manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Leviton
  6. •
  7. Surge Protector
  8. •
  9. Leviton 51120-1 User manual

Leviton 51120-1 User manual

This manual suits for next models

1

Other Leviton Surge Protector manuals

Leviton 52412-DS3 User manual

Leviton

Leviton 52412-DS3 User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton SmartlockPro GSIA2 User manual

Leviton

Leviton SmartlockPro GSIA2 User manual

Leviton R Series User manual

Leviton

Leviton R Series User manual

Leviton 57000-M3S User manual

Leviton

Leviton 57000-M3S User manual

Leviton 57000 Series User manual

Leviton

Leviton 57000 Series User manual

Leviton 51120-3R User manual

Leviton

Leviton 51120-3R User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 5480 User manual

Leviton

Leviton 5480 User manual

Leviton 51240-WM User manual

Leviton

Leviton 51240-WM User manual

Leviton 3812 User manual

Leviton

Leviton 3812 User manual

Leviton 51015-WM User manual

Leviton

Leviton 51015-WM User manual

Leviton 51005-WM User manual

Leviton

Leviton 51005-WM User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 47120-7 User manual

Leviton

Leviton 47120-7 User manual

Leviton 3880-DIN User manual

Leviton

Leviton 3880-DIN User manual

Leviton 51005-WM User manual

Leviton

Leviton 51005-WM User manual

Leviton 51110-PTC User manual

Leviton

Leviton 51110-PTC User manual

Leviton 51020-WMT User manual

Leviton

Leviton 51020-WMT User manual

Leviton 52000 Series User manual

Leviton

Leviton 52000 Series User manual

Leviton 3862-CON User manual

Leviton

Leviton 3862-CON User manual

Leviton 3803-MOD User manual

Leviton

Leviton 3803-MOD User manual

Leviton 50240-MSA User manual

Leviton

Leviton 50240-MSA User manual

Leviton 5280 User manual

Leviton

Leviton 5280 User manual

Popular Surge Protector manuals by other brands

Philips Theatre Director SPP4200WA/17 Owner's manual & warranty

Philips

Philips Theatre Director SPP4200WA/17 Owner's manual & warranty

M-system MMA instruction manual

M-system

M-system MMA instruction manual

CyberPower CSP600WSU user manual

CyberPower

CyberPower CSP600WSU user manual

UTP BALUN SP-VD08 user manual

UTP BALUN

UTP BALUN SP-VD08 user manual

ELAC ProteK PR91-W Setup guide

ELAC

ELAC ProteK PR91-W Setup guide

Tsubaki TSM4000M1 instruction manual

Tsubaki

Tsubaki TSM4000M1 instruction manual

CyberPower B1006T user manual

CyberPower

CyberPower B1006T user manual

QVS PP134C Specification sheet

QVS

QVS PP134C Specification sheet

Davis Instruments Radio Surge Protector user guide

Davis Instruments

Davis Instruments Radio Surge Protector user guide

CyberPower B300WRC1 user manual

CyberPower

CyberPower B300WRC1 user manual

M-system MGD-24 instruction manual

M-system

M-system MGD-24 instruction manual

Panamax MAX 5400-EX owner's guide

Panamax

Panamax MAX 5400-EX owner's guide

OBO Bettermann ÜSM-20-230I1PE65 installation instructions

OBO Bettermann

OBO Bettermann ÜSM-20-230I1PE65 installation instructions

CyberPower CSP604T user manual

CyberPower

CyberPower CSP604T user manual

CyberPower CSP706T user manual

CyberPower

CyberPower CSP706T user manual

Mitsubishi Electric LITOL LTM-125RF manual

Mitsubishi Electric

Mitsubishi Electric LITOL LTM-125RF manual

Intermatic PS3000 installation instructions

Intermatic

Intermatic PS3000 installation instructions

Siemens SICROWBAR 7VV3003 operating instructions

Siemens

Siemens SICROWBAR 7VV3003 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

INSTALLATION
WARNINGS & CAUTIONS:
• TOBEINSTALLEDAND/ORUSEDINACCORDANCEWITHELECTRICALCODESANDREGULATIONS.
• INSTALLATIONOFCAT.NOS.51120-1AND51120-3SPDDEVICESINABRANCHCIRCUITMUSTBEDONEBYANELECTRICIAN.
