NewPwr S-FLP Series User manual

S-FLP Series
The Tubular Parallel Form Structure
Surge Protective Devices
Website: http://www.anpe.cn
Service Tel: +86(25)-84459479
Address: New Power industrial Park, Luhe Economic Development Zone, Nanjing, China
Postcode: 211500
Nanjing New Power Electric Co., Ltd.
604100503000303
XX X X X X .X
Explosion proof:blank:Non explosion proof type
Types FL: :lightning protection
Ex:Explosion proof type
Protected mode:blank:floating
G:grounding
Voltage:5:5 V DC; 24:24 V DC
Input channel:2:2-wire; 3:3-wire
4:4-wire; 2D:dual channel
4P:4-wire parallel
2S:2-wire series; 3S:3-wire series
2P:2-wire parallel; 3P:3-wire parallel
Structure:T:12.4 mm module insert
S:7.4 mm; P :field installation
Series S: :S series SPD
Field Control room
Field
devices
(transmitter)
S series
surge
protective
devices
Equipotential connection drawing
Connection diagram
S series
surge
protective
devices
Control
room
devices
(DCS or
PLC)
èApplications
S-FLP series Form structure SPD is used to protect signals
and control equipments, preventing interference caused by
lightning or high voltage switch. In a short surge impact, by
discharging the transient current to the ground to clamp the
voltage in a safe level and ensure the transmission. It
guarantees the safety for industrial automation equipment.
This product is a 304 stainless steel shell, hybrid circuit
design with the advantages of strong surge shock resistance.
Moreover, it is easy to use and install, can be used with the
transmitter, flowmeter, etc.
èGrounding
It is necessary to ground the SPD correctly. Each SPD
should be grounding by DIN rail.
èExplosion protection parameters
Parameters certified by China National Quality Supervision
and Test Centre for Explosion Protected Electrical Products
(CQST):
Explosive-proof grade: Ex ia ⅡC T6 Ga
Explosion proof parameters: (please see the explosion-
proof certificate for details)
Type
Parameter
V Un
Max.continuous voltage Uc (AC)
oltage
Max.continuous voltage Uc (DC)
Impulse current limp(10/350 μs
Total discharge current C2
Discharge current per path In(8/20 μs, C2)
)
In(8/20 μs, )
Voltage protection Up(8/20 μs, C2)
Bandwidth fG(100 Ω resistance)
Intrinsically safe circuit certification
Response time Ta
Temperature
Thread size(match)
Installation
Grounding mode
Output wire size
Material
Protection degree
S-FLP-2P-24.Ex S-FLP-3P-24.Ex S-FLP-4P-24.Ex
24 V
32 V
22.5 V
2 kA
20 kA
10 kA
24 V
32 V
22.5 V
2 kA
20 kA
10 kA
24 V
32 V
22.5 V
2 kA
20 kA
10 kA
L-L ≤ 60 V/L-PE ≤ 650 V
10 MHz
L-L ≤ 60 V/L-PE ≤ 650 V
10 MHz
L-L ≤ 60 V/L-PE ≤ 650 V
10 MHz
Ex d ia IIC T6 Ga
<1ns
-40 ℃~80
M20×1.5, 1/2" NPT, 3/4" NPT etc. (Pin thread)
parallel form structure
connecting lead
2
1.5 mm , length 250 mm, Multiple lines to soft or hard, wear-resistance
304 stainless steel
IP67
IIC Gb, Ex
℃
RD
S-FLP-2P-24.Ex
S-FLP-3P-24.Ex
S-FLP-4P-24.Ex
BK
GNYE
RD
BK
BU
GNYE
RD
BK
BU
BN
GNYE
GND
EX cable gland
transmitter
èStandards
IEC 61643-21/GB 18802.21; IEC 60079-4/GB 3836.4
IEC 62305-1~IEC 62305-5; IEC 61508-1~IEC 61508-7
èModel description
èFeatures
m2-wire, 3-wire, 4-wire;
mMultiple protection circuit, strong resistance to surge;
mM20 × 1.5 etc (match);
mField parallel install module;
m304 stainless steel shell;
mApply to 0 ~ 24 V measurement and control system.
èParameters
èWiring diagram

