4 / 8
Siemens Electromotoric actuators for valves CE1Q4501en
Building Technologies 2013-11-11
Technical Data
SAX..9..
Power supply Operating voltage
SAX319.. AC 230 V ±15%
SAX619.. AC 24 V ± 20% / DC 24 V + 20% / -15%
Frequency 45…65Hz
Fusing ac. DIN 57 100 part 430 (supply lines) 6 A…10 A slow
Power consumption at 50 Hz
SAX319.00 Stem retracts / extends 3.5 VA / 2 W
SAX319.03 Stem retracts / extends 6 VA / 3.5 W
SAX619.03 Stem retracts / extends 8 VA / 3.75 W
Function data Positioning times (with the specified nominal stroke)
The positioning time can vary, depending on the type
of valve, refer to chapter "Type summary" (page 2)
SAX319.00 120 s
SAX319.03, SAX619.03 30 s
Positioning force 800 N
Nominal stroke 20 mm
Permissible medium temperature (valve fitted) -25…130 °C
Signal inputs Positioning signal ”Y” SAX319.. 3-position
SAX319.. Voltage AC 230 V ±15%
SAX619.. (DC 0...10 V) Current draw ≤0.1 mA
Input impedance ≥100 kΩ
SAX619.. (DC 4...20 mA) Current draw DC 4...20 mA ± 1%
Input impedance ≤500 Ω
Parallel operation SAX619.. ≤10 (depending on controller output)
Forced control Positioning signal ”Z” SAX619.. R = 0…1000 Ω, G, G0
R = 0…1000 ΩStroke proportional to R
Z connected to G Max. stroke 100%
Z connected to G0 Min. stroke 0%
Voltage Max. AC 24 V ± 20%
Max. DC 24 V + 20% / -15%
Current draw ≤0.1 mA
Position feedback Position feedback U SAX619.. DC 0...10 V ± 1%
Load impedance >10 kΩres.
Load Max. 1 mA
Connecting cable Wire cross-sectional areas 0.13…1.5 mm
, AWG 24…16
Cable entries SAX.. EU: 2 entries Æ20.5 mm (for M20)
1 entry Æ25.5 mm (for M25)
Degree of protection Housing from vertical to horizontal IP54 as per EN 60529
Insulation class As per EN 60730
Actuators SAX319.. AC 230 V II
Actuators SAX619.. AC / DC 24 V III
Environmental conditions Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Indoors (weather-protected)
Temperature -5…55 °C
Humidity (noncondensing) 5…95% r.h.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -25…70 °C
Humidity <95% r.h.
Storage
Climatic conditions
IEC 60721-3-1
Class 1K3
Temperature -15…55 °C
Humidity 5…95% r.h.
Max. media temperatur when mounted on valve 130 °C
Standards CE conformity
As per EMC directive 2004/108/EC
Immunity EN 61000-6-2:[2005] Industrial
Emmissions EN 61000-6-3:[2007] Residential
Electrical safety EN 60730-1
Low-voltage directive AC 230 V 2006/95/EC
C-tick N 474
UL conformity AC 230 V -
AC/DC 24 V UL 873
Environmental compatibility -ISO 14001 (environment)
ISO 9001 (quality)
SN 36350 (environment-compatible products)
RL 2002/95/EG (RoHS)
Dimensions -See "Dimensions" (page 7)