• READALLINSTRUCTIONSBEFOREINSTALLING.
• CAT.NOS.51120-1AND51120-3SPDDEVICESMUSTBEINSTALLEDONALINETHATISSERVEDBYDISCONNECTMEANS,SUCHAS20-AMPCIRCUITBREAKERSOR20-AMP
FUSEDDISCONNECTSWITCHES.
• SPDMAYNOTSURVIVESUSTAINEDOVERVOLTAGES.
• USETHISDEVICEONLY WITH COPPER OR COPPER CLAD WIRE.
FEATURES:
• UL1449Listed-Type2SPD
• IEEEC62.41-1991categoryA&Bcombinationwavesuppression
• Solid-statesemiconductorSPDcircuitryforeachphase
• Eachphaseindependentlyfused
• GreenLEDdiagnosticindicatorforeachphase
• NEMA1metalenclosure
• Pre-punchedstandardknockouts
• Interiorplasticcircuitenclosureforaddedsafety
• Flushmountingenclosure
ForsuperiorlocalSPDprotection,useLevitonSurgeSuppressionOutletstoprotectagainstinternally-generatedtransientsbetweenthebranchpanelandthepointofuse.
DESCRIPTION:
Leviton’sCatalogNos.51120-1(120/240V,single-phaseversion)andthe51120-3(120/208V,3-phaseversion)BranchPanelMountedSPDdeviceshavebeendesignedtoprotect
residentialandsmallcommercialestablishmentsfromhighvoltagetransients.ThestandardJ-Boxmetalenclosurewithpre-punchedstandardsizeknockoutssimpliesush
mountingintypicalframeconstructionenvironments,andprovidesconvenientconnectionmeanstoexistingbranchpanels.
TO INSTALL:
System Voltage Requirements
1. Measurepanelvoltage,L-N,todeterminethesystemvoltage.SystemvoltagemustnotexceedthespeciedmaximumcontinuousRMSvoltageontheSPDdevicelabel.
Location and Mounting
1. LocatetheSPDdeviceascloseaspossibletothebranchcircuitbreakerpanel.ConnectionleadlengthbetweentheSPDdeviceandcircuitbreakerboxshouldbeminimalfor
bestprotection.ThelocationshouldalsopermitgoodvisibilityoftheSPDdevice’sdiagnosticlights.
2. Removethecircuitbreakerpanelcoveranddeterminethebreaker-panelwiringentrypointrelativetochosenlocationoftheSPDdevice.
NOTE:SincethecircuitbreakerpanelandtheSPDunithaveoverlappingcovers,installationshouldallowatleastoneinchofclearancefromtheedgeofthecircuitbreaker
panelcover.
3. Forsurface-mountcircuitbreakerpanels,theSPDdevicemaybeconnectedusingrigidconduittoanyconduitknockouthole.
4. Fornon-surfacemountinstallations,securetheSPDtothesupportstudinthewallbycuttinga6x6-inchmountinghole.
5. RemoveSPD’scoverandconnect3/4-inchexibleorrigidconduitbetweencircuitbreakerboxandtheSPD.
6. PlacetheSPDdeviceintothe6x6-inchmountingholeandsecureittotheexposedstuds.
Wiring Connections
TheSPDdeviceterminalblockaccepts4AWG–12AWGCOPPERWIREONLY.ForwirerangeSolidorStranded12AWGto10AWGuseTorque25in-lbs.For8AWGStranded
wireuse30in-lbs.ForStranded6AWG–4AWGuse35in-lbs.
1.
WARNING:TOAVOIDFIRE,SHOCKORDEATH,TURN OFF POWERATCIRCUITBREAKERORFUSEANDTESTTHATPOWERISOFFBEFOREWIRING!
2. Connectwireleadstoterminalblock:BLACKtoPHASES,WHITEtoNEUTRALandGREENtoGROUND.SeeFigures 1through4onreverseside.
CAUTION:Ifplasticconduitisused,Greengroundwiremustbeconnectedtogroundlug,andGreenwireinsideenclosuremustalsobeconnectedtogroundlug.Failuretodo
somayresultinreorshock.SeeFig. 1,Fig. 2,Fig. 3andFig. 4onreversesideforinstallationdiagrams.
3. ThreadtheSPDdevice’swireleadsthroughtheconduittocircuitbreakerinterior.
4. SecuretheSPDcoverwiththescrewsremovedpreviously.
5. Selectcircuitbreakersascloseaspossibletoeachserviceentrancelug.Twenty-Amp(20A)circuitbreakersarerecommended,andmayshareSPDdeviceandbranchcircuit
leads.ThebreakersprovideadditionalfailureprotectionaswellasaSPDconnectionandservicingdisconnect.
NOTE:DonotconnectSPDleadsdirectlytoserviceentrancelugs.Thismayresultinre,shockordeath.
6. Leadlengthsshouldbeasshortaspossible.ConnecttheBLACKleadstoeachPHASEthroughtheselectedcircuitbreakers.ConnecttheWHITEleadtoNEUTRALascloseas
possibletoNEUTRALentranceservicelug.
NOTE: Avoidlongloopsanddonotcoilextraleadwire.
7. Replacethecircuitbreakerpanelcover.Installationiscomplete.
Power ON
1. Restorepowertocircuitbreakerpanel.ThegreendiagnosticlightsontheSPDdeviceshouldturnON.
