Miller Edge MIM-62 User manual

www.GateOpenerSafety.com
Model: MIM-62
INSTALLATION INST UCTIONS
IMPO TANT:
EAD AND UNDE STAND ALL INST UCTIONS BEFO E BEGINNING INSTALLATION
1-Pre-Installation Worksheet
MIM-62 connects up to 6 monitored entrapment protection devices to 1 or 2 operator inputs. It is recommended that you
read the following instructions completely before begining installation. Please also reference your operator’s manual to
determine power and input requirements.
MIM-62 will accept up to 6 separate monitored devices and connect them to either of two outputs. Non-monitored•
devices will not work with MIM-62.
Input Channels 1 and 2 must be used, and are always assigned to Output A. The other input channels•
may be assigned to either Output A or Output B using the Input Assignment Switch on the rear panel.
Use of all 6 inputs is not required.
Each of the Output circuits of MIM-62 may be set to “Relay” (10 termination or normally closed), or “Pulsed” (like•
photo-eye output signals), by the Output Type selection switch on the rear panel, and Terminal Connection choice
on P1.
MIM-62 may be powered from any 12 or 24 VAC/DC source that can supply at least 130 mA.•
MIM-62 can provide an unregulated DC voltage to each monitored device; this voltage is dependent upon the•
input supplied to MIM-62. The operator must supply enough current to power the devices and MIM-62 together.
The Solution
Multi-Input Module
Use the chart below to determine which input devices you will associate with each output when they are
connected to the operator.
Input # Device Type Location Output A/B Current Draw
From MIM-62*
1 A mA
2 A mA
3 mA
4 mA
5 mA
6 mA
MIM-62 130 mA
TOTAL CU ENT: mA
*All normally closed inputs must use power from MIM-62. 75 mA maximum per channel.

2-1. Disconnect primary power to the operator.
2-2. Leave enough slack in your wiring to allow removal of MIM-62 if/when re-learning is required.
2-3. Prepare a mounting location for MIM-62 inside the operator. Use the two mounting slots on the
top cover of MIM-62.
Note: Do not mount MIM-62 yet. The switches and the Learn button on the rear panel of MIM-62
must be accessed during installation.
2-4. Connect the power leads to the removable 8-pin connector, as indicated in Figure 1.
www.GateOpenerSafety.com
INPUTS 1-2
(top to bottom):
– Input
– Com
– Power-
– Power+
INPUTS 3-6
(top to bottom):
– Power+
– Power-
– Com
– Input
– COM
– P/N.C.
– 10K
– COM
– P/N.C.
– 10K
– 12-24 VAC/DC
– 12-24 VAC/DC
Outputs A & B connect to the
appropriate safety device’s
input (pulsed, N.C., 10 ) on
your operator’s main board
Connect to your operator’s
accessory power supply
(12-24 VAC/DC).
Inputs 1 & 2 must be used.
They are assigned to Output
A. Inputs 3-6 can be assigned
to Output A or B.
Your monitored devices may*
be powered through the MIM-
62 for convenience or simply
utilize your operator’s power
supply outputs (12-24 VDC).
*Note: All N.C. devices must
be powered through MIM-62.
2-Install Module & Test
Figure 1
P1

www.GateOpenerSafety.com
2-5. Wire each of your monitored devices to the removable 4-pin connector as shown in Figure 2. If the
device is polarity sensitive, identify the correct common/ground wires. You do not need to use all 6
inputs.
2-6. Plug the monitored device’s connector into an appropriate input, as indicated in Figure 1.
2-7. To assign signal Output Types, select either “R” for Relay (10 or normally closed), or “P” for
Pulsed, as required by your gate operator. See Figure 3.
2-8. Each device input can have a different output assignment. Use the Input/Output Assignment DIP
switches to select A or B for each input that has a monitored device. See Figure 3.
Note: Input Channels 1 and 2 are hard-wired for Output A; switch positions 1 and 2 are ignored.
Figure 2
Figure 3
All 4-Wire
Devices
I
INPUT(+)
INPUT(-)
PWR(-)
PWR(+)
OUTPUT
POWER
10K
Sensing Edge
INPUT(+)
INPUT(-)
PWR(-)
PWR(+)
10K
EDGE
2-Wire Pulsed
Photo-Eye
INPUT(+)
INPUT(-)
PWR(-)
PWR(+)
PHOTO
EYE
All 3-Wire
Devices
A
INPUT(+)
INPUT(-)
PWR(-)
PWR(+)
OUTPUT
POWER

