15
3.1 Choosing an Installation Location
When choosing an installation location, you must ensure that
the location provides adequate clearancefor the water heater,
adequate ue and drainage options, and sucient access to gas,
water, and electrical supplies.
Carefullyconsider the following factors when choosing an
installation location:
Compliance Requirements
This water heater must be installed by qualied personnel
in compliancewith the applicableLaws and Regulations.
In general,these Laws and Regulations are the Basic Gas
Installation Standards, the Heating, Air Conditioning and
Domestic Water Installation Regulation and all other local
regulations.
Access to Utilities
Water–the installation location shouldbe near where the
domestic water supplyenters the building.
Gas–the installation location shouldbe near where the gas
supplyenters the building.
Electricity–the installation location shouldbe near where the
electrical supplyenters the building.
Humidity and Contact with Water
When installing the water heater, avoid places with excessive
humidity. The water heater has electric gas ignition components.
Water spray or droppings can get inside the water heater and
damage the ignition system. The water heater must be installed
in away to ensure that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.) during
operation and service.
If the water heater is installed in avery humid room (a shower
room or bathroom, for example), the Low Voltage regulation
and the Technical Building Code must be observed for correct
installation.
Proximity to Fixtures and Appliances
Install the water heater near xtures that deliver or use hot
water, suchas bathroom, kitchen, and laundry room faucets.
Selectalocation that minimizes the water piping required
between major xtures. If the distances are long or if the user
requires “instant“ hot water, installation of arecirculation line
whichcirculates domestic hot water backto the water heater
from the furthest xture is recommended. Insulate as muchof
the hot water supplyand recirculation lines as possible.
Adequate Drainage
The water heater produces asigni cant amount of condensate
during operation. This condensate must be removed from
the water heater, and suitablytreated if national legislation
so requires. The water heater shouldbe located near a
suitabledrain and where damage from apossibleleak
will be minimal.Installing the water heater in alocation
without adrain will void the warranty and Navien will not
be responsiblefor water damage that occur as aresult.
For more information about condensate drainage, refer to
“3.5 Connecting the Condensate Drain Line” on page 27.
The water heater must be located in an area where leakage of
the unit or connections will not resultin damage to the area
adjacent to the applianceor to lower oors of the structure.
When suchlocations cannot be found, installation of an
adequatelydrained drain pan under the water heater is highly
recommended. When installing the drain pan, ensure that the
installation does not restrictcombustion air ow.
Adequate Flue and Ventilation
Selectalocation that requires minima ue. Consider ue
restrictions caused by windows, doors, air intakes, gas meters,
foliage, and other buildings. For more information about ue
system, refer to “3.6 Flue System” on page 28.
Toensure adequate ue and ventilation, follow these guidelines:
Maintain proper clearances from any openings in the building.
Install the water heater with aminimum clearanceof 300 mm
above an exterior grade or as required by local codes.
Do not enclose the ue termination.
Install the exhaust ue in an area that is free from any
obstructions, where the exhaust will not accumulate.
Do not install the water heater where moisture from the
exhaust may discolour or damage walls.
Do not install the water heater in bathrooms, bedrooms or
any other occupied rooms that are normallykept closed or
not adequatelyventilated.
The requirements and recommendations stipulated in the
Regulation for Heating Installations in Buildings (RITE) and any
other applicablelegislation in this eldmust be observed.
No specic ventilation is required in the room the water
heater is installed in. If it is installed in acupboard or
compartment, no specic ventilation is required, providing the
aforementioned dimensions are observed. The requirements
and recommendations stipulated in the Regulation for Heating
Installations in Buildings (RITE) and any other applicable
legislation in this eldmust be observed.
3. Installing the Water Heater
Installing the Water Heater