Nederma Airflow Alarm Kit User manual

User Manual
Airflow monitoring and measuring
Airflow Alarm Kit
www.nederman.com
A L A R M O N
P O W E R
FA I L U R E
Originaluser manual
EN USER MANUAL
Translation of originaluser manual
DA BRUGERVEJLEDN NG
DE BED ENUNGSANLE TUNG
ES MANUAL DE USUAR O
PL NSTRUKCJA OBSŁUG
SV ANVÄNDARMANUAL
2022-11-25 2130059 (06)
EN
DA
DE
ES
PL
SV

Airflow Alarm Kit
Trace back information:
Workspace Main version a73
Checked in 2022-11-25
Skribenta version 5.5.022

Airflow Alarm Kit
Declaration of Conformity ........................................................ 4
Figures .......................................................................................... 6
English ........................................................................................... 10
Dansk ............................................................................................. 20
Deutch ........................................................................................... 30
Español .......................................................................................... 40
Polski ............................................................................................. 50
Svenska ......................................................................................... 60
3

Airflow Alarm Kit
Declaration of Conformity
EN Englis
Declaration of Conformity
We, AB Ph. Nederman & Co., declare under our sole responsibility that
the Nederman product:
Airflow Alarm Kit (Part No. **, and stated versions of **) to which this
declaration relates, is in conformity with all the relevant provisions of
the following directives and standards:
Directives
2014/35/EU, 2014/30/EU, 2011/65/EU.
Standards
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO
20607:2019
The name and signature at the end of this document is the person re-
sponsible for both the declaration of conformity and the technical file.
DA Dansk
Overensstemmelseserklæring
AB Ph. Nederman & Co., erklærer som eneansvarlige, at følgende pro-
dukt fra Nederman:
Airflow Alarm Kit (Artikel nr. **, og erklærede versioner af **), som den-
ne erklæring vedrører, er i overensstemmelse med alle de relevante
bestemmelser i de følgende direktiver og standarder:
Direktiver
2014/35/EU, 2014/30/EU, 2011/65/EU.
Standarder
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO
20607:2019
Navnet og underskriften sidst i dette dokument tilhører den person,
der er ansvarlig for såvel overensstemmelseserklæringen som den tek-
niske dokumentation.
DE Deutc
Konformitätserklärung
Wir, AB Ph. Nederman & Co., erklären in alleiniger Verantwortung, dass
das Nederman Produkt:
Airflow Alarm Kit (Art.-Nr. **, und bauartgleiche Versionen **), auf wel-
ches sich diese Erklärung bezieht, mit allen einschlägigen Bestimmun-
gen der folgenden Richtlinien und Normen übereinstimmt:
Ric tlinien
2014/35/EU, 2014/30/EU, 2011/65/EU.
Standards
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO
20607:2019
Der Name und die Unterschrift am Ende dieses Dokuments sind die für
die Konformitätserklärung und die technischen Unterlagen verant-
wortlichen Personen.
ES Español
Declaración de Conformidad
Nosotros, AB Ph. Nederman & Co., declaramos bajo nuestra exclusiva
responsabilidad que el producto de Nederman,
Airflow Alarm Kit (Ref. n.º ** y las versiones indicadas de **), al que ha-
ce referencia esta declaración, cumple con todas las provisiones rele-
vantes de las Directivas y normas que se indican a continuación:
Directivas
2014/35/EU, 2014/30/EU, 2011/65/EU.
Normas
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO
20607:2019
El nombre y firma que figuran al final de este documento corresponden
a la persona responsable, tanto de la declaración como de la ficha técni-
ca.
PL Polski
Deklaracja Zgodności
My, AB Ph. Nederman & Co. niniejszym oświadczamy na naszą własną
odpowiedzialność, że Nederman produkt:
Airflow Alarm Kit [nr części ** oraz wskazane wersje **], który jest
przedmiotem niniejszej deklaracji, spełnia wszystkie odpowiednie wy-
magania wymienionych niżej dyrektyw i norm:
Dyrektywy
2014/35/EU, 2014/30/EU, 2011/65/EU.
Normy
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO
20607:2019
Na końcu niniejszego dokumentu znajdują się imię i nazwisko oraz pod-
pis osoby odpowiedzialnej za deklarację zgodności oraz dokumentację
techniczną.
SV Svenska
Överensstämmelsedeklaration
Vi, AB Ph. Nederman & Co., förklarar under vårt fulla ansvar att Neder-
man-produkten:
Airflow Alarm Kit (artikelnummer **, och angivna versioner av **) som
denna deklaration avser, är i överensstämmelse med alla relevanta be-
stämmelser i följande direktiv och standarder:
Direktiv
2014/35/EU, 2014/30/EU, 2011/65/EU.
Standarder
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO
20607:2019
Namnet och signaturen i slutet av detta dokument är den person som
ansvarar för både försäkran om överensstämmelse och den tekniska fi-
len.
**
40780434, 40780435, 40780436, 40780437, 40780438, 40780439, 40780440, 40780441
AB Ph. Nederman & Co.
P.O. Box 602
SE-251 06 Helsingborg
Sweden
Anna Cederlund
Product Center Manager
Technical Product Management
2022-11-25
4

