Tiancheng Fire Protection Equipment TCMK5413W User manual

Please read this user manual carefully before installation.
TCMK5413W Wireless Input&Output Module
User Manual
Liaoning·Tiancheng Fire Protection Equipment Co., LTD
Version
Date
Author
Note
Ver1.0 202009
Nov. 16, 2020
Deng Yi, Yan Chong
Create
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
1
I. General
The TCMK5413W wireless input/output module (hereinafter referred to as the module) is suitable
for installation in public places, factories and other environments. When there is a fire alarm, the module
can send an alarm signal to the controller through wireless communication technology after receiving the
closing signal, or it can output the closing signal to connect to other equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation.If this equipment
does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on,the user is encouraged to try to correct the interference by one or more of the
following measures:
--Reorient or relocate the receiving antenna.
--Increase the separation between the equipment and receiver.
--Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
--Consult the dealer or an experienced radio/TV technician for help.
Important: You are cautioned that changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate the equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Any Changes or modifications not expressly approved by the party responsible for compliance could void
the user's authority to operate the equipment.
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
2
II. Features
1. Adopting 470MHz wireless communication technology, no need to pre-buried wiring, easy and quick
engineering installation;
2. With battery low-voltage detection function, it can reflect the battery power status in time;
3. Use microprocessor to realize signal processing, and use digital signal to communicate with controller,
work stably and reliably, and have good suppression ability against electromagnetic interference.
III. Technical specifications
1. Battery type:CR17450(wired)
2. Rated working voltage:3.0V
3. Working Current:Standby Current≤14uA Alarm Current≤10mA
4. Indicators:Input light: red, always on when there is an input signal
Output light: red, always on when output action
Fault Indicator: yellow, flashing when the module is faulty
Working Indicator: Green, flashing when communication is normal
Note: When all the lights in this manual are flashing, the lights will turn on once every 200ms
5. Coding Method: The controller is automatically assigned during networking
6. Communication method: 470MHz FSK coded two-way communication
7. Communication distance:≤50m
8. Transmitted power:<20dBm
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
3
9. Reset method: by control panel
10. Application environment:
Type:indoor Atmosphere pressure:86kPa~106kPa
Temperature:-10℃~+55℃Relative humidity≤95%,non-condensing
11. Outline dimension:101mm×137mm×43mm
12. Material and color:ABS, off-white
13. Weight:about 170g (including battery)
14. Executive standard:GB 16806-2006 "Fire Linkage Control System"
XF 1151-2014 "General Requirements for Wireless Communication Functions of Fire
Alarm Systems"
IV. Structure characteristics and working principle
1. The outline diagram of the module is shown in Figure 1 :
Figure 1 Outline diagram of the module
2. Working principle
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
4
When the module input terminal receives the closing signal, it sends an alarm signal to the control panel
through wireless communication technology, and the module input indicates that the red light is always
on.
When the module receives the control signal from the control panel, the module outputs a closing signal
to connect to other devices, and the module output red light is always on.
When the module battery is low, the module sends a battery undervoltage signal to the control panel,
and the fault yellow light flashes.
3.Installation method
1. Before installation, first check whether the shell is intact and whether the identification is complete.
2. Module fixing method:
When installing, use two screws to fix the module base on the 86 series (width 72mm, height 49mm,
depth 47mm) embedded box, and then install the button front panel, the installation hole distance is
60mm.
Fig.2 Installation method
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
5
Fig.3 Installation hole distance
AS1,AS2: Passive answer signal input
OUT1,OUT2: Passive normally open output
Fig.4 Wiring diagram
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
6
V. Test
Warning: Please make sure that the polarity of the battery is correct before proceeding.
1. After the module is installed and tested every year during use.
2. Alarm test: After the networking is successful, choose a module to artificially make it meet the alarm
conditions (please turn off the fire alarm linkage function to avoid unnecessary alarm linkage), after the
test, power on again, and notify the relevant management department Restore the system to normal.
3. During the test, the unqualified modules are resolved according to "general failure and repair" and
"maintenance".
VI. Use and operation
1. Network segment setting: The device network segment should be set before the module accesses the
network. In the network setting interface of the control panel menu, set the module access network
segment according to the actual situation on site.
2. The device enters and exits the network:
A) Network access operation: When the control panel is in the "wireless registration interface" and the
module is not connected to the network, quickly press the "Settings" button 3 times, and the green light
flashes 3 times, the module sends a network access application to the control panel, application After
success, the total number of network access displayed by the control panel +1.
B) Network exit operation: When the control panel is in the "wireless registration interface" and the
module is in the network access state, press the "Settings" button 3 times in rapid succession, and the
green light flashes 3 times, the module sends a exit to the control panel After the application is successful,
the total number of withdrawals displayed by the control panel will be +1.
C) Status detection: After the module is powered on, press the "Settings" button once and the green light
flashes once. If the control panel responds to the device, it indicates that the module has successfully
connected to the network, otherwise the module is not connected to the network.
3. Equipment alarm: When the module input terminal receives the closing signal, it sends an alarm signal
to the control panel through wireless communication technology, and the module input red light is
always on.
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
7
4. Output start: when the module receives the control signal from the control panel, the module outputs
a passive close signal, which can be connected to other devices, and the module output red light is
always on.
5. Device reset: power on again.
6. Restore factory settings: After the module is connected to the network, when it is powered on again,
the output red light will be on for 10s. During this period, you can restore the factory settings by pressing
the setting button 5 times. The factory restoration is successful, and the output red light will flash 3
times.
7. Whether the output is detected or not: After the module is connected to the network, when it is
powered on again, the output red light will stay on for 10s. During this period, click the setting button 3
times to turn off the output fault detection, and the yellow light will flash 3 times when the setting is
successful. (Note: If the output failure detection has been set to turn off, the above operation can turn on
the failure detection)
VII. General failure and repair
General faults and their solutions are shown in the table below:
Fault
Reason
Solution
Faulty yellow light flashes once
every 48s
Low battery
Change the battery
Faulty yellow light flashes twice
every 48s
Too far away from the controller or
interference sources nearby
Move the module near the controller
to eliminate the source of interference
Faulty yellow light flashes three
times every 48s
A fault is detected at the input of
the module
10K resistors are serially connected to
the input of the module
Faulty yellow light flashes four
times every 48s
A fault is detected at the output of
the module
Input 24V power at the output of the
module
Faulty yellow light flashes five
The module detects the
Refer to the above solutions to solve
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
8
times every 48s
above-mentioned multiple faults
one by one
After the device alarms, the
controller has no status prompt
The device is not connected to the
network
Restart the network operation
Device networking is
unsuccessful
Too far away from the controller or
interference sources nearby
Move the device near the controller,
reconnect to the network and remove
the source of interference
The fault yellow light keeps
flashing
The battery is low and the device is
not working properly
Change the battery
VIII. Notes
1. After the signal passes through the wall, the signal strength will be greatly attenuated, so try to reduce
the number of partition walls for wireless products.
2. When installing the product, keep it away from metal to reduce the shielding of metal objects to the
signal. For example, it cannot be installed in a metal box such as a fire hydrant box or outside of a metal
cabinet.
3. Install in a low-interference environment and far away from motors or large-scale electrical
equipment.
IX. Documents and warranty instructions
1. Packing documents: 1) Packing list: 1
2) Instructions: 1 copy
3) 10K resistance: 1
2. Warranty: Our company is responsible for the maintenance of this product. If you find any problems,
please contact our company's technical service department in time. Users are not allowed to disassemble
or repair by themselves, otherwise they will be responsible for the consequences.
3. The maintenance contact information is as follows:
JTY-GM-TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1.0 202010
辽宁•营口天成消防设备有限公司
9
Liaoning·Yingkou Tiancheng Fire Equipment Co., Ltd.
Address: No. 11-2, Kechechang Xili, Xishi District, Yingkou, Pilot Free Trade Zone (Liaoning) China , City
Fax: 0417-4835568
Postcode: 115004
Tel:400-6930-119
Email: [email protected]
Website: www.tcfiretech.com