èSupplements
mThe apparatus must be installed, connected and
adjusted by qualified personnel in non-hazardous area
according with the instruction manual.
mIf faults cannot be eliminated, the apparatus must be
taken out of operation and protected from being placed
in service again inadvertently.
mThe operator must strictly comply with the relevant local
safety standards and guidelines.
mIf there is any content difference between the
specification and the website or sample, the instructions
shall prevail. We reserve the rights to change or update
the product information without prior noticing the users.
Website: http://www.anpe.cn
Service Tel: +86(25)-84459479
Address: New Power industrial Park, Luhe Economic Development Zone, Nanjing, China
Postcode: 211500
èCheck
RD wire←→BK wire
BU wire←→BN wire
RD wire, BK wire, BU wire, BN wire ←→GNYE wire
When 1 Ω or less,
è
Attention
m
The devices degree of protection is IP65. It is suitable for
installed in indoor.
m
The devices were designed for use in pollution degree 2
and overvoltage category III as per IEC/EN 60664-1. If
used in areas with higher pollution degree, the devices
need to be protected accordingly.
m
Installation position shall not be affected by strong
mechanical vibration; impact and electromagnetic
induction from signal terminal and power supply, should
conformity with the requirements on electromagnetic
interference resistance of products in Class 3 industrial
field atmosphere stipulated in IEC 61000-4; the
atmosphere shall be free from gases that are corrosive to
metal and plastic components.
mBefore installation, please check the surge protector is
intact or not. If have any damage, it should not be
installed.
mOnly using the SPD according to this document, if more
than the rated value, SPD and other device are likely to
be damaged.
m
Devices must only be repaired directly by the
manufacturer. Tampering with the apparatus is dangerous
and therefore forbidden.
èDimension
.................
NOTE: Please match thread size before order.
èInstallation
mInstallation steps are as follows:
Installation
SPD as shown in the above steps 1: aim at the transmitter
devices such as internal thread, as shown in step 2:
clockwise, until tighten SPD.
2
NOTE:Wire Size, 1.5 mm , length: 250 mm.
S-FLP-2P-24.Ex
2-wires
Input signal +
-
S-FLP 2P 24.Ex- -
S-FLP-4P-24.Ex
4-wires
+
-
S+
S-
S-FLP 4P 24.Ex- -
RD
BK
GNYE
3-wires S-FLP-3P-24.Ex
+
-
S
S-FLP 3P 24.Ex- -
Input signal RD
BK
BU
GNYE
Input
signal
RD
BK
BU
BN
GNYE
24mm
20mm
75mm
1/2"NPT
PG13.5
M20x1.5
1
2
measure
Ω
replace
604100503000303
èConnections
Type
S-FLP 2P-24.Ex
S-FLP-3P-24.Ex
S-FLP-4P-24.Ex
-Ui=30 V DC,
Ui=30 V DC, Ii=33 mA, Ci=0 μF, Li=0 mH, Pi=0.24 W
Ui=30 V DC, Ii=25 mA, Ci=0 μF, Li=0 mH, Pi=0.18 W
Ii=50 mA, Ci=0 μF, Li=0 mH, Pi=0.375 W
Intrinsically safe parameter
This manual suits for next models
3
Popular Surge Protector manuals by other brands

Belkin
Belkin RESOURCE F5C510 Important safety instructions

AMX
AMX NXA-MPS16F Specifications

Superior Electric
Superior Electric STABILINE PT2 Series Installation, operation and maintenance manual

SC&T
SC&T SP001VP user manual

Elk Products
Elk Products ELK-950 Connection guide

DataComm Electronics
DataComm Electronics 45-0041-WH Instruction/installation sheet