www.GateOpenerSafety.com
4-Safety Test
4-1. Activate each monitored device and confirm the corresponding inputs’ red LEDs on MIM-62
turn on.
4-2. Activate the operator and confirm that each monitored device stops and/or reverses as expected.
3-1. If monitored devices are not functioning, check for proper power connections, including polarity, if
necessary.
3-2. If, after the Learn button is pressed, one or both outputs are in fault (yellow LED on), check to see
which red LEDs are on. Confirm the device is connected to the assigned channel. If it is working,
confirm the output of the safety device is connected properly to the input connector.
3-3. If re-learning MIM-62 is necessary:
(a) Press the Learn button to clear settings
(b) Press the Learn button to learn new settings
3-4. If all monitored devices and MIM-62 are working (no red or yellow LEDs), and the operator is still
reporting a fault, confirm MIM-62 outputs are connected properly to the operator’s inputs. Also,
confirm the Output Interface is set correctly (pulsed or relay), as stated in the operator’s manual.
3-Troubleshooting
2-9. When all monitored safety device inputs are connected, turn on the power to the operator. MIM-
62 should display a brief light test followed by blinking of the Output A and Output B indicators.
The Learn Mode LED on the rear panel will also be lit. This indicates that MIM-62 is in Learn
Mode, and will display the present condition of each input channel’s sensor:
(a) On: solid Open circuit (faulty wiring or nothing connected)
(b) Blinking 10 ohm terminated sensor (no fault indicated)
(c) Off: solid Normally Closed sensor (no fault indicated)
(d) Fast Blink Pulsed sensor (no fault indicated)
If there is a fault, correct any wiring or make selection changes before proceeding.
Note: The LEDs behave differently in Learn Mode versus Run Mode.
2-10. When all intended devices are connected and indicating no faults, momentarily press the Learn
button on the rear panel. The lights should flash, and then all the LEDs should go off, except the
green power LED. Test each entrapment device to confirm the associated red LED turns on when
the device is activated.
2-11. At this point, MIM-62 should be operational and may be mounted to its mounting location.

www.GateOpenerSafety.com
Power: 12-24 VAC/DC nominal (8-30V max); typically 130 mA device power may be supplied from the
operator or alternatively from an external supply
Note: when using a normally closed operator input, MIM-62 must connect to operator accessory power
Cable Connections: 18-22 AWG
Dimensions: 4”W x 4.74”H x 1”D
Indicator Lights:
5-Specifications and Controls
LED State Meaning
Green Power LED On MIM-62 is getting power
Off No power to MIM-62
Yellow Output LED (A or B) On One of the input devices has detected a fault
Off No Faults detected for this output channel (A or B)
Red Input LED (1-6) Off This input is working properly
On: Solid This input has detected a Fault
On: Slow blink This device has detected a termination fault
On: Fast blink This device failed the N.C. monitoring test on power up
MODEL: MIM-62
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which may be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1- Re-orient or relocate the receiver antenna
2- Increase the separation between the equipment and the receiver
3- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4- Consult the dealer or an experienced radio/TV technician for help.
Changes or Modifications Not Expressly Approved By The Party Responsible For Compliance Could Void
The User’s Authority To Operate The Equipment.
6-FCC Compliance
Table of contents
Popular I/O System manuals by other brands

Allen-Bradley
Allen-Bradley Flex integra 1793-IB16 installation instructions

EES
EES USM series manual

Allen-Bradley
Allen-Bradley 1757-PIM installation instructions

Tiancheng Fire Protection Equipment
Tiancheng Fire Protection Equipment TCMK5413W user manual

Siemens
Siemens SIMATIC ET 200iS manual

Omron
Omron GT1-TS04T instruction manual

ICP DAS USA
ICP DAS USA ET-7219Z quick start guide

Accuphase
Accuphase DAC-50 instruction manual

ERMA
ERMA IO 1388 manual

Allen-Bradley
Allen-Bradley ControlLogix 1756-IH16ISOE installation instructions

Gopel Electronic
Gopel Electronic G Patch 6222 manual

National Instruments
National Instruments NI USB-6008 USER GUIDE AND SPECIFICATIONS