Other Tiancheng Fire Protection Equipment I/O System manuals

Tiancheng Fire Protection Equipment TCSG5270 User manual

Tiancheng Fire Protection Equipment

Tiancheng Fire Protection Equipment TCSG5270 User manual

Popular I/O System manuals by other brands

ICP DAS USA EC2-C32 quick start

ICP DAS USA

ICP DAS USA EC2-C32 quick start

Rockwell Automation Allen-Bradley 1790D-N4CO manual

Rockwell Automation

Rockwell Automation Allen-Bradley 1790D-N4CO manual

National Instruments NI REM-11100 Getting started guide

National Instruments

National Instruments NI REM-11100 Getting started guide

Banner SureCross DX80 manual

Banner

Banner SureCross DX80 manual

CTI 2550-A Installation and operation guide

CTI

CTI 2550-A Installation and operation guide

Advantech WISE-4210 Series Startup manual

Advantech

Advantech WISE-4210 Series Startup manual

Jung KNX 2214REGA-01 operating instructions

Jung

Jung KNX 2214REGA-01 operating instructions

M-system R3-PC16A instruction manual

M-system

M-system R3-PC16A instruction manual

M-system R7I4DML3-DA32A instruction manual

M-system

M-system R7I4DML3-DA32A instruction manual

Beckhoff EPP4374-0002 manual

Beckhoff

Beckhoff EPP4374-0002 manual

Helm C Series installation instructions

Helm

Helm C Series installation instructions

M-system R7M-DAC16C-R instruction manual

M-system

M-system R7M-DAC16C-R instruction manual

YASKAWA VIPA SLIO SDI operating manual

YASKAWA

YASKAWA VIPA SLIO SDI operating manual

Phoenix Contact FLS FLM PB SYS PRO UM E user manual

Phoenix Contact

Phoenix Contact FLS FLM PB SYS PRO UM E user manual

turck BL20-E-4IOL operating instructions

turck

turck BL20-E-4IOL operating instructions

Campbell SDM-AO4A product manual

Campbell

Campbell SDM-AO4A product manual

aci ANALOG INTERFACE Series Installation & operation instructions

aci

aci ANALOG INTERFACE Series Installation & operation instructions

FireClass FC410SIO installation manual

FireClass

FireClass FC410SIO installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.