2. Ifduringnormaloperationadiagnosticlightshutsoff,haveanelectriciandetermineifphasepowerisapplied.Ifpowerispresent,thenatransientsurgehasexceededtheSPD
device’srating.Theunitshouldbereplacedand/orupgradedassoonaspossible.
BRANCH PANEL MOUNTED SURGE PROTECTIVE DEVICE (SPD)
Cat. Nos. 51120-1&51120-3
DI-000-51120-00E
©2010LevitonMfg.Co.,Inc. DI-000-51120-00E
120 V
120 V
240 V
120/240 V
1
Ø
51120-1
L1
N
L2
Suitable for use on a circuit capable of delivering no more than 10,000
rms symmetrical amperes, 120 volts maximum when protected by a 20
ampere circuit breaker rated 120 volts minimum. The interrupting rating of
the fuse or circuit breaker shall not be less than the available fault current.
FIGURE 1 - SINGLE-PHASE INSTALLATION
Suitable for use on a circuit capable of delivering no more than 10,000
rms symmetrical amperes, 120 volts maximum when protected by a 20
ampere circuit breaker rated 120 volts minimum. The interrupting rating of
the fuse or circuit breaker shall not be less than the available fault current.
208 V
208 V
120 V
120 V
120 V
208 V
L3
L2
L1
N120/208 V
3
Ø
51120-3
FIGURE 2 - THREE-PHASE INSTALLATION
G
L1
L2
N
20
20
20
20
40
20
20
20
20
40
Flexible Conduit
to J-Box
Circuit Breaker Panel
(Cover Removed)
51120-1
FIGURE 3 - SINGLE-PHASE WIRING
Flexible Conduit
to J-Box
Circuit Breaker Panel
(Cover Removed)
51120-3
G
L1
L2
L3
N
20
20
20
20
40
20
20
20
20
40
FIGURE 4 - THREE-PHASE WIRING
LIMITED LIFETIME WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benet of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under
normal and proper use during the lifetime of the product. Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if the product is returned prepaid, with proof of
purchasedate,andadescriptionoftheproblemtoLeviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, N.Y. 11747.Thiswarrantyexcludesand
there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened,
abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including
merchantabilityandtnessforaparticularpurpose.Levitonisnotliableforincidental,indirect,special,orconsequentialdamages,includingwithoutlimitation,damageto,orlossofuseof,anyequipment,
lost sales or prots or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call:
1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only)
www.leviton.com
ARTWORK PRINT SPECIFICATIONS
PART NUMBER REV DESCRIPTION
Line Screen:
Angle:
Resolution:
Offset Flexo
Other
Body Material:
Bindery
Thickness:
Trim
Perfect Bind
Die cut Saddle Stitch
Drill
Fold
The information in this document is the exclusive PROPRIETARY property of LEVITON MANUFACTURING COMPANY, INC. It is disclosed
with the understanding that acceptance or review by the recipient constitues an undertaking by the recipient. (1) to hold this information in strict
confidence, and (2) not to disclose, duplicate, copy, modify or use the information for any pupose other than that for which disclosed.
© 2010 Leviton Mfg. Co., Inc.
Unpublished, All Rights Reserved
PlantApprovals:
PN-ARN: Pilot Rev:ECO Number:
Artwork Release Date:
Artwork Print Specification Sheet Rev A06.eps
PMCQA
Artist:
Notes:
Other
Cust Other
S & A
Mktg Eng
FOR LEVITON USE ONLY
SPECIFICATIONS :
PROCESS :
MANUAL INTERIORS / BINDERY / FOLD SCHEME :
COMMENTS :
For manuals - designates cover specifications
Dimensions:
Material:
Thickness:
Finish:
:
Spot
CMYK
1:
4:
3:
2:
Color(s): over
1:
4:
3:
2:
Fonts:
Spot
CMYK
1:
4:
3:
2:
Color(s): over
1:
4:
3:
2:
Fonts:
CI0054-3154
H Sanchez
Black Helvetica
1 1
FOLD SCHEME / BINDERY DIAGRAM
Fold Line
Die Cut Punch/Drill Hole
Part No.
DI-000-51120-00E
01 C. Clemente
C. Corona
J. Rhinestine T. Pulsonetti
10/13/10
11" x 8.5"
20 lb.
Offset
Instruction sheet
8.5"
11"
Part No. 8.5"
5.5"
FINAL
V. Lonigro