Airflow Alarm Kit
UK Declaration of Conformity
We, AB Ph. Nederman & Co., declare under our sole responsibility that the Nederman product:
Airflow Alarm Kit (Part No. **, and stated versions of **) to which this declaration relates, is in conformity with all the relevant pro-
visions of the following regulations and standards:
Relevant legislation
Electrical Equipment (Safety) Regulations 2016, Electromagnetic Compatibility Regulations 2016, The Restriction of the Use of
Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012
Standards
EN 60730-1:2012, EN 61000-6-3:2007, EN 61000-6-1:2007, EN SO 20607:2019
The name and signature at the end of this document is the person responsible for the declaration of conformity.
The UK importer is authorised and responsible to compile the technical file.
**
40780434, 40780435, 40780436, 40780437, 40780438, 40780439, 40780440, 40780441
AB Ph. Nederman & Co.
P.O. Box 602
SE-251 06 Helsingborg
Sweden
Anna Cederlund
Product Center Manager
Technical Product Management
2022-11-25
UK mporter:
Nederman Ltd
91 Seedlee Road,
Walton Summit Centre,
Bamber Bridge,
Preston,
Lancashire,
PR5 8AE
5

Airflow Alarm Kit
Figures
www.nederman.com
A L A R M O N
P O W E R
FA I L U R E
1
2
3
4
5
6
1
6

Airflow Alarm Kit
PSU2L
PSU2N
PSU1L
PSU1N
Alarm NO
Alarm C
Alarm NC
1 5 6 7
Output
12 VDC
Fan Constant
80-230VAC Power
Input
80-230 VAC
2 3 4
P-SW
P-SW
GND Out Alarm
+12V Out Alarm
8
3 2
OPS Alarm Flash
Open = Alarm
9 10 11
Output
12 VDC
Input
80-230 VAC
Relay in alarm
state
GND_DC
+12V
Black
Red
+
−
85- 230 VAC
fan on 85- 230 VAC
Power
Central
surveillance
COM
2 NO
1 NC
P
3
21 3 4 5
2
7

Airflow Alarm Kit
Pressure switch
Airflow alarm and pressure switch mounted
Airow alarm
1
2
3
8

