Alarm conditions
When a fault condition occurs the alarm relay is activated, in addition to light and sound. With
DIP-switch 1 in OFF position all sound warnings will be deactivated. The alarm relay will stay
activated as long as one or more alarm conditions exist. Sound and LED light signals are
activated according to priority.
Priority example:
Mains power off, starts Alarm 2. If the cabinet door opens, Alarm 1 starts ( higher priority ).
When the door is closed, status goes back to Alarm 2. But if the mains input falls out whilst the
door is open , Alarm 2 will not occur until the door is closed.
The following alarm conditions are listed according to priority:
Alarm 1
ON when Off when Light Sound
Door opens Door closed Only sound 7 beeps, pause, 7
beeps, pause, ...
Alarm 2
On when Off when Light Sound
Mains off.
Time delay for
alarm-relay DIP-
switch:
- 0 min (All DIP off)
- 15 min (DIP 2)
- 30 min (DIP 3)
- 60 min (DIP 4)
Mains on Green LED
flashes. Pattern
depends on
battery voltage
6 beeps, pause, 6
beeps, pause, ...
Alarm 3
On when Off when Light Sound
Current overload
> 5A Current under
limit Overloaded LED
flashes 5 beeps, pause, 5
beeps, pause, ...
Alarm 4
On when Off when Light Sound
Temperature over
55 degrees Temperaure
under 50 degees Temperature LED
flashes 4 beeps, pause, 4
beeps, pause, ...
Alarm 5
On when Off when Light Sound
Battery voltage
too low (automatic
test)
Battery voltage
OK with manual
or automatic test
Battery status
LED, red 3 beeps, pause, 3
beeps, pause, ...
Alarm 6
On when Off when Light Sound
Battery more than
3 years old Power-on reset Alternative red/
green battery
status -LED
2 beeps, pause, 2
beeps, pause, ...