M7829 Operating Manual
4
1
10 1112
2345678
+
+24
25m
O
IN
mA
C. Adjusting the alarm limits
1. Press either the -or the ¯buttononthe front panel.
The corresponding alarm limit is shownondisplay.
2. Now adjust the requested alarm limit withthe corresponding screw located onthe
right hand side of the front panel.
D. Displayand signal output adjustment
Fouradjustmentscrews are ontheback panel. Do not change these settings as they
have beenexactly adjusted at the factory or by the panelbuilder.
If, however, the instrument needs to be adjusted, proceed as follows:
1) set the input signalto the lowest possible value
2) adjust thedisplay withthe"DVM MIN". screw andthesignaloutputwiththe"mA
MIN" screw.
3) set theinputsignalto maximumvalue, adjust thedisplay withthe"DVM MAX"
screw and the signaloutput withthe "mA MAX" screw.
Back panel withthe terminals
V1.01 02.12.02