Airflow Alarm Kit
P
V
PS
V
-10%PS
90%-95%
4
9

Airflow Alarm Kit
EN Englis
User Manual
Table of contents
Figures ............................................................................................................................................................................. 6
1 Preface ............................................................................................................................................................................ 11
2 Safety .............................................................................................................................................................................. 11
2.1 Classification of important information ......................................................................................................... 11
3 Description ..................................................................................................................................................................... 11
3.1 ntended use ....................................................................................................................................................... 11
3.2 Function ............................................................................................................................................................... 11
3.3 Main parts ............................................................................................................................................................ 11
3.3.1 Airflow Alarm - Control box ................................................................................................................ 11
3.4 Technical data ..................................................................................................................................................... 12
4 nstallation ...................................................................................................................................................................... 13
4.1 Control box .......................................................................................................................................................... 13
4.2 Electrical connections ....................................................................................................................................... 13
4.3 Monitoring point ................................................................................................................................................. 13
4.4 Startup ................................................................................................................................................................. 13
4.4.1 Adjustment ........................................................................................................................................... 13
5 Use ................................................................................................................................................................................... 14
5.1 Control box LEDs and indications .................................................................................................................... 15
6 Maintenance .................................................................................................................................................................. 16
7 Troubleshooting ............................................................................................................................................................ 17
8 Spare Parts ..................................................................................................................................................................... 18
8.1 Ordering spare parts .......................................................................................................................................... 18
9 Recycling ......................................................................................................................................................................... 18
10 Control protocol for Airflow Alarm ............................................................................................................................. 19
10

Airflow Alarm Kit
1Preface
Thank you for using a Nederman product!
The Nederman Group is a world-leading supplier and
developer of products and solutions for the environ-
mental technology sector. Our innovative products
will filter, clean and recycle in the most demanding of
environments. Nederman's products and solutions will
help you improve your productivity, reduce costs and
also reduce the impact on the environment from in-
dustrial processes.
Read all product documentation and the product iden-
tification plate carefully before installation, use, and
service of this product. Replace documentation imme-
diately if lost. Nederman reserves the right, without
previous notice, to modify and improve its products
including documentation.
This product is designed to meet the requirements
of relevant EC directives. To maintain this status, all
installation, maintenance, and repair is to be done
by qualified personnel using only Nederman original
spare parts and accessories. Contact the nearest au-
thorized distributor or Nederman for advice on tech-
nical service and obtaining spare parts. f there are
any damaged or missing parts when the product is de-
livered, notify the carrier and the local Nederman rep-
resentative immediately.
2Safety
2.1Classification of important informa-
tion
This document contains important information that
is presented either as a warning, caution or note, ac-
cording to the following examples:
WARNING!Risk of personal injury
Warnings indicate a potential hazard to the
health and safety of personnel, and how that
hazard may be avoided.
CAUTION!Risk of equipment damage
Cautions indicate a potential hazard to the
product but not to personnel, and how that
hazard may be avoided.
NOTE!
Notes contain other information that is import-
ant for personnel.
3Description
3.1Intended use
The Airflow Alarm monitors pressure conditions in a
suitable duct.
3.2Function
The Airflow Alarm is connected to a fan starter so that
Airflow Alarm starts to monitor automatically and sim-
ultaneously with the fan. The alarm is activated when
the static pressure in the duct is outside preset limits.
The Airflow Alarm can either monitor one particular
exhaust point at a workplace or a group of workplaces
connected to a single air duct leading to the fan.
3.3Main parts
See Figure1. The Airflow Alarm Kit consists of:
1 Airflow Alarm - Control box.
2 Pressure switch. Available as a standard model,
and an ATEX-approved model for zone 2/22.
3 Protection filter.
4 Rubber fitting
5 Flashlight (optional)
6 Cable gland (optional)
3.3.1 Airflow Alarm - Control box
See Figure2. The Airflow Alarm contains a terminal
block that includes connections to:
1 85-230 VAC power supply (Phase 1). Signal in from
fan to activate monitoring.
2 85-230 VAC power supply (Phase 2). Power into
Airflow Alarm.
3 External connection to central surveillance (Op-
tional)
4 Pressure switch
5 External Airflow Alarm devices, such as a flash-
light
NOTE!
Drill an extra hole and install a cable gland if the
Control box is to be directly connected to both
a flashlight and central surveillance. See Fig-
ure1 (6).
EN
11

