function by an input.
bThisfunction can beapplied permanently or restrictedto
a particular time range programmable over one or more
days of the week.
bIn the "PROGRAM" mode, select "NEW PRO/ADD"
then "FLASH DEVICE."
Discover the flash device function bb
bb For example:
"ON" output channel for 1 s, "OFF" output channel for 20 s in
turn, from 20H00 to 05:00 from Monday to Friday or when the
selected input is closed.
ON
OFF
ON
OFF
T 2
T 1 T 3 T X
ON
OFF
COUNTER:
INPUT 1
0100 HRS
RESET/INP 3
bThis function is used to count the cumulated activation
time of the associated input and to activate an output
channel once the adjustable threshold has been reached.
bThreshold adjustable from 0 to 99 999 hours.
bA different input is used to de-activate the output and
resets the counter (RESET).
bIn the "PROGRAM" mode, select "NEW PRO/ADD"
then "TIME COUNT."
Discover the time counter and impulse meter functions
bb
bb For example:
Time counter
"ON" output channel when
input 1 has cumulated 100
hours activation:
the counter will be reset on
input 3.
Status of
input 1
Output
channel
status
Status of
input 3
(≠input1)
time
time
time
counting
reset
countingthreshold
approach warning
Time counter
Impulsion counter
bThis function is used to count the number of impulses
on the associated input and to activate an output channel
once the adjustable threshold has been reached.
bThreshold adjustable from 0 to 99 999 impulses.
bA different input is used to de-activate the output and
resets the meter (RESET).
bIn the "PROGRAM" mode, select "NEW PRO/ADD"
then "IMPUL. METER"
Channel 1
DURING A
TIME
RANGE?
YES
T1+T2+T3+TX = 100 h
Output channel
status
time
operation for 1 s
non operation for 10 s

11
Schneider Electric
Centre Merlin Gerin
F-38050 Grenoble cedex 9
tél. : 04 76 57 60 60
12
10
11
51112370BA
As standards, equipment, characteristics and dimensions develop from time to time, always ask for confirmation of
the information given in this publication.
Thisproductmustbeinstalled,connected and used in compliance with current installationstandardsandregulations.
Ctrl Count. Cond. ON override RESET Connected item
E1 vvv v v.................................................
E2 vvv v v.................................................
Function programmed: E3 vvv v v.................................................
vWeekl. prog. vClose delay vFlash device E4 vvv v v.................................................
vYearl. prog. vOpen delay vTime count. E5 vvv v v.................................................
vImpuls. prog. vTimer vImpul. meter E6 vvv v v.................................................
Time ranges 12345
Time Date Time Date Time Date Time Date Time Date
ON
OFF
Days MTWTFSS MTWTFSS MTWTFSS MTWTFSS MTWTFSS
vvvvvvv vvvvvvv vvvvvvv vvvvvvv vvvvvvv
Circuit controlled: .................................................
Function configuration (delay duration, impulse, timer, counting threshold...):....................................................................................................................
.................................................................................................................................................................................................................................................
Channel 3
DUPLICATE
PROGRAMME
PRODUCT
> CARTRIDGE
(1)
DUPLICATE
PROGRAMME
CARTRIDGE
> PRODUCT
(2)
bThe cartridge can be used on all ITMs.
bIt lets you duplicate the program of your ITM (back-up
copy) or incorporate this program into another ITM.
bYou can duplicate the ITM's program on the cartridge (1)
or the cartridge on the ITM (2).
bIn the "PROGRAM" mode, select "DUPLICATE".
Use the memory cartridge (cat. no. 15280 optional)
Characteristics
b
Consumption: max. 45 VA
b
Memory:
v45 time ranges in weekly programming,
v15 time ranges in yearly programming,
v20 ranges in impulse programming.
b
Minimum time between 2 programmed switching
operations:
b
1 min
b
In event of mains power cut:
vthe display disappears,
vclock (date, time) is backed up by lithium battery:
- lifetime: 10 years,
- Back-up time: 5 years,
vprogram saved by EEPROM
vthe module cannot be programmed until it is
re-energised.
b
Operating temperature:-5°C … +50°C
b
(preferably install in the least hot part of the enclosure).
b
Degree of protection: IP 40 in the electrical switchboard
b
Connection terminals:
vmax. capacity: 6 mm2,
vrecommended screwdriver:posidriv 1 or flat 0.8x4 mm,
bStandard cartridge: EEPROM
b
Dimensions (9mm pitch): 10 pitch
b
Weight: 290g
Discover the summer/winter time changeover function
bThis function lets you select your summer/winter time automatic changeover.
bBy default, your ITM uses European parameters:
vEurope:
- summer (last weekend in March +1 hour)
- winter (last weekend in October - 1 hour)
bFor other parameters specific to your geographic zone, enter the month and the
corresponding week.
bIn the "PROGRAM" mode, choose "SUM/WINTIM" then "EUROPE" or "OTHER",
to be defined.
bIn the manual mode, you can directly adjust the product to make the summer/winter time
changeover.
"Configuration Sheet
Ctrl Count. Cond. ON override RESET Connected item
E1 vvv v v.................................................
E2 vvv v v.................................................
Function programmed: E3 vvv v v.................................................
vWeekl. prog. vClose delay vFlash device E4 vvv v v.................................................
vYearl. prog. vOpen delay vTime count. E5 vvv v v.................................................
vImpuls. prog. vTimer vImpul. meter E6 vvv v v.................................................
Time ranges 12345
Time Date Time Date Time Date Time Date Time Date
ON
OFF
Days MTWTFSS MTWTFSS MTWTFSS MTWTFSS MTWTFSS
vvvvvvv vvvvvvv vvvvvvv vvvvvvv vvvvvvv
Circuit controlled: .................................................
Function configuration (delay duration, impulse, timer, counting threshold...):...................................................................................................................
.................................................................................................................................................................................................................................................
Channel 4
Other Merlin Gerin Controllers manuals
Popular Controllers manuals by other brands

Westell
Westell AISG-RM3 manual

Siemens
Siemens ACVATIX SAX319.03 manual

General Power
General Power STAMFORD MX341 Specification, Installation and Adjustments

Comtrol
Comtrol RocketPort Plus Hardware installation

Herth+Buss
Herth+Buss Reanimator 4600 owner's manual

XICOY
XICOY FADEC system Autostart 10 user guide