
The 3/4” I.D. flexible tubing included should be connected to the
Comfort Pack drain connection so that it can easily be discon-
nected if the cooling chassis must be removed. A trap at least
2” deep should be provided close to the drain pan. The tubing
should not be higher than the bottom of the unit drain pan at
any point to assure proper drainage and allow chassis removal.
The drain line should pitch downward at least 1” per 10 ft. to an
open building drain trap.
The trap and 3” piece of clear flexible1. 1/2” ID tubing
are shipped loose to prevent damage. They should be
installed after the Comfort-Pack unit is installed and the
return air connection completed.
The trap must be primed (filled with water) for proper2.
operation of the secondary drain system. This may be
done prior to installation of the trap or after.
Position the trap as shown below and slide the 3” piece3.
of clear flexible about 1 1/2” onto the top end of the trap.
Install the other end of the trap through the grommet
in the slide-out chassis under the indoor coil drain pan.
Slide the top of the flexible tube on the trap onto the
bottom of the 1/2” OD secondary drain connection and
push the top of the trap up. The trap should be positioned
so that there is only a small gap between the top of the
trap and the bottom of the secondary drain connection.
To avoid damage whenever the slide-out chassis has to4.
be removed from the cabinet, remove the secondary drain
trap before sliding the chassis out. After the chassis is
reinstalled in the cabinet, prime the trap with water before
reinstalling it.
All wiring must be installed in accordance with applicable
codes.
The unit is factory wired for 230/1/60 power. For 208/1/60
power systems, the wiring to the primary side of the control
transformer should be changed from the 240-volt connection
to the 208-volt connection to provide proper operation of the
control system.
The operating voltage of the unit is from 197 to 253 volts.
Operating the equipment outside of these limits will void the
warranty.
Field wiring between the unit and the wall thermostat (by others)
may be low voltage for Class 2 systems. The location of the wall
thermostat should be 4 to 5 feet above the floor and carefully
selected so that the thermostat senses the temperature of the
largest conditioned area, without being influenced by drafts, sun
exposure or outside temperature.
Air Filter
The 16” x 25” x 1” filter on the cooling chassis must be
maintained regularly to assure that the unit provides optimal
performance and energy efficiency. The intervals between
replacing depends entirely on the cleanliness of the return air
to the unit and the time that the indoor blower operates. The
air filter is accessible by removing the lower access panel. The
filter should be inspected and replaced as needed and is not
washable. Substituting the air filter with media other than the
type provided with the unit is not recommended, since other
materials may cause additional static pressure, which could
reduce the air delivery of the unit. The unit should never be
operated without the air filter and access panels in place.
Cooling Chassis
The cooling chassis contains all items related to the cooling
functions of the unit, and also contains the indoor blower and
motor for the heating function. For extensive servicing, qualified
personnel may choose to remove the cooling chassis from the
unit and take it to a work area. Spare chassis are recommended
so that extensive servicing can be performed outside the living
space. This will prevent introducing dirt or doing damage in the
living area, and could help to eliminate significant disruption of
the air conditioning and heating functions in the living areas.
The indoor blower motor and the outdoor fan motor have
permanently lubricated bearings and do not require routine
service. The refrigeration system is sealed and factory charged
with Refrigerant 22 so that routine maintenance is not required.
Cleaning of the outdoor coil, indoor coil, drain pan, and inside
the bottom of the chassis are recommended at least once a
year, and more often if the equipment is operated in a dusty
or hostile environment. The electrical controls do not require
routine service.
Power to the unit should always be turned off before
performing service or removing the cooling chassis from
the unit. One power connector and one control circuit connector
are provided for easy disconnecting and re-connecting of the
3
Electrical
Controls
Maintenance
Drain Connection
Drain Pan
Pitch Downward 1” per 10’
3/4” O.D. Drain Connection
Highest point must not be above
bottom of drain pan
3/4” I.D. Flexible Tubing Included
Dotted line represents components provided and installed by others
2” min.
Optional Secondary Drain Trap
Install Instructions
Secondary Drain Connection Drain Pan
1/2” I.D. Tubing
Grommet
Chassis Base
Trap