Airflow Alarm Kit
EN 3.4Tec nical data
Part Description
Supply PSU1 85 - 230V AC, 50-60Hz, max. 13A Fuse
Supply PSU2 85 - 230V AC, 50-60Hz, max. 13A Fuse
Pressure switch External contact must be below 100 Ohm
12 V DC out alarm 12 V DC maximum 200 mA
Alarm relay Maximum 8A AC1 250 VAC
9V battery 6LR61, non-rechargeable
Dimensions 120 mm x 170 mm x 60 mm
Fuse 5 x 20 T500mA
Operating temperature 0 - 50 °C
P Class Control box P54
P Class Pressure Switch Standard P54
P Class Pressure Switch ATEX P65, ATEX model approved for zone 2/22.
12

Airflow Alarm Kit
4Installation
nstallation, repair and maintenance work is to be car-
ried out by qualified personnel using only original Ne-
derman spare parts. Contact your nearest authorized
distributor or Nederman for advice on technical ser-
vice.
4.1Control box
Figure3 shows the Airflow Alarm and pressure switch
mounted.
1 Pressure switch
2 Airflow alarm
NOTE!
• Before starting installation, an unused volts-
free contact from the fan starter should be
wired through to the Fan ON position.
• The Airflow Alarm control box must be in-
stalled outside the ATEX classified zone.
• The optional flashlight should be situated at
a location visible from the workplace(s) mon-
itored.
• The electrical enclosure should be mounted
near the workplace so that the alarm LEDs
can be clearly seen and noted from the oper-
ator’s working place.
• f the operator does not have a permanent
place or where several working places are su-
pervised by one alarm, a flashlights should
be installed so that the alarm may be clearly
seen from the operator’s working places.
4.2Electrical connections
WARNING!Risk of personal injury
Work with electric equipment is to be carried
out by a qualified electrician.
Figure2 shows the wiring diagram and cabling for ter-
minals for the Airflow Alarm.
Electrical connections between components should
comply with current national regulations.
4.3Monitoring point
WARNING!Risk of personal injury
• f there is flammable dust present, turn off
the fan.
• Eliminate ignition sources such as heat or
sparks.
• Wear a dust mask.
NOTE!
• A non-ATEX-approved differential pressure
switch must be installed outside of an ATEX
classified zone.
• Any screws or other fixings used into the air
duct must not cause any collection of dust/
chips. f the differential pressure switch
housing is conductive, there needs to be con-
tact between the pressure switch housing
and the metal duct or ground.
The monitoring point is selected as follows:
W en monit-
oring Location
One single
workplace Between dust extraction point,
such as a suction hood, and a
connection to the duct system.
A group of
workplaces Close to the connection point
farthest away from the fan. See
Figure3.
The pressure switch can be mounted on the air duct.
NOTE!
When drilling in air ducts, safety regulations
must be kept in mind.
The hose is connected to the hose connection on the
pressure switch marked with a minus (-) sign. Nothing
is connected to the hose connection marked plus (+)
atmospheric pressure.
4.4Startup
When the fan starts, the alarm is activated, and the
ALARM LED remains lit until the required pressure is
reached. The ON LED is also lit.
4.4.1Adjustment
1 A suitable part of the duct is selected, and a hole
for the protection filter is drilled close to the last
connection point. See Chapter4 nstallation.
2 The maximum airflow according to the order ac-
knowledgement, technical specifications etc.
must be determined and the corresponding air ve-
locity calculated.
3 The air velocity is measured with the planned
number of extraction points open. f the airflow is
larger than (V0), reduce the airflow. For example,
this can be done by inserting a plate in front of the
fan outlet flange to reduce the airflow until the
airflow (V0) planned is reached.
4 At this airflow, the static vacuum at the monit-
oring point (PS0) is measured, and the pressure
monitor is set 10% lower. See Figure4, where the
alarm limit setting is represented with the dotted
line.
EN
13

