4.Safety
•Connect the input and output wires only when mains are not connected
•To prevent fire spreading in case of shortcut, the hub must be installed in a suitable enclosure
without any openings at the bottom.
•Connect mains only to 110-230Vac power source
•All AC connections should be done by an authorized electrician
•The unit intends to be powered from building wiring in Overvoltage Category . f the unit is
installed in Overvoltage Category higher than , external overvoltage protective device compliant
with EC 61643 standard and NEC/CEC shall beprovided in building installation to reduce mains
transients to Overvoltage Category .
1.Supply disconnect switch
A supply disconnect switch, or a circuit breaker must be installed at the connection point of the
power cable to the mains. Circuit breaker should be a standard device with the following
characteristics - 2A 110/230VAC 50/60Hz. An example - S201M-C4NA by ABB. The switch should be
in close proximity to the hub within easy reach for the operator. A marking should be added on the
switch identifying it as a disconnection device for the hub.
5.Environmental characteristics
•The Hub is intended for indoor use only. For outdoor application a weatherproof external enclosure
should be added.
•nstallation site altitude will be up to 2000m.
•Temperature range should be -40- +70 deg C. For harsher temperatures an external temperature
controlled enclosure should be added.
•Maximum relative humidity 80% for temperatures up to 31 deg C decreasing linearly to 50%
relative humidity at 40 deg C.
•Mains supply voltage fluctuations up to +-10% of the nominal voltage.
•Overvoltage category
•Pollution Degree 2
Page 10 MiniHub User Guide 2/18/2013