Page 3of 5
MT300 Quickstart Guide (1) Tel: 905.457.6322 ●Fax: 905.457.4716 ●www.mod-tronic.com
: Input types; (T/C type K), (T/C type E), or . Channel being set is
indicated on far left digit.
: Amount of offset in degrees to apply to each channel
: or scale
: What channel to display in normal running mode
: 4-20mA loop settings
oLoop or internal power
oChannel to display
o: Zero point
o: Span
: Number of minutes for AUDIBLE SILENCE button to silence beeper
: Channel 1, trip setup a
o: This trip settings enable/disable. Skips rest of settings if set to disable
o: Trip on error enable/disable
o: Fan output enable/disable
o: Alarm output enable/disable
o: Trip output enable/disable
o: Beeper output enable/disable
o: Setpoint
o/: Whether to trip over or under the trip point
o/: Whether this trip setup can be untripped by hysteresis, or if it requires pressing CANCEL
o: Hysteresis for untrip (only displayed if previous is set to )
: Channel 1, trip setup b
oSame as previous, and same with remaining
: Channel 1, trip setup c
: Channel 2, trip setup a
: Channel 2, trip setup b
: Channel 2, trip setup c
: Channel 3, trip setup a
: Channel 3, trip setup b
: Channel 3, trip setup c
: MODBUS setup
o(first parameter): MODBUS node ID number
o(second parameter): Communication bitrate or USB
: fan exerciser
o: Period in days, or disable
o: Duration, in hours
: Manual fan timeout in minutes