Airflow Alarm Kit
EN NOTE!
f the pressure switch measuring range
does not cover the setting value required,
the pressure switch is replaced by one with
a relevant measuring range.
5 The main airflow is reduced slowly by inserting the
plate in the fan outlet flange until the alarm is re-
leased.
6 The air velocity is measured and the airflow is cal-
culated. f it is between 90 and 95% of the airflow
specified, the adjustment has been completed.
7 f the airflow is less than 90% of the airflow spe-
cified, set the pressure switch 5% higher, and re-
peat item 5.
8 f the airflow is higher than 95% of the airflow
specified, set pressure switch 5% lower, and re-
peat item 5. t might be necessary to remove the
plate in front of the fan outlet flange.
9 When the adjustment has been completed,
note the following in the control protocol, see
Chapter10Control protocol for Airflow Alarm:
Make a copy of the control protocol for the Nederman
service technician.
5Use
WARNING!Risk of personal injury
f there is work with hazardous substances that
are assigned mandatory exposure limits and
there is a problem with the Airflow Alarm, stop
work immediately and fix the problem.
NOTE!
n the event of an alarm, the red ALARM LED
on the Airflow Alarm control box will be lit, and
any external connected alarm devices will be
activated. Stop work at once, find the cause
of the alarm, and fix the problem. See also
Chapter7Troubleshooting.
The Airflow Alarm limit has been set according to the
arrangement and operating parameters of the partic-
ular extraction system. Normally, the Airflow Alarm
limit will be at 90% airflow per workplace, 100% be-
ing the airflow specified. When monitoring a group of
workplaces, the airflow per workplace is an average
value. The Airflow Alarm limit setting is found in the
control protocol for the exhaust alarm.
The Airflow Alarm begins monitoring as soon as the
fan starter is activated, and monitors pressure condi-
tions in a suitable duct. The alarm is activated when
the static air pressure in the duct is outside the preset
limits.
When the cause of the alarm has been fixed, and the
static pressure in the duct returns to within the nor-
mal range, the alarm will turn off automatically, and
the Airflow Alarm will resume monitoring.
NOTE!
During normal operation, the green ON LED
should be lit, which indicates that the 230 V
source works. f the green ON LED is not lit dur-
ing normal operation, one of the 230 V sources
is defective and the red POWER FA LURE LED
will also be flashing. The 230 V source must be
fixed and reconnected at once. f changing a
fuse cannot solve the problem, contact an au-
thorized Nederman technician for assistance.
14

Airflow Alarm Kit
5.1Control box LEDs and indications
Indicator Lig t Description
ALARM Red Too low airflow in the system.
POWER FA LURE Red Problem with electrical supply to unit.
ON Green Unit active/standby. System is working.
Alarm LEDs Alarm Status PSU1
Fan PSU2
Constant P-SW Alarm
Out Relay Internal
battery
used
Fan OFF OFF ON Open/
Closed OFF
NO
5
6
7
NO
Operating mode:
Normal
Flow=OK
ON ON ON
(Closed) OFF
NO
5
6
7
NO
Low flow ON ON OFF
(Open) ON
NC
5
6
7
NO
Power failure ON OFF ON
(Closed) ON
NC
5
6
7
NO
Low flow
Power failure OFF ON OFF
(Open) ON
NC
5
6
7
NO
Power OFF OFF OFF OFF OFF
NC
5
6
7
YES
EN
15

Airflow Alarm Kit
EN 6Maintenance
nstallation, repair and maintenance work is to be carried out by qualified personnel using only original Neder-
man spare parts. Contact your nearest authorized distributor or Nederman for advice on technical service.
WARNING!Risk of personal injury
Before restarting, close and reconnect guards, doors/hatches, etc.
When any defective components are found, they should be replaced, and the unit re-adjusted by a Nederman
service technician. f the Airflow Alarm control box is defective, it must be replaced.
Maintenance Mont ly/Operating ours interval
Check that the green ON LED on the controller is lit during nor-
mal operation. Daily
Check correct start-up sequence. Airflow Alarm must be re-
leased immediately and stay active until the fan has reached
normal speed and vacuum has been built up in the system.
Daily
Check the hose and the protection filter between the pressure
switch and air duct for clogging. Blow air to clean if necessary. Every 3 months or 1,000 hours
Check the Airflow Alarm limit setting*.Every 12 months (annually)
*To be performed by qualified personnel.
16

Airflow Alarm Kit
7Troubles ooting
All troubleshooting and similar activities should only be performed by skilled personnel with knowledge of the
plant function and construction, and in accordance with safety regulations, maintenance instructions, etc.
Fault Possible cause Solution
Alarm occurring briefly at
startup Fan starts slowly. Alarm is activated for a maximum of 60 seconds dur-
ing startup. The alarm at startup may be considered
as a daily function check.
Alarm occurring periodic-
ally • Extraction system
overloaded by too
many exhaust points
being opened at the
same time.
• Extraction system
overloaded by a bad
connection on one or
more exhaust points.
• Protection filter regen-
eration occurs too in-
frequently.
• Airflow Alarm Kit limit
set too high.
• Shut unused exhaust points.
• Limit the number of exhaust points to the capacity
of the plant.
• Establish automatic dampers and connect control
with max. limit.
• Extend extraction system capacity.
• Re-establish correct connections such as smaller
hose diameter, longer hoses, hoses without holes,
etc.
• For plants with filter regeneration during opera-
tion: Reduce time interval between regeneration /
decrease cleaning start level.
• For plants with regeneration in breaks: Stop the
plant more frequently or establish regeneration
during operation.
• Call Nederman service technician.
Alarm activated perman-
ently or for extended
periods.
• Extraction system ca-
pacity less than before.
• Extraction system
overloaded by hav-
ing too many exhaust
points connected.
• Extraction system
overloaded by de-
fective connection on
one or more exhaust
points.
• The hose assembly
between air duct
and pressure switch
clogged.
• Airflow Alarm defect-
ive.
• Clean or replace clogged protection filter in the ex-
traction system.
• Clean clogged air ducts/fan.
• Replace flexible connections at the fan.
• Replace defective V-belt drives/fan motor.
• Fix or replace defective fan.
• Shut unused exhaust points.
• Limit number of exhaust points to plant capacity.
• Establish automatic dampers and connect control
with max. limit.
• Extend extraction system capacity.
• Re-establish correct connections, such as smaller
hose diameter, longer hoses, hoses without holes
etc.
• Check the hose and the protection filter between
the pressure switch and the air duct for clogging.
Blow air to clean if necessary.
• Call Nederman service technician.
EN
17

Airflow Alarm Kit
EN Fault Possible cause Solution
Alarm is not activated in
connection with startup
or when it is supposed to
be activated.
• No power supply.
• The hose/protection
filter is clogged.
• Hose assembly for
the pressure switch
clogged.
• Pressure switch de-
fective.
• Change the defective fuse.
• Have an electrician check the wiring system.
• Disconnect the pressure switch, and clean the
hose and protection filter. Recconect the pressure
switch.
• Check the hose and the protection filter between
the pressure switch and the air duct for clogging.
Blow air to clean if necessary.
• Call Nederman service technician.
• See also Section5.1Control box LEDs and indica-
tions.
The POWER FA LURE LED
is not lit. • A connection to the
voltage supply has
been cut off.
• Battery backup is de-
fective.
• See Section5.1Control box LEDs and indications.
• Change the fuse.
• Have an electrician check the voltage supply.
• Replace the battery.
8Spare Parts
CAUTION!Risk of equipment damage
Use only N$e$d$e$r$m$a$n$ original spare parts and ac-
cessories.
Contact your nearest authorized distributor or
N$e$d$e$r$m$a$n$ for advice on technical service or
if you require help with spare parts. See also
w$w$w$.$n$e$d$e$r$m$a$n$.$c$o$m$.
8.1Ordering spare parts
When ordering spare parts always state the following:
• The part number and control number (see the
product identification plate).
• Detail number and name of the spare part (see
w$w$w$.$n$e$d$e$r$m$a$n$.$c$o$m$/$e$n$/$s$e$r$v$i$c$e$/$s$p$a$r$e$-$p$a$r$t$-
$s$e$a$r$c$h$).
• Quantity of the parts required.
9Recycling
The product has been designed for component mater-
ials to be recycled. Different material types must be
handled according to relevant local regulations. Con-
tact the distributor or$N$e$d$e$r$m$a$n$ if uncertainties arise
when scrapping the product at the end of its service
life.
f the Airflow Alarm Kit needs to be removed, the
sensor hole in the duct should be sealed. f hazardous
dust is likely to be present, suitable precautions must
be taken such as the use of goggles, dust mask and
gloves.
18

Airflow Alarm Kit
10 Control protocol for Airflow Alarm
Copy the control protocol, fill it in and save it as a service record.
NOTE!
f a value is outside its accepted level, or a result is incorrect or missing, fix the problem before initial star-
tup and normal operation.
Monitoring
point Work-
places
covered by
t e monit-
oring
Adjust-
ment date Adjusted
by Airflow
planned V0
Static va-
cuum at V0
Alarm limit
setting
Company
Date Sign
EN
19

Airflow Alarm Kit
DA
Dansk
Brugervejledning
Ind oldsfortegnelse
Figurer ............................................................................................................................................................................. 6
1 Forord .............................................................................................................................................................................. 21
2 Sikkerhed ........................................................................................................................................................................ 21
2.1 Klassificering af vigtige oplysninger .............................................................................................................. 21
3 Beskrivelse ..................................................................................................................................................................... 21
3.1 Tiltænkt anvendelse ......................................................................................................................................... 21
3.2 Funktion ............................................................................................................................................................... 21
3.3 Hoveddele ........................................................................................................................................................... 21
3.3.1 Airflow Alarm-kontrolboks ................................................................................................................ 21
3.4 Tekniske data ...................................................................................................................................................... 22
4 nstallation ...................................................................................................................................................................... 23
4.1 Kontrolboks ......................................................................................................................................................... 23
4.2 Elektriske tilslutninger ...................................................................................................................................... 23
4.3 Overvågningspunkt ........................................................................................................................................... 23
4.4 gangsætning ...................................................................................................................................................... 23
4.4.1 Justering ................................................................................................................................................ 23
5 Anvendelse ..................................................................................................................................................................... 24
5.1 Styreboksens LED'er og kontrollamper .......................................................................................................... 25
6 Vedligeholdelse ............................................................................................................................................................. 26
7 Fejlfinding ....................................................................................................................................................................... 27
8 Reservdele ...................................................................................................................................................................... 28
8.1 Bestilling af reservedele ................................................................................................................................... 28
9 Genbrug ........................................................................................................................................................................... 28
10 Kontrolprotokol for Airflow Alarm .............................................................................................................................. 29
20
This manual suits for next models
8
Table of contents
Languages:
Popular Measuring Instrument manuals by other brands

COLOGICX
COLOGICX PROTOGEN EGCP-03 user manual

PureAire
PureAire Air Check O2 KF-25 instruction manual

National Instruments
National Instruments NI 5731 Series USER GUIDE AND SPECIFICATIONS

Dwyer Instruments
Dwyer Instruments CSG user guide

Level Sense
Level Sense Pro user manual

ACO
ACO 3116 instruction manual